UT_MOTOR_REV — Reversing starter

UT_MOTOR_REV — Reversing starter

A forward and a reverse contactor that are never on together, with a dead time
(reversalDelay) so the motor stops before it changes direction. Everything else
(modes, interlocks, protection, faults, restart rules) is the same as
UT_MOTOR.

Pins

Pin Type Default What to wire
in AutoCmd BOOL FALSE Run request from your logic (Auto)
in AutoReverse BOOL FALSE Direction in Auto: FALSE = forward, TRUE = reverse
in FeedbackFwd BOOL FALSE Forward contactor aux
in FeedbackRev BOOL FALSE Reverse contactor aux
in Overload BOOL FALSE Overload relay tripped (TRUE = tripped; a NC aux through NOT at the pin)
in Thermistor BOOL FALSE PTC relay / thermal switch tripped (a NC contact through NOT at the pin)
in DriveFault BOOL FALSE Soft-starter fault relay
in Current REAL 0.0 Motor current in amps (used if fullLoadCurrent > 0)
in Interlock BOOL TRUE FALSE stops the motor in every mode
in Permissive BOOL TRUE FALSE blocks starting only
in SwHand / SwAuto BOOL FALSE Selector switch (if modeSource uses it)
in LocalFwd BOOL FALSE Local forward pushbutton (Hand): runs it forward
in LocalRev BOOL FALSE Local reverse pushbutton (Hand): runs it in reverse
in LocalStop BOOL FALSE Local stop pushbutton (TRUE = pressed; a NC button through NOT at the pin)
in Reset BOOL FALSE Reset for MANUAL protections (rising edge)
out RunFwd BOOL Forward contactor
out RunRev BOOL Reverse contactor (never on with RunFwd)
out Running BOOL Run confirmed by feedback (stays on through a reversal)
out Fault BOOL A trip is holding it off
out Warning BOOL A protection set to warn is active
out Ready BOOL Would start now if asked: healthy, permitted, in Auto or Hand, not waiting out restartDelay (stays TRUE while running)
out Auto BOOL In Auto mode
out State UT_STATE For HMIs
out Reversed BOOL Running in reverse
inout Data UT_MOTOR_DATA Shared motor record (UT_MOTOR)
inout Rev UT_MOTOR_REV_DATA The reversing settings, commands and status (below)

Always wire the contactors' NC auxiliaries as a hardware interlock as well. The
block never turns both on, but only the wiring stops a welded contactor.

Record UT_MOTOR_REV_DATA (pin Rev)

Field Type Default Meaning
reversalDelay TIME T#2s Dead time between one direction switching off and the other switching on (negative: 0 is used, with a config warning wrnConfig)
changeover UT_PROTECTION TRIP · 0 · MANUAL Contactor feedback wrong for the sequence (faultCode bit 9, below)
cmdFwd / cmdRev BOOL FALSE Hand: run forward / run in reverse (each acts once, on its rising edge, then cleared: one held TRUE acts once)
reverse (status) BOOL The reverse contactor is on

Everything else (modes, protections, cmdStart / cmdStop, status) is in the motor
record Data.

How it works

  • Direction. Auto: AutoReverse. Hand: cmdFwd / LocalFwd run it forward,
    cmdRev / LocalRev run it in reverse; each starts it as well. cmdStart starts
    it in the direction chosen last. Forward and reverse pressed together do nothing.
    The direction commands are ignored (and cleared) in Off and Auto. Switching
    Auto → Hand keeps the direction it was running in.
  • Changing direction while running: the running contactor goes off at once, the
    dead time runs, then the other contactor comes on. The motor stays requested the
    whole time, so Running stays on, a permissive does not stop it, and the restart
    delay does not apply. If the request goes back to the old direction during the dead
    time, that contactor comes straight back on.
  • Starting after a stop: the same direction starts at once; the other direction
    waits until reversalDelay has passed since the last contactor went off (the motor
    may still be turning).
  • After a power-up either direction waits reversalDelay first, because the motor
    may still be turning.
  • With feedback supervised (useFeedback, not in simulate), the new direction
    also waits until the other contactor's aux shows open. With reversalDelay = T#0s
    there is still at least one scan with both off, and the new direction waits for the
    old contactor to drop out.
  • Changeover protection (changeover, bit 9, TRIP · MANUAL by default) trips when
    both auxes show closed, when the aux of the direction that is off shows closed while
    the other direction is on, or when a contactor switched off for a reversal still
    shows closed after stuck.delay (the new direction is never switched on into it).
    A contact that stays closed at standstill is the welded-contactor protection
    (stuck), as on UT_MOTOR.
  • If the new direction's aux does not confirm after a reversal, feedbackLost
    trips; if the motor never had feedback, noFeedback does.

