UT_INTERLOCK — Interlock / permissive list with first-out and bypass

UT_INTERLOCK — Interlock / permissive list with first-out and bypass

Collects all the conditions that must be healthy before a device may run (guards,
pull cords, levels, pressures, upstream running…) into one Ok signal for the
device's Interlock or Permissive pin. It records which condition tripped first
(first-out) and allows controlled maintenance bypasses.

Pins

Pin Type Default What to wire
in BypassEnable BOOL FALSE Key switch / HMI permission that lets bypasses take effect. Always wire it (FALSE if bypasses are never allowed)
in Reset BOOL FALSE Rising edge: clear the first-out and the held conditions
out Ok BOOL All conditions OK (or bypassed) → device Interlock/Permissive
out FirstOut INT Position of the first condition to stop it since the last reset (0 = none)
out Bypassed BOOL At least one bypass is in effect (show it on the HMI!)
out NotOkCount INT Conditions holding Ok FALSE
inout Conditions ARRAY[*] OF UT_INTLK_COND One element per condition, any length
inout Data UT_INTLK_DATA

Condition slot UT_INTLK_COND

Field Type Default Who writes it Meaning
ok BOOL TRUE you Condition healthy
delay TIME T#0s you Must be not OK this long to count (filter)
reset UT_RESET_MODE UT_RST_AUTO you AUTO: OK again as soon as healthy. MANUAL: stays out until a reset (pull cord, e-stop). RETRY acts as MANUAL
bypass BOOL FALSE you / HMI Request a bypass (only effective with BypassEnable)
bad BOOL block Not OK now (before the delay)
tripped BOOL block Counts against Ok (after the delay, or held); still shown while bypassed
latched BOOL block MANUAL: held until a reset
bypassed BOOL block The bypass is in effect
badFor TIME block How long it has been not OK
bypassFor TIME block How long the bypass has been in effect
delayLeft TIME block Not OK and still within its delay: the time until it counts (0 otherwise)
bypassLeft TIME block Bypass in effect: the time until it drops out (0 = no bypass, or bypassTimeout 0)

Record UT_INTLK_DATA

Field Type Default Meaning
bypassTimeout TIME T#8h A bypass drops out after this (0 = never)
cmdReset BOOL FALSE HMI reset: acts once, on its rising edge (cleared by the block)
ok, firstOut, bypassed, notOkCount status, as the pins
trips UDINT status: times Ok went FALSE (not kept over a power cut)
configBad BOOL status: a setting is invalid (a warning, see Bad settings)
statusCode UT_STATUS status: what holds Ok FALSE, or a bypass in effect, or OK (see Status codes)
faultId UT_FAULT status: UT_F_CONDITION when the status is about a condition (statusCond), the setting for a bad setting, else UT_F_NONE
statusText STRING(30) status: statusCode and faultId in words, e.g. Blocked: interlock
timeLeft TIME status: the countdown the status shows (a bypass's time left, or a condition's delay left); 0 when it shows none
statusCond INT status: the condition the status is about, by its position from 1 (0 = none)

How it works

  • Ok is FALSE while any condition is tripped and not bypassed, and always with no
    conditions at all (an empty array: a config fault, configBad).
  • Delay. A condition counts once it has been not OK for its delay, timed from
    the scan it was first seen. A loss shorter than that, or a chattering input, never counts.
  • Reset. Reset or cmdReset, each on its rising edge, clears the first-out and
    releases MANUAL conditions that are healthy again. A condition that is still not
    OK stays out: the reset is refused, not remembered. A reset held on (a stuck
    button, a Modbus coil left on, a debugger force) acts once: a pull cord pulled again
    stays out until a new reset.
  • First-out is the first condition to stop it since the last reset. Several at
    once: the lowest position. After a reset with conditions still out: the lowest of
    those. It counts positions from 1, whatever the array's lower bound, so declare the
    array from 1 and FirstOut is the index.
  • Bypass. bypass takes effect only while BypassEnable is TRUE. It drops out
    after bypassTimeout, and stays out until the request or BypassEnable goes FALSE
    and back. Bypassed shows any bypass in effect, even on a healthy condition. A
    MANUAL condition still latches while bypassed; reset it before removing the bypass.
  • Every condition keeps its own timing in its element, so the array can be any length
    and the block has no fixed limit.

Status codes

statusCode / faultId / statusText say why Ok is FALSE, or what to watch while
it is TRUE, and statusCond says which condition. The most important wins: config >
blocked > bypassed or a bad setting > OK. It names the lowest condition holding Ok
FALSE now
(not the first-out, which stays until a reset), by its position from 1.
Name the conditions on the HMI, by position. statusText changes only when the code
or faultId changes.

statusCode faultId statusText When
UT_ST_OK UT_F_NONE OK All conditions healthy
UT_ST_OK UT_F_CONDITION OK Condition statusCond is not OK but still within its delay (timeLeft: the time until it counts)
UT_ST_INTERLOCK UT_F_CONDITION Blocked: interlock Condition statusCond, the lowest holding Ok FALSE, is not OK now
UT_ST_RESET_NEEDED UT_F_CONDITION Waiting: reset It is healthy again but MANUAL: a reset releases it
UT_ST_BYPASSED UT_F_CONDITION Bypassed A bypass in effect (the lowest, statusCond); timeLeft the time until it drops out (0 with bypassTimeout 0)
UT_ST_WARN_SETTING UT_F_BYPASS_TIMEOUT Setting: bypass timeout bypassTimeout negative (see Bad settings)
UT_ST_WARN_SETTING UT_F_CONDITION Setting: condition Condition statusCond has a negative delay or an unknown reset
UT_ST_CONFIG UT_F_NO_CONDITIONS Config: no conditions An empty array: Ok is always FALSE

Using it

|--[ GuardClosed ]----------------( Crusher[1].ok )--|
|--[ PullCordHealthy ]------------( Crusher[2].ok )--|
|--[ Conveyor2.Running ]----------( Crusher[3].ok )--|
CrusherIntlk(BypassEnable := MaintKey, Reset := ResetPB, Conditions := Crusher, Data := CrusherIntlkData);
Crusher1(AutoCmd := StartChain.Step3, Interlock := CrusherIntlk.Ok, Data := Crusher1Motor);

Bad settings

Invalid settings warn (configBad) and fall back to the safe side: a negative
bypassTimeout allows no bypass at all; a negative condition delay acts at once (as 0);
an unknown reset holds the condition until a reset (as MANUAL).