UT_PUMP_CASCADE — Multi-pump booster and manifold

UT_PUMP_CASCADE — Multi-pump booster and manifold

Runs several pumps (any number) on one header to hold a pressure (or a flow):
irrigation manifolds, booster sets, town and stock-water supply. Pumps come on one
at a time as the demand rises and drop off one at a time as it falls, the work is
shared by run hours, a pump that fails hands over to the next, and a small jockey
pump can carry the low demand on its own.

Each pump keeps its own motor block, mixed freely: UT_MOTOR for a
contactor or soft starter (fixed speed), UT_MOTOR_VSD for a drive.
The cascade takes the array of the pumps' motor records, like
UT_DUTY; the array size is the number of pumps. Every VSD the group runs
gets the same speed; fixed-speed pumps run flat out. The control loop inside is a
UT_SPEED_CTRL (its record is Data.ctrl), so the pipe fill,
sleep / wake, overpressure, burst-pipe, hunting and failed-sensor handling are the same
as on a single pump.

Pins

Pin Type Default What to wire
in Enable BOOL FALSE Pumping wanted (a schedule, a switch, UT_ZONE_SEQ.PumpDemand)
in Pv REAL 0.0 The value held: the header pressure (or a flow), e.g. UT_ANALOG_IN.Value
in PvGood BOOL TRUE Its transmitter is healthy (UT_ANALOG_IN.Good)
in Flow REAL 0.0 Header flow: flow staging, high flow, low-flow sleep, flow limit (optional)
in FlowGood BOOL TRUE The flow meter is healthy
in Sp REAL 0.0 Setpoint when ctrl.spSource := UT_SP_PIN
in Rotate BOOL FALSE Rising edge: hand the longest-running pump over now
in Reset BOOL FALSE Rising edge: reset MANUAL protections (the loop's too)
out RunningCount INT Pumps running (any mode)
out Speed REAL The shared VSD speed, % (0 when stopped)
out Phase UT_SC_PHASE The loop's phase: IDLE, FILLING, CONTROL, BOOST, SLEEP, FALLBACK
out AtSetpoint BOOL Pv within ctrl.atSpBand
out Shortfall BOOL More pumps wanted than can run (none left, or maxRunning reached)
out Fault BOOL A trip has stopped the pumps, or the loop's settings run nothing
out Warning BOOL A warning (see the fault code)
inout Units ARRAY[*] OF UT_MOTOR_DATA The pumps' motor records (any size, any lower bound)
inout Data UT_PUMP_CASCADE_DATA Group record

Record UT_PUMP_CASCADE_DATA

Staging

Field Type Default Meaning
stageBy UT_PC_STAGE UT_PC_STAGE_PV What adds and drops pumps: UT_PC_STAGE_PV (0, the pressure), UT_PC_STAGE_FLOW, UT_PC_STAGE_PER_PUMP (see How it works)
stageDelay TIME T#10s Add: the need has lasted this long, and this long since the last start or stop command
destageDelay TIME T#20s Drop: the same, for dropping
addBand REAL 0.3 No VSD running: add when Pv is this far below sp
dropBand REAL 0.3 No VSD running: drop when Pv is this far above sp
dropSpeed REAL 0.0 PV with a VSD running: drop one when the shared speed is below this % (0 = only at the minimum speed)
addPct REAL 90.0 FLOW and the jockey: add above this % of the running pumps' capacity
dropPct REAL 75.0 FLOW and the jockey: drop below this % of the capacity left after the drop
bepMin / bepMax REAL 0.0 / 0.0 PER_PUMP: keep the flow per running pump between these (the pumps' best-efficiency range)
maxRunning INT 0 Most pumps running at once, Hand ones included (0 = all)
failoverDelay TIME T#10s A called pump not running this long after its run command is skipped and the next one called

Rotation

Field Type Default Meaning
rotation UT_ROTATE_MODE UT_ROT_HOURS UT_ROT_FIXED · UT_ROT_EACH_START · UT_ROT_HOURS · UT_ROT_INTERVAL
fixedLead INT 1 FIXED: array index of the first pump
hoursDiff TIME T#1h HOURS: a running pump with this much more run time than an idle one hands over to it (0 = no swap while running)
rotateInterval TIME T#24h INTERVAL: the pump running longest hands over this often (0 = never)