Status

statusCode, faultId and statusText say the one main thing the motor is
doing, or what holds it back, so a technician can see on the HMI why it is not
running without opening the program. A motor asked to run that is not running
always shows a held, fault or configuration status. The most important reason wins:
configuration > fault > held / waiting > warning > running > idle. A warning shows
over "Running" so it is seen. The time that goes with a status is in timeLeft.
The text is rebuilt only when the status or the fault changes. The numbers are in
conventions.

statusCode Words When
UT_ST_OFF Off Mode Off
UT_ST_IDLE Idle Auto with nothing asking it to run
UT_ST_RUN_AUTO Running: Auto
UT_ST_RUN_HAND Running: Hand With handMaxRun: timeLeft is the time left
UT_ST_STARTING Starting Run given, run feedback not yet in
UT_ST_STOPPING Stopping Stopped, run feedback still on
UT_ST_RUN_GROUP Running: group A group (UT_DUTY, UT_PUMP_CASCADE) runs it; grpRank is its place
UT_ST_RESTART_DELAY Waiting: restart delay Asked to run, restartDelay not over yet (timeLeft counts down)
UT_ST_INTERLOCK Blocked: interlock Interlock FALSE (every mode but OOS)
UT_ST_NOT_PERMITTED Not permitted Permissive FALSE while stopped, in Hand or Auto
UT_ST_HAND_PRESS_START Hand: press start Hand and stopped: no start given, or it was dropped (a stop, a trip, the interlock, not permitted)
UT_ST_WAIT_GROUP Waiting: turn in group A group owns it and does not run it now
UT_ST_HAND_MAX_RUN Hand: max run, press start handMaxRun ended the Hand run
UT_ST_MUST_CYCLE Waiting: command must cycle After a MANUAL reset, or a local stop in Auto: AutoCmd must go off and on
UT_ST_OOS Out of service
UT_ST_DEAD_TIME Waiting: dead time (this block) Changing direction (or starting the other way): both contactors off for reversalDelay; timeLeft counts down
UT_ST_WAIT_OPEN Waiting: contactor to open (this block) The other direction's contactor aux still shows closed
UT_ST_WARNING Warning: <fault> A protection set to WARN is raised, or Current is NaN or infinite while a current level is in use (UT_F_CURRENT_BAD, current signal)
UT_ST_WARN_SETTING Setting: <setting> An invalid setting, a safe value in use (settings below)
UT_ST_FAULT Fault: <fault> Tripped, AUTO: clears by itself once the cause has gone for recover (timeLeft while it counts)
UT_ST_FAULT_RETRY Retrying: <fault> Tripped, RETRY: the protection's retries of maxRetries (timeLeft while it counts)
UT_ST_FAULT_RESET Latched: <fault> Tripped, MANUAL: a reset (pin, cmdReset, Off) once the cause has gone
UT_ST_FAULT_LOCKED Locked: <fault> RETRY used up: now as MANUAL
UT_ST_CONFIG Config: <setting> An invalid setting keeps the motor off

<fault> is faultId, one of: UT_F_OVERLOAD (overload) · UT_F_MOTOR_HOT (motor
too hot) · UT_F_NO_FEEDBACK (no run feedback) · UT_F_FEEDBACK_LOST (feedback
lost) · UT_F_WELDED (contactor welded) · UT_F_CURRENT_HIGH (current high) ·
UT_F_CURRENT_LOW (current low) · UT_F_DRIVE (drive fault) · UT_F_SPEED_DEV
(speed deviation) · UT_F_CHANGEOVER (changeover) · UT_F_DRIVE_NOT_READY (drive
not ready).
<setting> is one of: UT_F_FLC (full load current) · UT_F_CURRENT_NEEDS_FLC
(current needs FLC) · UT_F_START_MASK (start mask) · UT_F_RESTART_DELAY (restart
delay) · UT_F_HAND_MAX_RUN (hand max run) · a protection's name (its delay,
recover or maxRetries).
This block adds the setting UT_F_REVERSAL_DELAY (reversal delay, negative) and uses UT_F_CHANGEOVER for its changeover protection.
The rows marked (this block) come from its own sequence and show from the scan after it changes.

Using it

Conv1(AutoCmd := Line.Run, AutoReverse := Line.Back, FeedbackFwd := K1_Aux, FeedbackRev := K2_Aux,
      Overload := Conv1_OL, LocalFwd := PB_Fwd, LocalRev := PB_Rev, LocalStop := PB_Stop, Data := Conv1Data,
      Rev := Conv1Rev);
K1 := Conv1.RunFwd;
K2 := Conv1.RunRev;