UT_RUN_LIMIT — A run limited by time or volume, or held by a remote signal

UT_RUN_LIMIT — A run limited by time or volume, or held by a remote signal

Runs a piece of equipment for a set time, until a set volume has gone through, or
for as long as a remote signal is held, and says why the run ended. Typical uses: an
effluent or irrigation run ("50 m³ or 2 h, whichever first"), filling a trough,
flushing a line, running a generator for a set time, a SCADA schedule that holds a
run signal.

RunCmd asks the equipment to run: wire it to a UT_PUMP's Demand (or a
motor's AutoCmd). The pump block still decides whether it is safe to run; this block
only decides how long.

Pins

Pin Type Default What to wire
in Start BOOL FALSE Rising edge: start a run (a local button, a SCADA start pulse). Wire FALSE if only RunHeld starts it
in Stop BOOL FALSE Rising edge: end the run
in RunHeld BOOL FALSE A remote run signal: its rising edge starts a run, dropping it ends the run
in Permit BOOL TRUE FALSE ends the run (Stopped: not permitted) and refuses a start
in Abort BOOL FALSE Ends the run and refuses a start, e.g. the sump low level or a pump fault
in AbortCode UT_STOP UT_STOP_NONE The endReason an Abort gives, e.g. UT_STOP_LOW_LEVEL (UT_STOP_NONE = UT_STOP_ABORTED, Stopped: aborted)
in Running BOOL TRUE The equipment really runs (the pump's Running): time only counts while TRUE, so a trip or a restart delay pauses the run. Unwired: always counts
in Volume REAL 0.0 A running total, e.g. UT_TOTALISER.Total: the run's volume is how much it rises
in CommsOk BOOL TRUE The remote link is up (e.g. NOT UT_WATCHDOG.CommsFail)
out RunCmd BOOL Run the equipment
out Active BOOL A run is in progress
out Done BOOL One scan: a run has ended (endReason says why)
out Elapsed TIME Running time counted in this run (kept after it ends)
out TimeLeft TIME byTime: running time still to go
out Delivered REAL Volume in this run (kept after it ends)
out VolumeLeft REAL byVolume: volume still to go
inout Data UT_RUN_LIMIT_DATA The run's settings and status (below)

Record UT_RUN_LIMIT_DATA

Field Type Default Meaning
byTime BOOL FALSE End the run when Elapsed reaches runTime
byVolume BOOL FALSE End the run when Delivered reaches targetVolume. Both: whichever comes first. Neither: it runs until stopped (a remote run)
runTime TIME T#1h byTime: the running time of a run
targetVolume REAL 0.0 byVolume: the volume of a run, in the unit of Volume
maxPause TIME T#0s End the run when Running stays FALSE this long (Stopped: paused too long). 0 = no limit
commsLostStops BOOL TRUE CommsOk FALSE ends a run that needs the remote to end it (RunHeld, or no limit), and a RunHeld rising edge while the link is down is ignored. A timed or metered run carries on
cmdStart / cmdStop BOOL HMI / SCADA: start / end a run (each acts once, on its rising edge, and is set back to FALSE)
active BOOL Status: a run is in progress
paused BOOL Status: active, Running FALSE: time is not counting
elapsed TIME Status: as Elapsed
timeLeft TIME Status: as TimeLeft
phaseTime TIME Status: time since the run started, pauses included (0 when idle)
pauseTime TIME Status: time in the current pause
delivered / volumeLeft REAL Status: as the pins
remoteHeld BOOL Status: the run needs the remote to end it (RunHeld, or no limit)
endReason UT_STOP Status: why the last run ended (below; UT_STOP_NONE = none since power-up). How far it got is in elapsed and delivered
lastVolume, lastDuration, lastEndReason REAL, TIME, UT_STOP Status: the last run's summary (volume, running time, why it ended), kept over a power cut
runs UDINT Status: runs ended since power-up
configBad BOOL Status: byTime with runTime not above 0, or byVolume with targetVolume not above 0 (or not a number): no start, a run in progress ends
statusCode UT_STATUS Status: what it is doing (below)
faultId UT_FAULT Status: the setting that is invalid (configBad): UT_F_RUN_TIME or UT_F_TARGET_VOLUME; else UT_F_NONE
statusText STRING(30) Status: the two in words
powerUp UT_RUN_POWERUP UT_RPU_RESUME What a run does after a power cut: UT_RPU_RESUME (0, the default: it carries on with what it had left) · UT_RPU_RESTART (a held run starts again from the beginning) · UT_RPU_NONE (nothing starts). See After a power cut. An unknown value acts as NONE
progressSave TIME T#1m RESUME: while a run is active its running time and volume are saved at most this often (and at its start and end). At most this much running is done again after a power cut. 0 = saved only at the start and end (a resumed run starts its count again)

End reasons

The shared reasons of conventions. The words carry
no numbers: how far the run got is in elapsed and delivered (lastDuration and
lastVolume for the last run), and the limits in runTime and targetVolume.

endReason Words (UT_STOP_TEXT) Why
UT_STOP_OPERATOR Stopped: operator Stop or cmdStop
UT_STOP_DONE Done The time or the volume was reached
UT_STOP_ABORTED Stopped: aborted Abort with AbortCode UT_STOP_NONE
UT_STOP_COMMS_LOST Stopped: comms lost CommsOk FALSE on a run the remote must end
UT_STOP_REMOTE_OFF Stopped: remote off RunHeld dropped
UT_STOP_NOT_PERMITTED Stopped: not permitted Permit went FALSE
UT_STOP_PAUSED_LONG Stopped: paused too long maxPause
UT_STOP_SETTING Stopped: setting invalid A limit made invalid while running
UT_STOP_POWER_CUT Stopped: power cut A run in progress at a power cut that does not carry on (RESTART, NONE). Reported at power-up
any its words Abort with your AbortCode, e.g. UT_STOP_LOW_LEVEL (Stopped: low level)