Protection and the loop

Field Bit Type Default Meaning
highFlow 8 UT_LEVEL TRIP · 10 s · RETRY (3, recover 5 min) · sp 0 A burst main: Flow above sp while pumps run. TRIP stops every pump. sp 0 = off
ctrl 0–7 UT_SPEED_CTRL_DATA The loop: setpoint, PID, speed limits, pipe fill, sleep, overpressure (highPv), burst at full speed (lowPvAtMax), hunting, failed sensor (pvFail), manual speed. Every field as UT_SPEED_CTRL. ctrl.sp must be set. ctrl.stageDelay and the MoreNeeded / LessNeeded outputs are not used here

ctrl.control chooses what the shared speed follows, as on
UT_SPEED_CTRL: the PID on
the header pressure Pv (UT_SC_CTRL_PV, the default), the PID on the Flow pin
(UT_SC_CTRL_FLOW, setpoints ctrl.flowSp / flowSpLow / flowSpHigh), or a fixed
speed (UT_SC_CTRL_FIXED, ctrl.fixedSpeed / fixedSpeedLow / fixedSpeedHigh).
ctrl.preset picks NORMAL, LOW or HIGH: for example ctrl.spLow for a travelling
irrigator working near the station. ctrl.highPv always watches Pv. The value
under control is ctrl.pv.

Stopping

Field Type Default Meaning
stopMode UT_PC_STOP UT_PC_STOP_ALL_AT_ONCE How the group stops on Enable FALSE or sleep: UT_PC_STOP_ALL_AT_ONCE (0) every pump at once; UT_PC_STOP_STAGED one pump at a time, less water hammer (see Stops). A trip always stops every pump at once
stopStep TIME T#3s STAGED: the time between pump stops

HMI commands (act once, cleared by the block)

Field Meaning
cmdRotate Hand the longest-running pump over now
cmdReset Reset MANUAL protections, the loop's too
ctrl.cmdManual / ctrl.cmdAuto The loop's manual speed (ctrl.manualSpeed): the called pumps run at it, the loop's protections still act, no pump is added or dropped; cmdAuto hands back to the loop (see UT_SPEED_CTRL)

Status fields

Field Type Meaning
stage INT Duty pumps wanted (0 with jockeyOn: the jockey alone)
jockeyOn BOOL The jockey is the running stage
runningCount / calledCount / availableCount INT Pumps running (any mode) / called by the group / in Auto and ready
capacity REAL Capacity of the group's pumps running
flowPerPump REAL Flow / group pumps running
speed REAL The shared speed, %
stageByUsed UT_PC_STAGE The criterion in use (PV after a fallback)
shortfall BOOL As the pin
configBad BOOL The loop's settings are invalid: nothing runs (bit 0)
wrnConfig BOOL A group setting is invalid: a safe value is used (bit 10)
flowBad BOOL The flow signal is bad while it is used (bit 9)
pvStaging BOOL FLOW / PER_PUMP left the pressure short: staging on Pv until the group next starts (bit 11)
fault, warning, faultCode : DWORD Bits 0–7 are the loop's (UT_SPEED_CTRL): 0 settings, 1 sensor failed, 2 overpressure, 3 low at max (burst), 4 fill timeout, 5 not reaching, 6 hunting, 7 a loop setting warning. Then 8 high flow, 9 flow signal bad, 10 group setting, 11 flow staging fell back to Pv. Warnings set their bits too
faultId UT_FAULT The most important fault or warning by name: UT_F_HIGH_FLOW, UT_F_FLOW_BAD, UT_F_FLOW_SHORT, UT_F_GROUP_SETTING, else the loop's faultId (UT_F_NO_UNITS with an empty array)
statusCode UT_STATUS What the group is doing, or what holds it back (see Status)
statusText STRING(30) The status in words, for a person looking at the PLC
statusUnit DINT The pump (array index) the status is about; one below the array's first index when none
stopping BOOL A STAGED stop is under way
timeLeft TIME The countdown that goes with the status: the add or drop delay, the failover, the next staged stop, or (where the loop's status is shown) the loop's timeLeft. 0 = none
phaseTime TIME Time in the loop's phase (ctrl.phaseTime)
stopReason UT_STOP Why the group last stopped: UT_STOP_FAULT for a high-flow trip, otherwise the loop's (UT_STOP_DEMAND_ENDED for Enable off, UT_STOP_FAULT a loop trip, UT_STOP_SETTING a setting, UT_STOP_ASLEEP asleep)
lastFaultCode / lastFault DWORD / UT_FAULT The last trip (the loop's bits and name, or bit 8 and UT_F_HIGH_FLOW), kept after it clears
trips UDINT Trips since power-up, the loop's and high flow

