UT_ZONE_SEQ — Irrigation / wash-down zone sequencer

UT_ZONE_SEQ — Irrigation / wash-down zone sequencer

Runs a list of zones (irrigation blocks, pivots, wash-down stations, effluent
spreading) one after another, each by time or by volume. It opens the right valve,
runs the pump, sets each zone's pressure for the speed controller, and overlaps
valves so the pump never deadheads. It also handles cycle-and-soak, rain hold,
flow checks per zone (blocked dripper line, burst lateral), pause, skip and
manual zone runs.

Pins

Pin Type Default What to wire
in Start BOOL FALSE Rising edge: run the program (e.g. UT_SCHEDULE.Active edge). Also resumes an HMI pause. With startIsLevel: held = run, dropping it stops the program (a remote schedule that holds a run signal)
in Stop BOOL FALSE Rising edge: end the program (closes safely)
in Pause BOOL FALSE Hold where it is (pump off, valves closed, time kept)
in RainHold BOOL FALSE Rain sensor / soil moisture satisfied (action set by rainAction)
in PumpRunning BOOL FALSE Pump running. Zone time only counts while TRUE — wire it
in PumpFault BOOL FALSE Pump tripped: zone time stops, carries on when the pump recovers
in Flow REAL 0.0 Flow meter (volume zones, per-zone flow checks). Optional. NaN, infinite or negative counts as 0
in Clock DT DT#1970-01-01-00:00:00 Real-time clock, for each zone's lastRun. Optional
in Permit BOOL TRUE FALSE holds back the start of the program and of each next zone (Not permitted): nothing opens, the pump stays off. A zone already watering carries on to its end. TRUE again: it carries on. E.g. tank level OK, an off-peak window
in Abort BOOL FALSE Ends the program safely (pump off, then the valves) and refuses a start while on (Blocked: abort). E.g. a low-low level or a site trip
in AbortCode UT_STOP UT_STOP_NONE The endReason an Abort gives, e.g. UT_STOP_LOW_LEVEL. UT_STOP_NONE gives UT_STOP_ABORTED
out PumpDemand BOOL → UT_SPEED_CTRL.Enable / UT_PUMP.Demand
out ZoneSp REAL Active zone's pressure (its sp, or defaultSp) → UT_SPEED_CTRL.Sp
out ActiveZone INT Position of the zone whose valve is open (0 = none)
out Busy BOOL Running, or closing up
out Done BOOL One scan at the end of the program (not after a stop or a rain cancel)
out Warning BOOL A zone had a flow problem or hit maxZoneTime in this run (stays until the next start)
inout Zones ARRAY[*] OF UT_ZONE One element per zone, in run order
inout Data UT_ZONE_SEQ_DATA

Positions (ActiveZone, cmdRunZone) count from 1 = the first
element, whatever the array's lower bound.

Zone slot UT_ZONE

Field Type Default Meaning
enable BOOL TRUE Include in the program
runTime TIME T#10m Watering time (when volume = 0)
volume REAL 0.0 Water to apply, in the flow meter's volume unit (needs Flow). 0 = time-based
sp REAL 0.0 Pressure for this zone (0 = defaultSp)
cycles INT 1 Split the zone into this many cycles…
soakTime TIME T#0s …with this soak between them (less runoff on heavy soils)
minFlow / maxFlow REAL 0.0 / 0.0 Expected flow band (0 = not checked): low = blocked, high = burst
flowCheck UT_PROTECTION WARN · 60 s · AUTO What to do on a flow-band breach. TRIP = end this zone and move on
valve BOOL Output: this zone's valve should be open. With the default NC drive, wire this or openCmd to the valve's output
active BOOL Status: this zone is the one being watered
done BOOL Status: finished in this run (watered, skipped or capped)
skipped BOOL Status: skipped (rain, cmdSkip, flow trip)
capped BOOL Status: ended by maxZoneTime
flowAlarm BOOL Status: flow out of band in this run
delivered REAL Status: volume this run
watered TIME Status: water time this run
remaining TIME Status: water time left (volume zones: maxZoneTime left)
cycle INT Status: cycles finished
soakLeft TIME Status: soak time left
lastRun DT Status: Clock when it last finished watering
endBy UT_ZONE_END UT_ZE_AUTO How the zone ends: UT_ZE_AUTO (0: volume if it has one, else runTime) · UT_ZE_TIME (runTime, the volume only counted) · UT_ZE_VOLUME (volume, runTime ignored) · UT_ZE_FIRST (whichever comes first) · UT_ZE_UNTIL_STOP (it waters until Stop / cmdStop, a held Start dropping, cmdSkip, Abort or a protection; runTime, volume and cycles are not used; maxZoneTime still caps it). A zone with nothing to give for its endBy (VOLUME with no volume, TIME with no runTime) is passed over
useProven BOOL FALSE The valve must be proven open (proven) before the pump starts or the previous valve closes (see Valve proven open)
proven BOOL FALSE Input: the valve is proven open, e.g. its open limit switch. Write it from your input every scan
openCmd BOOL Output: NC drive: on = open (the same as valve). LATCH: the open pulse. MOTOR: the open run
closeCmd BOOL Output: NO drive: on = closed. LATCH: the close pulse. MOTOR: the close run
driveLeft TIME Status: LATCH / MOTOR: the pulse or travel time left

