07 - Pulses and diagnostics

07 - Pulses and diagnostics

Two blocks for the things a pump site always ends up needing: a flow meter's
pulses turned into a total and a rate, and a look at the controller itself when
something is odd on site.

A flow meter: PULSE_COUNT

Pins first

Pin
TOTAL in-out, LREAL the running total, in your units. Your own variable: RETAIN it
CHANNEL in, USINT the input, 1..8 (DI01..DI08)
K_FACTOR in, REAL pulses per unit, from the meter's plate. 0 counts pulses
RATE_PER in, TIME T#1s units a second, T#1m a minute, T#1h an hour
FILTER in, TIME pulses shorter than this are noise
WINDOW in, TIME the rate is measured over at least this long (T#1s)
ZERO_AFTER in, TIME no pulse this long: the rate is 0 (T#30s)
ENABLE in, BOOL count while TRUE
RATE out, REAL units per RATE_PER
PULSES out, UDINT pulses since counting started
COUNTING out, BOOL the counter is running
ERROR, STATUS out why it is not

Wiring it

VAR RETAIN
  flowTotalL : LREAL;          (* litres, kept over a power cut *)
END_VAR

flow( TOTAL := flowTotalL, CHANNEL := 3, K_FACTOR := 100.0, RATE_PER := T#1m );
(* flow.RATE: litres a minute *)

The meter's plate gives its K-factor: pulses per litre (or per m³, per
gallon). Put that in K_FACTOR and TOTAL and RATE come out in that unit.
A meter that gives one pulse per 10 litres has a K-factor of 0.1.

What it does

  • The chip counts, not the scan. The ESP32-S3's pulse counter sees every
    rising edge, so a fast meter loses nothing however long the scan is. Four
    inputs can be counted at once (the chip has four counters); a fifth reports
    UIO_TOO_LARGE. The input still reads normally on DIGITAL_IN.
  • The total is yours. Each scan's new pulses (divided by K_FACTOR) are
    added to TOTAL. Make it RETAIN and it carries over a power cut; write 0
    to reset it. It is an LREAL because a REAL total of a meter that has run for
    years loses its small increments. Pulses that arrive while the PLC is off are
    not counted.
  • The rate suits fast and slow meters. Fast pulses are counted over at
    least WINDOW, from one pulse to another, so the answer does not jitter
    with the scan. Slow pulses use the time between them: one pulse every ten
    seconds reads a steady 0.1 a second, not 1 then 0. When the pulses stop, the
    rate falls away (it can be no more than one pulse over the time since the
    last) and is 0 after ZERO_AFTER. Set ZERO_AFTER above the longest gap
    you expect at the lowest real flow.
  • Contact (reed) meters bounce for milliseconds. The hardware filter tops
    out at about 12 µs, so it cannot remove that. Use a meter with an
    open-collector (solid-state) output, or an RC filter on the input.

The controller: SYS_INFO

Pins first

Pin
HEAP_FREE out, UDINT internal RAM free now
HEAP_MIN out, UDINT the least it has been since the board started
HEAP_LARGEST out, UDINT the largest block that could be allocated now
PSRAM_FREE, PSRAM_SIZE out, UDINT external RAM free, and fitted
STACK_MIN out, UDINT the smallest stack margin among the PLC's tasks, bytes
STACK_TASK out, STRING(16) which task that is
UPTIME out, TIME since the board started
RESET_REASON out, UIO_RESET why it last started
PROGRAM_ID out, STRING(32) the program's identity
FIRMWARE out, STRING(30) firmware and ESP-IDF version
STATUS out, UIO_RESULT UIO_UNSUPPORTED on the Runtime
info();
STS.heapMin := info.HEAP_MIN;
STS.resetReason := info.RESET_REASON;

No inputs: call it once, anywhere. It reads the heap once a second (the
figures walk the heap, so not every scan).

Reading it

You see It means
RESET_REASON = UIO_RST_PANIC the firmware crashed
UIO_RST_INT_WDT, UIO_RST_TASK_WDT, UIO_RST_OTHER_WDT a watchdog: a task hung or ran far too long
UIO_RST_BROWNOUT the supply dipped - look at the power, not the program
UIO_RST_SOFTWARE RESTART, or an update
HEAP_MIN falling day after day a leak
HEAP_LARGEST far below HEAP_FREE the heap is fragmented
STACK_MIN under about 512 STACK_TASK is close to overflowing its stack

STACK_MIN covers every IEC task (each is a FreeRTOS task of that name when
the board runs in RTOS mode) and the firmware's own service tasks
(plc_dispatch, plc_modbus, plc_protocols). Without RTOS mode it is the
task SYS_INFO runs in.

PROGRAM_ID is the MD5 the editor's debugger checks: it tells which program
is on a board.

Alarm on RESET_REASON being a panic or a watchdog: the board restarted by
itself, and nobody would otherwise know.