Status

statusCode, faultId and statusText say the one main thing the group is
doing, or what holds it back. The most important reason wins: configuration > fault >
held / waiting > warning > running > idle. Where the loop's own status is the main
thing (its settings, its trips, sleep, Enable cycling, its warnings, pipe fill,
boost, flow limit, fallback) the loop's status and its fault (ctrl.statusCode, see
UT_SPEED_CTRL) are shown, with the loop's timeLeft.
Enabled with no pump running or starting (a called pump's run command out), it always
shows a held, fault or configuration status; UT_ST_STARTING shows over a warning.
The pump a status is about is statusUnit (an array index); the counts are
runningCount, calledCount and availableCount, the speed speed, and the time
left timeLeft. The text is rebuilt only when the status or the fault changes. The
numbers are in conventions.

statusCode Words When
UT_ST_IDLE_NOT_ENABLED Idle: not enabled Enable FALSE
UT_ST_IDLE_NO_DEMAND Idle: no demand Nothing running
UT_ST_STARTING Starting Pump statusUnit called, not running yet; skipped if not running within timeLeft (the failover delay)
UT_ST_RUNNING Running Pumps running (any mode): runningCount, at speed with a VSD running
UT_ST_ADDING Adding a pump The add rule holds; the next pump after stageDelay (timeLeft)
UT_ST_DROPPING Dropping a pump The drop rule holds; the next drop (or hand-back to the jockey) after destageDelay (timeLeft)
UT_ST_JOCKEY Jockey running The jockey is the running stage
UT_ST_SWAPPING Swapping pumps (rotation) A rotation swap: the new pump (statusUnit) starts, then the old one stops
UT_ST_STOPPING Stopping A STAGED stop: the next pump stops in timeLeft
UT_ST_ENABLE_CYCLE Waiting: Enable must cycle After a MANUAL high-flow reset (unless ctrl.restartAfterReset)
UT_ST_MAX_RUNNING Waiting: max running reached Another pump wanted, maxRunning pumps on (Hand ones count)
UT_ST_SHORTFALL Shortfall: too few available More pumps wanted than can run
UT_ST_WARNING Warning: flow signal bad UT_F_FLOW_BAD: the flow signal is bad while it is used (FLOW / PER_PUMP staging falls back to Pv; high flow, the flow limit or low-flow sleep)
UT_ST_WARNING Warning: flow staging short UT_F_FLOW_SHORT: pvStaging (bit 11): flow staging left the pressure short, staging is on Pv
UT_ST_WARNING Warning: high flow UT_F_HIGH_FLOW: highFlow set to WARN
UT_ST_WARN_SETTING Setting: group setting UT_F_GROUP_SETTING: a group setting is invalid (bit 10)
UT_ST_FAULT · UT_ST_FAULT_RETRY · UT_ST_FAULT_RESET · UT_ST_FAULT_LOCKED Fault: high flow · Retrying: high flow · Latched: high flow · Locked: high flow The high-flow trip, by its reset mode (timeLeft while the recover time counts)
UT_ST_CONFIG Config: no units in array UT_F_NO_UNITS: an empty array
(the loop's) e.g. Config: setpoint, Fault: overpressure, Sleeping, Pipe fill, Running: fallback speed The loop's status and fault

Fields in each pump's motor record (UT_MOTOR_DATA)

Field Type Written by Meaning
capacity REAL you The pump's flow at full speed at the setpoint pressure (its duty point), in the units of Flow. 0 = not known. Used by FLOW staging and the jockey
jockey BOOL you A small pump that carries the low demand on its own
isVsd BOOL the motor block TRUE on a UT_MOTOR_VSD record (set every scan), FALSE on the others
grpActive, grpRun BOOL the cascade The group owns the pump and calls it (as UT_DUTY)
grpSpeed REAL the cascade The shared speed, %. A UT_MOTOR_VSD uses it as its Auto speed only while a group owns the record; otherwise AutoSpeed as always
grpRunTime TIME the cascade The pump's run time counted by the group since power-up, for HOURS rotation (every pump counts)

capacity and jockey sit in the motor record so they travel with the pump: any
number of pumps, any array bounds, nothing to keep in step in a second array. They
cost a REAL and a BOOL per motor, and a motor that is not in a cascade ignores them.