Record UT_ZONE_SEQ_DATA

Field Type Default Meaning
valveOverlap TIME T#5s Next valve opens this long before the previous one closes (no deadhead)
pumpStartDelay TIME T#3s First valve opens this long before the pump starts
valveCloseDelay TIME T#5s Valves close this long after the pump is told to stop, and only once PumpRunning has gone (no water hammer)
rainAction UT_RAIN_ACTION UT_RAIN_PAUSE UT_RAIN_PAUSE (0, resume when cleared) · UT_RAIN_SKIP (each zone is skipped as it comes up while it rains; the one running ends now) · UT_RAIN_CANCEL (end the program) · UT_RAIN_IGNORE
repeats INT 1 Run the whole program this many times
maxZoneTime TIME T#0s Safety cap on any zone's water time (volume zones with a dead meter). 0 = off
defaultSp REAL 0.0 ZoneSp when the zone's sp is 0, and when idle
flowPer UT_RATE_UNIT UT_PER_HOUR Flow is volume units per second / minute / hour / day
cmdStart BOOL HMI: start, or resume an HMI pause
cmdStop BOOL HMI: stop
cmdPause BOOL HMI: pause until a start
cmdSkip BOOL HMI: skip the zone running now
cmdRunZone INT -1 HMI: run only this zone (position, enabled or not); -1 = none
phase UT_ZONE_PHASE Status: UT_ZS_IDLE, _OPENING, _WATERING, _OVERLAP, _SOAKING, _PAUSED, _RAIN, _PUMP_FAULT, _CLOSING, _HELD (Permit off, a zone waiting to start)
activeZone INT Status: same as ActiveZone
pass INT Status: which pass of the program (1..repeats, 0 idle)
programRemaining TIME Status: water time left (time zones; soaks not included)
runs UDINT Status: programs completed since the PLC started (manual zone runs not counted)
paused BOOL Status
warning BOOL Status: same as Warning (also on a bad setting)
configBad BOOL Status: a setting is invalid (see Bad settings)
statusCode UT_STATUS Status: what it is doing, or what holds it back (see Status codes)
faultId UT_FAULT Status: the warning or setting the status is about (UT_F_NONE when none)
statusText STRING(30) Status: statusCode and faultId in words, e.g. Running: zone. The zone is in activeZone, its time left in timeLeft
maxPumpWait TIME T#0s While a zone waters, the pump faulted or not running this long ends the program (Stopped: pump fault, valves closed safely). 0 = wait for ever
pumpWaitSkips BOOL FALSE maxPumpWait, and a valve not proven in provenTime, skip that zone instead, and the next one runs
startIsLevel BOOL FALSE Start held = run, dropping it stops the program (Stopped: remote off)
timeLeft TIME Status: the countdown the status shows (the zone's water time left, the pump start delay, the soak)
phaseTime TIME Status: time in the current phase
programDelivered REAL Status: volume through the meter in this program (all zones), kept after it ends
endReason UT_STOP Status: why the last program ended: UT_STOP_OPERATOR (Stop, cmdStop), UT_STOP_DONE (also a cmdRunZone run), UT_STOP_RAIN (CANCEL), UT_STOP_PUMP_FAULT (maxPumpWait), UT_STOP_REMOTE_OFF (startIsLevel, or found off at power-up), UT_STOP_SETTING (a setting made invalid), UT_STOP_POWER_CUT (a program cut off that does not carry on: RESTART, NONE), AbortCode (Abort; UT_STOP_ABORTED when it is NONE), UT_STOP_FAULT (a valve not proven in provenTime). UT_STOP_NONE = none since power-up
endZone INT Status: the zone watering (or watered last) when it ended: the cmdRunZone zone, the zone of a power cut (0 = none)
lastFaultCode / lastFault DWORD / UT_FAULT Status: the last fault, kept after it clears: bit 0 UT_F_ZONE_FLOW (a flow TRIP), bit 1 UT_F_PUMP_FAULT (maxPumpWait), bit 2 UT_F_NOT_PROVEN (a valve not proven). The zone's flowAlarm / skipped show which, until the next start
trips UDINT Status: flow trips, pump waits and valves not proven since power-up
powerUp UT_RUN_POWERUP UT_RPU_RESUME What a program does after a power cut: UT_RPU_RESUME (0, the default: it carries on where it was) · UT_RPU_RESTART (a held program starts again from zone 1) · UT_RPU_NONE (nothing starts). See After a power cut. An unknown value acts as NONE. The enum is declared with UT_RUN_LIMIT
progressSave TIME T#1m RESUME: while a program runs, the zone's water time and volume are saved at most this often (and at once when the zone, pass or cycle changes). At most this much water is given again after a power cut. 0 = saved only on those changes (the zone starts its count again)
provenTime TIME T#30s useProven: a valve not proven this long after it is told to open is a fault (UT_F_NOT_PROVEN): the program ends (UT_STOP_FAULT), or with pumpWaitSkips the zone is skipped. Include the MOTOR travel. 0 = wait for ever
valveDrive UT_ZV_DRIVE UT_ZV_NC How the zone valves are driven, for every zone (see Valve drives): UT_ZV_NC (0, output on = open) · UT_ZV_NO (output on = closed) · UT_ZV_LATCH (open / close pulses) · UT_ZV_MOTOR (open / close runs)
driveTime TIME T#0s LATCH: the pulse time. MOTOR: the travel time, open or close. Needed (above 0) for LATCH and MOTOR