Status

statusCode Words When
UT_ST_IDLE Idle No run; endReason says how the last one ended
UT_ST_RUN_TIME Running: by time A timed run (timeLeft)
UT_ST_RUN_VOLUME Running: by volume A metered run, or one with both limits (delivered, volumeLeft)
UT_ST_RUN_REMOTE Running: remote held A run held by RunHeld (no limit)
UT_ST_RUN_UNTIL_STOP Running: until stopped A run with no limit
UT_ST_RESUMED Running: resumed The run carried on after a power cut (RESUME), in place of the statuses above
UT_ST_RESTARTED Running: restarted The run started again after a power cut (RESTART), in place of the statuses above
UT_ST_NOT_PERMITTED Not permitted RunHeld on, Permit FALSE
UT_ST_ABORT Blocked: abort RunHeld on, Abort on
UT_ST_WAIT_POWERUP Waiting: start again NONE: a RunHeld that would have run is on at power-up; it must go off and on again
UT_ST_PAUSED Paused: not running Active, Running FALSE (pauseTime)
UT_ST_CONFIG Config: run time · Config: target volume byTime with runTime not above 0, or byVolume with targetVolume not above 0: no run until fixed

How it works

  • A run starts on a rising edge of Start, cmdStart or RunHeld, if Permit is
    TRUE, Abort is FALSE and the settings are valid. A start while a run is active is
    ignored; Stop wins over a start in the same scan. A held Start acts once.
  • Time counts only while Running is TRUE: a pump trip or restart delay pauses the
    run, and it carries on when the pump runs again (maxPause can end it).
  • The volume is the rise of Volume since the start. A total that goes down (reset)
    or reads not-a-number is handled: the run carries on from the new value, never
    counting backwards. A total that is not a number when the run starts is not
    counted from 0: the run counts from the first valid reading.
  • The first reason found ends the run: Stop, Abort, Permit, RunHeld dropping, lost
    comms, an invalid setting, the limit, maxPause.

After a power cut

An irrigation run on a sports field or a property often has no operator: when the
power comes back (or the PLC is stopped and started) the run should carry on, as a
commercial irrigation controller does. powerUp chooses:

powerUp A run in progress at the cut RunHeld on at power-up, no run in progress
UT_RPU_RESUME (default) Carries on with the time and volume it had left (UT_ST_RESUMED). A run whose RunHeld was on at the cut and is off now ends: UT_STOP_REMOTE_OFF. A run started by Start / cmdStart just carries on Starts a fresh run
UT_RPU_RESTART Nothing is kept. A run started by RunHeld, with RunHeld still on, starts again from the beginning (UT_ST_RESTARTED); the run cut off is reported as UT_STOP_POWER_CUT. A run started by Start / cmdStart ends (UT_STOP_POWER_CUT) Starts a fresh run
UT_RPU_NONE Ends (UT_STOP_POWER_CUT) Nothing starts: UT_ST_WAIT_POWERUP until RunHeld goes off and on again
  • A RunHeld that was already on at the cut and had been dealt with (its run
    done, or the start refused) does not start another run after the power cut, in any
    mode: as without a power cut, it must go off and on again. Only a RunHeld that
    came on while the power was off counts as a new request.
  • A run that carries on keeps its running time and volume: time spent before the cut
    is not counted again, and the run never goes past runTime or targetVolume (a
    run already at its limit ends at once, Done). The volume carries on from where
    the Volume total reads at power-up, so a total that came back lower (a totaliser
    saved every 12 h) is not counted backwards.
  • The resumed run starts from its last save: the progress is saved when the run
    starts and ends, and every progressSave (default 1 min) while it is active, never
    every scan (flash wear: a few hundred saves on a day of irrigation, none when idle).
    So up to progressSave of running can be given again after a cut.
  • A run ended at power-up (UT_STOP_REMOTE_OFF, UT_STOP_POWER_CUT) is a run end:
    Done is on for that scan, runs counts it, and it becomes the last-run summary.
  • Permit, Abort, CommsOk and the limits are checked from the first scan: a run
    that carries on with Permit FALSE ends at once, as it would without a power cut.
  • Kept over a power cut (inside the block): the last run's summary, saved once
    at each run end; and the progress of a run in progress (whether one is, whether
    RunHeld started it, whether RunHeld is on, its running time and volume), saved
    as above and when RunHeld changes.

Using it

IrrRun(Start := StartPB, Stop := StopPB, RunHeld := ScadaRun, Abort := SumpLow,
       AbortCode := UT_STOP_LOW_LEVEL, Running := P1.Running, Volume := FlowTot.Total, CommsOk := NOT ScadaWd.CommsFail,
       Data := IrrRunCfg);
P1(Demand := IrrRun.RunCmd, Running := M1.Running, MotorReady := M1.Ready, MotorAuto := M1.Auto,
   Data := P1Data);

With IrrRunCfg.byTime := TRUE, byVolume := TRUE, runTime := T#2h,
targetVolume := 50.0, the run ends at 50 m³ or 2 h of pumping, whichever comes
first (endReason UT_STOP_DONE), or when the sump runs low (UT_STOP_LOW_LEVEL,
with delivered showing how much went, e.g. 32.4 m³).