How it works

Every arrangement

  • Enable starts the loop; its Run starts the group with one pump. A pump is
    available when it is in Auto and ready (healthy, interlock and permissive made, not
    in its restart delay). Hand, Off, OOS and faulted pumps are skipped.
  • One start at a time. Nothing is called while a called pump is not yet running.
    Stage delays count from the last start or stop command, so a pump that waited for
    its turn never starts in the same breath as the next one.
  • Failover. A pump that trips or leaves Auto is released at once and the next one
    is called. A called pump not running failoverDelay after its run command is
    skipped (until it leaves Auto or faults and comes back, or the group next starts
    from none; skip memory for the first 32 pumps) and the next one is called. A pump
    in its restart delay is not ready, so it is never taken for a failed start.
  • maxRunning counts pumps running in Hand. A pump put in Hand while the group is at
    the limit makes the group release one of its own.
  • Stops. Any trip (overpressure TRIP, burst, high flow, a failed sensor with
    STOP, fill timeout) or a loop setting that runs nothing stops every pump at once: a
    fault never leaves a pump running against a closed system. Enable FALSE or sleep
    stops every pump at once too with stopMode ALL_AT_ONCE (the default). With
    UT_PC_STOP_STAGED the called VSDs go to ctrl.minSpeed and the pumps stop one at
    a time: the first at once, then one every stopStep, fixed-speed pumps first, then
    the jockey (stopping, status UT_ST_STOPPING). A trip during a staged stop stops the rest at
    once. Enable back during a staged stop keeps the pumps still running and carries
    on from them.
  • Overpressure WARN holds the speed at the minimum and drops a pump each
    destageDelay while it lasts (never the last one; TRIP is the hard limit).
  • Failed sensor. STOP: everything stops (fault). FALLBACK: one pump (a VSD if one is
    running) at ctrl.fallbackSpeed, the others stop. HOLD: the pumps and the speed stay
    as they are. A hunting trip keeps the pumps and runs at the fallback speed.
  • Burst. ctrl.lowPvAtMax (at full speed and Pv still below half the setpoint)
    waits while another pump can still be added: the next pump is the answer first. With
    every pump in and the pressure still low, it trips. highFlow trips on the flow.
  • Pipe fill (ctrl.pipeFill) runs with one duty pump (a VSD if available), never
    the jockey; staging starts when the fill is done.
  • Sleep. The loop's sleep (low speed or low flow, then boost, then sleep) stops every
    pump; a pressure drop wakes the group with one pump (the jockey first).
  • Power cut. Only the rotation's next pump in turn is kept (saved at once when it
    changes, that is when a pump is started; not for FIXED), so after frequent power cuts
    the first pump does not always lead. The run hours for HOURS (each pump's
    grpRunTime) start at 0, also when the motor records are RETAIN (equal hours go
    by the kept turn), every grpRun starts cleared, nothing is called on the first
    scan, and the pumps start again one at a time. The motors keep their own modes and
    restart delays.
  • Manual speed. ctrl.cmdManual runs the called pumps at ctrl.manualSpeed, with
    the loop's protections still acting (overpressure, burst at the top speed); no pump
    is added or dropped until ctrl.cmdAuto.
  • Each pump's own protection. The cascade sees only what a pump's motor record
    says: a pump whose motor trips (overload, no feedback, a drive fault) is no longer
    ready, so the group releases it and calls the next. A pump's hydraulic checks
    (dry run, prime, seal leak, a pump's own pressure or flow switches) live in its
    UT_PUMP, which has no group link to the cascade: wire
    UT_PUMP.Healthy to the motor block's Interlock, so a pump that fails a hydraulic
    check holds its motor off, reads not ready and is replaced. Without that wire a pump
    running dry stays called.