How it works

  • Order, so the pump never deadheads and never hammers: start = the valve opens,
    pumpStartDelay later PumpDemand comes on. Zone change = the next valve opens,
    valveOverlap later the previous one closes. End, pause or soak = PumpDemand goes
    off; the valves close once valveCloseDelay has passed and the pump has stopped.
  • Zone time counts only while PumpRunning and not PumpFault. A pump trip keeps
    the valve open and the pump asked for, and the zone carries on when it recovers.
  • How a zone ends (endBy): AUTO (the volume if it has one, else the time), TIME,
    VOLUME, or FIRST (whichever comes first, e.g. "50 m³ or 2 h"). Volume counts Flow
    integrated, units per flowPer. maxZoneTime caps any zone; a capped zone gives
    Warning and the program moves on.
  • A pump that does not run: the zone waits (no water time). With maxPumpWait, a
    pump faulted or not running that long ends the program safely (endReason UT_STOP_PUMP_FAULT), or
    with pumpWaitSkips skips the zone; either is counted in trips with
    lastFault.
  • Run while held (startIsLevel): Start held runs the program, dropping it stops
    it (endReason UT_STOP_REMOTE_OFF). A program that ends while Start is still held does not start
    again until Start cycles. After a power cut, see powerUp.
  • Cycle and soak: each cycle is runTime / cycles (or volume / cycles). While a
    zone soaks, the next zones run; the program comes back to it after its soak. With
    nothing else to run the pump stops and the valves close until a soak is over.
  • Flow check: a flow outside minFlow..maxFlow while one valve is open (not
    during an overlap) is the zone's flowCheck protection: after its delay, WARN keeps
    watering, TRIP ends the zone. Either sets flowAlarm and Warning.
  • Pause keeps the zone's time. Disabled zones, and zones with no time and no
    volume, are passed over.
  • Permit: Permit off holds back each start: the program's first zone, the next
    zone, and a zone coming back after a pause or a soak. A zone already watering
    carries on to its end; then the pump stops and the valves close as at the end, and
    the program waits (Not permitted, phase UT_ZS_HELD, Busy on). Permit on
    again carries on. To stop a zone that is watering, use Pause or Abort.
  • Abort: ends the program as Stop does (pump off, then the valves), with
    endReason = AbortCode. While it is on a start is refused, and is not kept for
    later (Blocked: abort).
  • Until stopped: a zone with endBy UT_ZE_UNTIL_STOP waters until it is stopped,
    the held Start drops (startIsLevel, a remote that holds the run), or cmdSkip
    moves on (status Running: until stopped, timeLeft 0). The zones after it run only
    after a cmdSkip. It is not counted in programRemaining.
  • Power cut: every valve starts closed and the pump off (even if you declared the
    zones RETAIN); LATCH and MOTOR valves are driven closed (one close pulse / run);
    then powerUp decides, below.
  • Start and Stop in the same scan: no start. Commands held on act once.
  • A pump that never reports running holds the program (no water time), and a pump
    that never stops holds the valves open: both are what you want hydraulically, and
    the pump block reports the fault.

