UT_VALVE_3POS — Three-position valve (diverter or open/mid/closed)

UT_VALVE_3POS — Three-position valve (diverter or open/mid/closed)

For actuators with three positions:

  • 3-way diverters: A / closed / B,
  • spring-centred double-solenoid valves and cylinders (centre = both coils off),
  • three-coil valves (one coil per position),
  • motorised valves with a mid position (mid limit switch or timed).

Mode, safe position, protections and stroke count work exactly as
UT_VALVE (UT_VALVE_CORE).

Pins

Pin Type Default What to wire
in AutoPos INT 2 Auto position request: 1, 2 or 3 (anything else is ignored)
in Ls1 / Ls2 / Ls3 BOOL FALSE Position limit switches
in Interlock BOOL TRUE FALSE → safePos3 position
in DriveFault, SwHand, SwAuto, Reset As UT_VALVE
in Permissive BOOL TRUE FALSE: no move away from safePos3 starts (a move to it is allowed; it never forces it)
in Local1 / Local2 / Local3 BOOL FALSE Local pushbuttons (Hand), each on its rising edge: go to position 1, 2, 3
in LocalStop BOOL FALSE Local stop pushbutton (Hand; held: keeps stopping). Motorised: stops where it is
out Out1 / Out2 / Out3 BOOL Coils, see the type table
out Position INT Confirmed position 1–3 (0 = moving/unknown)
out Fault BOOL A trip is holding it at the safe position
out State UT_STATE OFF at safePos3, ON at another position, STARTING moving away from safePos3, STOPPING moving to it
inout Data UT_VALVE_DATA Shared valve record (UT_VALVE)
inout Pos3 UT_VALVE3_DATA The three-position settings, command and status (below)

Record UT_VALVE3_DATA (pin Pos3)

Field Type Default Meaning
type3 UT_VALVE3_TYPE UT_V3_SPRING_CENTRE UT_V3_SPRING_CENTRE (pos1 = Out1, pos2 = none, pos3 = Out3) · UT_V3_THREE_COIL (one output per position) · UT_V3_MOTOR (Out1 drives toward 1, Out3 toward 3, stops at the target; mid by Ls2 or midTime)
useLs1 / useLs2 / useLs3 BOOL TRUE Which limits are fitted
travelTime TIME T#10s Timeout per move (end to end for a motor). Without that limit, the position is taken as reached after this
midTime TIME T#0s Motor without Ls2: timed run from an end to mid (0 = half of travelTime)
safePos3 INT 2 Position on interlock / Off / a trip (outside 1–3 = 2)
cmdPos INT −1 HMI position request 1–3 (Hand). A one-shot request like cmdMode: it acts when a new value arrives and is set back to −1; invalid values are ignored
targetPos / actualPos INT Status: where it is going (0 = hold) / confirmed position (0 = moving or unknown)

In the valve record Data: reversalDelay (T#500ms, motor: pause before driving the
other way), the modes, protections, cmdOpen / cmdClose / cmdStop / cmdReset
and the status.

cmdStop stops a motorised valve where it is (Hand). Faults use the shared bits:
a move toward a higher position that times out is openTimeout (bit 0), toward a
lower one closeTimeout (bit 1); two limits on → bit 2; position lost → bit 3.
lastOpenStroke / lastCloseStroke are the last measured moves up / down
(on a limit). position is 0 / 50 / 100 at positions 1 / 2 / 3.

How it works

  • A motor going 1 ↔ 3 passes 2 without stopping.
  • Motor to 2 with Ls2: from 1 it drives up, from 3 down, from an unknown
    position down; if it reaches end 1 first it turns round (reversal pause) and
    drives up to Ls2.
  • Motor to 2 without Ls2: from a known end it runs midTime toward the
    middle; from an unknown position it first goes to end 1 (re-sync), then runs
    midTime up.
  • A limit that drops again within the travel time is a flicker: the valve
    carries on. At most two legs per move, then a timeout.
  • Power-up: the position comes from the limits, no false fault. Hand stays put;
    Off goes to safePos3; Auto goes to AutoPos.