1. All pumps on VSDs

Every running pump gets the same speed from the loop. A pump is added when the speed
is at its maximum and Pv is still short of sp by more than ctrl.atSpBand for
stageDelay. One is dropped at the minimum speed, or, with dropSpeed set, when the
speed stays below dropSpeed for destageDelay. Set dropSpeed a few % below the
speed the pumps settle at just after one is added (that gap is the hysteresis). With a
lot of static head that speed differs from stage to stage: use FLOW or PER_PUMP
staging there.

2. One VSD plus fixed-speed pumps

The VSD starts first (the first pump is always a VSD when one is available) and trims.
A fixed pump is added when the VSD is at full speed and still short, and dropped first
when the VSD is at its minimum (or below dropSpeed): the VSD is the last to go. If the
VSD is lost, the fixed pumps carry on on the pressure bands (arrangement 3).

3. All fixed-speed

No speed: pumps are added when Pv stays addBand below sp for stageDelay and dropped
when it stays dropBand above sp for destageDelay. Make the bands wider than the
pressure step one pump makes, or the set will cycle (the delays only slow it).

4. Mixed sizes and a jockey

Give each pump its capacity. With FLOW staging the running capacity is the sum of the
pumps running, so a small and a large pump count for what they are. Mark the small
pump jockey := TRUE: it starts first and runs alone. When it cannot keep up (Flow
above addPct % of its capacity, or the pressure short on the PV rule) a duty pump
starts, and the jockey stops once the duty pump runs. When one duty pump is left and
the demand falls (Flow below dropPct % of the jockey's capacity, or the PV drop rule
when its capacity is 0), the jockey starts again and the duty pump stops once it
runs. A jockey that has to hand over on pressure while its flow is below its capacity
is not doing its job (air-locked, worn): it is skipped until the group next starts.
Several pumps may be jockeys: they rotate among themselves, one at a time.

Staging criteria

stageBy Add when Drop when
UT_PC_STAGE_PV With a VSD running: at full speed and still short. Without: Pv addBand below sp With a VSD running: at the minimum speed or below dropSpeed. Without: Pv dropBand above sp
UT_PC_STAGE_FLOW Flow > addPct % of the running capacity Flow < dropPct % of the capacity left after the drop
UT_PC_STAGE_PER_PUMP Flow per running pump > bepMax (and would stay above bepMin with one more) Flow per pump < bepMin (and would stay below bepMax with one fewer)

FLOW and PER_PUMP also add a pump on the PV rule: the pressure is never left short
while a pump is free. If that happens, the flow settings are wrong (a capacity too
high, bepMax too high), so the group warns (pvStaging, bit 11) and stages on the
pressure until it next starts from none. They fall back to PV with a warning while the
flow meter is bad (flowBad, bit 9), or while their settings are not usable (a duty
pump with no capacity, bepMax not above bepMin: wrnConfig).

Rotation (even wear)

rotation Starts Stops first While running
UT_ROT_FIXED From fixedLead, in array order (a lead in its restart delay is waited for, not passed over) The last one started —
UT_ROT_EACH_START The next pump in turn after the last one started The one running longest —
UT_ROT_HOURS (default) The fewest run hours The most run hours A running pump hoursDiff ahead of an idle one hands over
UT_ROT_INTERVAL As EACH_START As EACH_START Every rotateInterval the one running longest hands over

Equal run hours is the answer to "start at random so one pump doesn't do all the
work": the pump with the fewest hours always starts next. Run hours are counted inside
the block (first 32 pumps) and start again at 0 after a power cut (equal hours: the
next in turn, which is kept). A swap (HOURS,
INTERVAL, Rotate, cmdRotate) is between pumps of the same kind (VSD for VSD, fixed
for fixed, jockey for jockey), waits while a pump is to be added or dropped, starts the
new pump first and stops the old one once it runs; at maxRunning the old one stops
first. In arrangement 2 the VSD runs whenever the group runs (it is the trim pump).

Wiring

The cascade before the motors, each in its own unconditional rung. AutoCmd must be
wired (the editor checks it) but is not used while the group owns the motor.