Valve drives

valveDrive sets how every zone valve is driven. valve is always "this zone should
be open"; wire the outputs for your valve:

valveDrive Wire Opening Closing
UT_ZV_NC (default) openCmd (or valve) → the solenoid openCmd on, held openCmd off
UT_ZV_NO closeCmd → the solenoid closeCmd off closeCmd on, held (also when idle)
UT_ZV_LATCH openCmd → open coil, closeCmd → close coil (or the polarity relays) one openCmd pulse of driveTime one closeCmd pulse of driveTime
UT_ZV_MOTOR openCmd → open contactor, closeCmd → close contactor openCmd on for the driveTime travel closeCmd on for the driveTime travel
  • openCmd and closeCmd are never on together. A valve told the other way while it
    moves reverses at once and gets the full driveTime.
  • A LATCH or MOTOR valve counts as open once its driveTime is over: the pump starts
    (after pumpStartDelay too) and the previous zone's valve closes only then. The
    status shows Starting with the time left.
  • At power-up every LATCH or MOTOR valve gets a close pulse / run (its position is not
    known: it may have been open at the cut). The close pulse or run can still be on
    for driveTime after Busy goes off.
  • LATCH or MOTOR with no driveTime, or an unknown valveDrive: Config: valve drive, nothing runs, both outputs stay off.
  • On NO valves the valve opens when the output is off: also when the PLC is stopped
    or loses power.

Valve proven open

With a zone's useProven on, its valve must prove it has opened before water is
counted for it:

  • The valve opens; the pump starts once pumpStartDelay has passed and proven is
    on. At a zone change, the previous valve stays open (the pump keeps running through
    it) until the new valve is proven and valveOverlap has passed. The new zone's time
    counts once it is proven. Status Waiting: valve proven, timeLeft = provenTime left.
  • Use a signal that is valid with the pump off, e.g. the valve's open limit switch (a
    pressure switch behind the valve only proves once the pump runs: it works at a zone
    change, not at the first zone).
  • Proven is checked while the valve opens; once seen it is not checked again while the
    zone waters (a flow or pressure check covers a valve that shuts while watering).
  • Not proven within provenTime: lastFault UT_F_NOT_PROVEN, trips + 1, and the
    program ends (UT_STOP_FAULT) with the pump off, or with pumpWaitSkips the zone is
    skipped and the next one opens (at a zone change, while the previous valve still
    carries the flow, so the pump never deadheads).

After a power cut

Irrigation of sports fields and properties often runs with no operator: when the
power comes back (or the PLC is stopped and started) the program should carry on, as
a commercial irrigation controller does. powerUp chooses:

powerUp A program running at the cut Start held (startIsLevel) at power-up, no program running
UT_RPU_RESUME (default) Carries on: the zone that was watering with the time / volume it had left (status Running: resumed), then the zones after it, and the passes left. A program started by a held Start that is off now ends: UT_STOP_REMOTE_OFF. One started by a pulse, cmdStart or cmdRunZone just carries on Starts the program
UT_RPU_RESTART Nothing is kept. A program started by a held Start that is still on starts again from zone 1 (status Running: restarted); endReason says UT_STOP_POWER_CUT, endZone the zone it was in. One started by a pulse, cmdStart or cmdRunZone ends (UT_STOP_POWER_CUT, endZone) Starts the program
UT_RPU_NONE Ends (UT_STOP_POWER_CUT, endZone) Nothing starts: Waiting: start again until Start goes off and on again
  • The valves open again in the normal order: valve first, the pump pumpStartDelay
    later.
  • Resume carries on with the zone that was watering: the zones before it count as
    done for this pass, the zone gets its water time, volume and cycles back, and the
    zones after it run in full. A zone that was soaking at the cut soaks again in full.
    programDelivered and an HMI pause (cmdPause) carry on too; a cmdRunZone run
    carries on with that zone only.
  • With cycle and soak, a zone that was soaking while a later zone watered (other
    than the one cut off) is not tracked: if it is before the interrupted zone in the
    list its cycles left are not given; if after, it runs all its cycles again.
  • Water time spent before the cut is not counted again, and a zone never gets more
    than its runTime / volume.
  • The zone carries on from its last save: the progress is saved when the program
    starts and ends, when the zone, pass or cycle changes, on Start and HMI pause
    changes, and every progressSave (default 1 min) while it runs, never every scan
    (flash wear: a few hundred saves on a day of irrigation, none when idle). So up to
    progressSave of a zone's water can be given again after a cut.
  • A held Start that was already on at the cut and had been dealt with (its
    program done, or stopped) does not start the program again after the power cut, in
    any mode: as without a power cut, it must go off and on again. Only a Start that
    came on while the power was off counts as a new request.
  • Pause, RainHold, PumpFault and the settings act from the first scan, as they
    would without a power cut.
  • Kept over a power cut (inside the block, for this only): whether a program is
    running, how it was started, whether Start is on, the HMI pause, the zone
    watering (position, cycles done, soaking, water time, volume), the pass, a
    cmdRunZone run, and programDelivered. runs counts from when the PLC started.