Status

statusCode, faultId and statusText say the one main thing the valve is
doing, or what holds it back, so a technician can see on the HMI why it is not where
it was asked to be. The most important reason wins: configuration > fault > held /
waiting > warning > position > Off. The words hold no numbers: the target and the position are in targetPos and actualPos. The time left
(travel, a pause, a fault's recover / retry wait) is in timeLeft. The text is
rebuilt only when the status or the fault changes. Where the valve is (the rows
marked (this block)) comes from the block's last scan, so it shows one scan after
it changes. The numbers are in conventions.

statusCode Words When
UT_ST_OFF Off Mode Off (it goes to its safe position)
UT_ST_MOVING Moving (this block) Going to targetPos; timeLeft is the travel time left when one applies
UT_ST_AT_POSITION At position (this block) At actualPos
UT_ST_BETWEEN Stopped between positions (this block) Held where it is (a Hand stop on a motorised valve)
UT_ST_POS_UNKNOWN Position unknown (this block) Not moving and no limit or travel time says where it is
UT_ST_INTERLOCK Blocked: interlock Interlock FALSE: at its safe position (every mode but OOS)
UT_ST_MUST_CYCLE Waiting: command must cycle After a MANUAL reset in Auto: it stays safe until the Auto request changes (unless restartAfterReset)
UT_ST_OOS Out of service
UT_ST_NOT_PERMITTED Not permitted (this block) Permissive FALSE holds back a move away from the safe position
UT_ST_DEAD_TIME Waiting: dead time (this block) Motorised: the pause before driving the other way (timeLeft)
UT_ST_WARNING Warning: <fault> A protection set to WARN is raised
UT_ST_WARN_SETTING Setting: <setting> An invalid setting, a safe value in use (settings below)
UT_ST_FAULT Fault: <fault> Tripped, AUTO: clears by itself once the cause has gone for recover (timeLeft while it counts)
UT_ST_FAULT_RETRY Retrying: <fault> Tripped, RETRY: the protection's retries of maxRetries (timeLeft while it counts)
UT_ST_FAULT_RESET Latched: <fault> Tripped, MANUAL: a reset (pin, cmdReset, Off) once the cause has gone
UT_ST_FAULT_LOCKED Locked: <fault> RETRY used up: now as MANUAL
UT_ST_CONFIG Config: <setting> An invalid setting: every output off until it is fixed

<fault> is faultId, one of: UT_F_OPEN_TIMEOUT (open timeout) · UT_F_CLOSE_TIMEOUT (close timeout) · UT_F_BOTH_LIMITS (both limits) · UT_F_POS_LOST (position lost) · UT_F_NO_MOVEMENT (did not move) · UT_F_ACTUATOR (actuator fault).
<setting> with UT_ST_WARN_SETTING is one of: UT_F_SAVE_EVERY (save every) · UT_F_RETRY_WINDOW (retry window) · UT_F_MODE_SOURCE (mode source) · UT_F_SAFE_POSITION (safe position, must be 1..3); with UT_ST_CONFIG one of: UT_F_THREE_POS_TYPE (three-position type) · UT_F_MID_TIME (travel / mid time) · UT_F_REVERSAL_DELAY (reversal delay).

Bad settings

A setting that is not a number, negative or unknown never drives the valve somewhere
it could do damage. configBad is set and faultCode bit 8, and faultId names the
setting (the lowest priority). A negative saveEvery keeps nothing; a negative retryWindow
uses the default 1 h; an unknown modeSource uses the HMI (warnings).

  • Refused (a fault, every output off): an unknown type3; a negative travelTime,
    midTime or reversalDelay.
  • Warning: safePos3 outside 1..3 (2 is used).