DEV_SOIL_7IN1 — 7-in-1 RS485 soil sensor

DEV_SOIL_7IN1 — 7-in-1 RS485 soil sensor

Reads a 7-in-1 soil probe on Modbus RTU: moisture, temperature, conductivity
(EC), pH, nitrogen, phosphorus and potassium.

Pins

Pin Type Default What to wire
in-out Node MODBUS_NODE The RS485 line's node, as a client
in-out Data DEV_SOIL_DATA Settings and status (below)
in Enable BOOL TRUE Read the sensor
out Good BOOL Answering, every value plausible
out Moisture REAL % (as the sensor reports it)
out Temperature REAL °C, negative below zero
out Ec REAL µS/cm
out Ph REAL pH
out Nitrogen REAL mg/kg
out Phosphorus REAL mg/kg
out Potassium REAL mg/kg

Data (DEV_SOIL_DATA)

Field Type Default Meaning
unit USINT 1 The sensor's Modbus address, 1..247 (factory 1)
map DEV_SOIL_MAP DEV_SOIL_JXCT Its register map (below)
every TIME T#10s Read it this often (at least 1 s)
status DEV_STATUS Status code (see the README)
statusText STRING(30) Status in words
age TIME Time since the last good reading

Wiring and line settings

  • RS485 A/B to the line; the probe's supply as its label says (usually 5–30 V DC).
  • The common sensor: 9600 baud, 8N1 (SERIAL_PARITY := MODBUS_PARITY_NONE_8N1),
    factory address 1. Several probes share one line at different addresses.

Register maps (Data.map)

Makers differ, so the map is a setting.

Map Registers (holding, FC03) Scaling
DEV_SOIL_JXCT (default) — JXCT JXBS-3001 and most generic units pH 0x0006; moisture 0x0012, temperature 0x0013; EC 0x0015; N P K 0x001E–0x0020 pH ÷100, moisture and temperature ÷10
DEV_SOIL_LINEAR moisture, temperature, EC, pH, N, P, K at 0x0000–0x0006 pH ÷10, moisture and temperature ÷10

Check the map against your sensor's sheet before installing. A wrong map
never shows plausible numbers: the sensor refuses the addresses (No reply) or
the values are impossible (Bad data).

How it works

  • Plausible: moisture 0–100 %, temperature −40–80 °C, pH 0–14, EC 0–20000 µS/cm,
    N P K 0–2000 mg/kg. Anything outside is Bad data and Good drops.
  • The outputs hold the last good reading while Good is FALSE; Data.age says how old it is.
  • A sensor that stops answering backs off (up to 16 × every) before it is asked
    again, so after a cable is fixed it can take that long to show OK.
  • Power cut: nothing is kept; the outputs are 0 until the first good reading.