Status codes

statusCode is a UT_STATUS and faultId a UT_FAULT (an HMI reads their numbers);
statusText is the two in words, changed only when one of them changes. The one main
thing, in the order config, held, warning, normal, idle. The zone is in activeZone
(a position in the array), the countdown in timeLeft, a volume zone's progress in its
delivered of volume. Name the zones on the HMI, by position.

statusCode faultId statusText When
UT_ST_IDLE Idle Not running
UT_ST_STARTING Starting The valve is open, pumpStartDelay before the pump (timeLeft)
UT_ST_STOPPING Stopping The end (or a pause or soak) closing safely: pump off, then the valves
UT_ST_RUN_ZONE Running: zone Watering: timeLeft the zone's water time left (all its cycles); 0 for a volume zone
UT_ST_RESUMED Running: resumed The same, for the first zone watered after a power cut (RESUME), until the zone changes
UT_ST_RESTARTED Running: restarted The same, after a power cut with RESTART
UT_ST_WAIT_POWERUP Waiting: start again NONE: a held Start that would have run is on at power-up; it must go off and on again
UT_ST_PAUSED_RAIN Paused: rain RainHold with rainAction PAUSE
UT_ST_PAUSED_INPUT Paused: Pause input Pause
UT_ST_PAUSED_START Paused: press Start cmdPause
UT_ST_PUMP_FAULT_HOLD Blocked: pump fault PumpFault while watering: the zone time stops
UT_ST_WAIT_PUMP Waiting: pump not running Watering but PumpRunning is off (the time does not count)
UT_ST_SOAK Waiting: soak Every zone left is soaking (timeLeft: the shortest soak left)
UT_ST_RUN_UNTIL_STOP Running: until stopped Watering a UT_ZE_UNTIL_STOP zone
UT_ST_NOT_PERMITTED Not permitted Permit off: the next zone (or the first) waits; the valves close after the pump
UT_ST_WAIT_PROVEN Waiting: valve proven The zone's valve is open, waiting for proven (timeLeft: provenTime left)
UT_ST_ABORT Blocked: abort Abort on: not running, a start is refused
UT_ST_WARN_SETTING UT_F_SETTING Setting: a setting A setting with a safe value (see Bad settings)
UT_ST_WARNING UT_F_ZONE_FLOW Warning: zone flow The zone's flow check (WARN) is raised now
UT_ST_CONFIG UT_F_VALVE_PUMP_TIME Config: valve / pump time A negative valve or pump time: nothing runs
UT_ST_CONFIG UT_F_DEFAULT_SP Config: default setpoint defaultSp negative or not a number: nothing runs
UT_ST_CONFIG UT_F_VALVE_DRIVE Config: valve drive LATCH / MOTOR with no driveTime, or an unknown valveDrive: nothing runs

Bad settings

  • Nothing runs (configBad, Warning; a program running ends safely: pump off, then the
    valves once it has stopped; ZoneSp 0): a negative valveOverlap, pumpStartDelay or
    valveCloseDelay, defaultSp negative or not a number, an unknown valveDrive, or
    LATCH / MOTOR with driveTime 0 or negative.
  • Warning, safe values: an unknown rainAction (PAUSE), an unknown flowPer (per
    hour), repeats below 1 (1), a negative maxZoneTime (none), a negative
    provenTime (wait for ever); a zone with a negative
    runTime / soakTime, volume, sp, minFlow or maxFlow negative or not a number,
    or cycles below 1 (it runs on the safe value or is passed over).