All on VSDs (arrangement 1)

VAR Pumps : ARRAY[1..6] OF UT_MOTOR_DATA; Booster : UT_PUMP_CASCADE; Cfg : UT_PUMP_CASCADE_DATA;
    P : ARRAY[1..6] OF UT_MOTOR_VSD; PV : ARRAY[1..6] OF UT_MOTOR_VSD_DATA; END_VAR
Cfg.ctrl.sp := 5.0;                       (* bar *)
Cfg.ctrl.minSpeed := 45.0;
Cfg.dropSpeed := 70.0;
Booster(Enable := SystemOn, Pv := Header.Value, PvGood := Header.Good, Units := Pumps, Data := Cfg);
P[1](AutoCmd := FALSE, Feedback := P1_Running, DriveReady := P1_Ready, DriveFault := P1_Fault,
     Data := Pumps[1], Vsd := PV[1]);
P1_RunRelay := P[1].Run;
P1_SpeedAO := P[1].SpeedRefRaw;           (* every drive gets the same reference *)
(* ... P[2] to P[6] the same ... *)

One VSD plus contactors and soft starters (arrangement 2)

P1(AutoCmd := FALSE, Feedback := VSD1_Running, DriveFault := VSD1_Fault, Data := Pumps[1],
   Vsd := P1Vsd);                                                                           (* UT_MOTOR_VSD *)
P2(AutoCmd := FALSE, Feedback := K2_Aux, Overload := NOT P2_OL_NC, Data := Pumps[2]);       (* UT_MOTOR, contactor *)
P3(AutoCmd := FALSE, Feedback := SS3_TopOfRamp, DriveFault := SS3_Fault, Data := Pumps[3]); (* UT_MOTOR, soft starter *)
K2_Coil := P2.Run;
SS3_Run := P3.Run;

Nothing to set for the trim pump: the block knows Pumps[1] is a VSD (isVsd) and
starts it first.

All fixed-speed (arrangement 3)

Cfg.addBand := 1.0;                       (* add below 4.0 bar *)
Cfg.dropBand := 1.5;                      (* drop above 6.5 bar *)
Cfg.ctrl.sleep.enable := TRUE;
Cfg.ctrl.sleep.flow := 5.0;               (* sleep below 5 m3/h *)
Booster(Enable := SystemOn, Pv := Header.Value, Flow := FlowMeter.Value, FlowGood := FlowMeter.Good,
        Units := Pumps, Data := Cfg);

Mixed sizes with a jockey (arrangement 4)

Pumps[1].jockey := TRUE;                  (* the small pump *)
Pumps[1].capacity := 12.0;                (* m3/h at the setpoint pressure *)
FOR k := 2 TO 6 DO Pumps[k].capacity := 80.0; END_FOR;
Cfg.stageBy := UT_PC_STAGE_FLOW;
Booster(Enable := SystemOn, Pv := Header.Value, Flow := FlowMeter.Value, FlowGood := FlowMeter.Good,
        Units := Pumps, Data := Cfg);

Invalid settings

  • Runs nothing (Fault, configBad, bit 0): the loop's own (ctrl.sp 0, not a
    number or infinite, ctrl.minSpeed above ctrl.maxSpeed and the rest listed in
    UT_SPEED_CTRL).
  • Warning, safe value used (wrnConfig, bit 10, Warning): stageDelay,
    destageDelay or failoverDelay negative → T#10s / T#20s / T#10s; addBand or
    dropBand negative, not a number or infinite → 0.3; dropSpeed outside 0..100 or not a
    number → 0 (the minimum speed only); addPct / dropPct not in 0 < dropPct < addPct ≤
    100 → 90 / 75; maxRunning negative → 1 (the safe side); an unknown rotation → HOURS,
    an unknown stageBy → PV; FIXED with fixedLead not a pump → the first; hoursDiff or
    rotateInterval negative → 0 (no swap); stopStep negative → T#3s; an unknown
    stopMode → all at once; PER_PUMP with bepMax not above bepMin →
    PV staging; FLOW with a duty pump's capacity 0 → PV staging; a capacity negative, not
    a number or infinite → 0; every pump a jockey (the jockey runs alone); highFlow with a
    bad setpoint, deadband or time. The loop's own warnings are its bit 7.
  • Signals: Pv not a number or infinite (or PvGood FALSE) is a failed sensor (the
    loop's pvFail). Flow not a number or infinite (or FlowGood FALSE) while it is used
    gives flowBad (bit 9) and PV staging; highFlow, low-flow sleep and the flow limit
    then ignore it.