UT_VESSEL — Level → volume, percent, mass

UT_VESSEL — Level → volume, percent, mass

Converts a level into contents for common tank and silo shapes. For odd shapes
use a strapping table with UT_LINEARISE. Replaces
SiloVolumeCalculator, DividedSiloVolumeCalculator and volumeToWeight.

Pins

Pin Type Default What to wire
in Level REAL 0.0 Level from the sensor, in levelUnit (m by default; mm, cm or % of the full height)
out Volume REAL In volumeUnit (m³ by default; L or ML)
out Percent REAL Of total volume
out Mass REAL Volume × density, in massUnit (kg by default; t)
out Free REAL Space left, in volumeUnit
inout Data UT_VESSEL_DATA

Record UT_VESSEL_DATA

Field Type Default Meaning
shape UT_VESSEL_SHAPE UT_SHAPE_VERTICAL UT_SHAPE_VERTICAL (flat-bottom vertical cylinder), UT_SHAPE_CONE (silo: cylinder over a cone/hopper), UT_SHAPE_HORIZONTAL (horizontal cylinder, flat ends), UT_SHAPE_RECT (rectangular), UT_SHAPE_SPHERE
diameter REAL 1.0 In levelUnit (m by default)
height REAL 1.0 Straight-section height, in levelUnit (CONE: the cylinder above the hopper; 0 = hopper only)
length / width REAL 1.0 / 1.0 Horizontal / rectangular, in levelUnit
coneHeight REAL 0.0 Hopper height, in levelUnit
outletDiameter REAL 0.0 Hopper outlet, in levelUnit
levelUnit UT_LEVEL_UNIT UT_LEVEL_M Unit of Level, levelOffset and the dimensions: UT_LEVEL_M (0), UT_LEVEL_MM, UT_LEVEL_CM; or UT_LEVEL_PCT (Level and levelOffset in % of the full level height: the height, the hopper plus the cylinder, or the diameter of a horizontal tank or sphere; the dimensions are then in metres)
volumeUnit UT_VOL_UNIT UT_VOL_NONE Unit of Volume, Free, volume, totalVolume, free and deadVolume: UT_VOL_NONE (0) and UT_VOL_M3 = m³, UT_VOL_L = litres, UT_VOL_ML = megalitres
massUnit UT_MASS_UNIT UT_MASS_KG Unit of Mass, mass and totalMass: UT_MASS_KG (0) or UT_MASS_T (tonnes)
levelOffset REAL 0.0 Added to Level (sensor zero above or below the vessel bottom), in levelUnit
fraction REAL 1.0 Share of the vessel (0.5 = your divided silo)
density REAL 1000.0 kg/m³ (water 1000; for a specific gravity, SG × 1000)
deadVolume REAL 0.0 Unusable volume below the outlet, in volumeUnit, taken off your share's contents and total
volume, totalVolume, percent, mass, totalMass, free REAL Status, in the units above
overfull BOOL Status: level above the top (the outputs show full)
wrnConfig BOOL The settings don't make a vessel; every output is 0
wrnLevel BOOL Level is not a number or infinite; the outputs hold their last values
statusCode UT_STATUS Status: OK, or what is wrong (see Status codes)
faultId UT_FAULT Status: the warning or the setting the status is about (UT_F_NONE when OK)
statusText STRING(30) Status: statusCode and faultId in words, e.g. Config: diameter. The contents are in percent / levelPct
pctLow REAL 0.0 levelPct is 0 % at this level (empty, or the stop level L), in levelUnit, like Level
pctHigh REAL 0.0 levelPct is 100 % at this level (the overflow level). pctLow and pctHigh both 0 = the whole height
levelPct REAL Status: the level as a % of pctLow … pctHigh, the easy number for an operator. Never below 0; above 100 between pctHigh and the top

How it works

  • The level is measured up from the bottom (CONE: from the hopper outlet) and
    clamped: below 0 is empty, above the top is full with overfull set.
  • The partial cone volume is computed at the actual fill height. This fixes the
    overestimate in the original.
  • Units. The dimensions are in the same unit as the level, so the tank
    drawing and the transmitter can be typed in as they are: with
    levelUnit := UT_LEVEL_MM a 2.4 m tank is diameter := 2400.0. With
    UT_LEVEL_PCT the level is a share of the full height and the dimensions are
    in metres (the % needs the real size to give a volume). The volumes and the
    mass each have their own unit setting, so an HMI showing litres or tonnes
    needs no maths in the program. Density is always kg/m³ (SG × 1000).
  • Example: a 2400 mm × 3000 mm vertical water tank, radar in mm, HMI in litres:
    levelUnit := UT_LEVEL_MM, diameter := 2400.0, height := 3000.0, volumeUnit := UT_VOL_L. A level of 1500 mm gives 6786 L (50 %). The same tank
    with the radar scaled 0–100 %: levelUnit := UT_LEVEL_PCT, diameter := 2.4, height := 3.0, and 50 % gives the same 6786 L.
  • wrnConfig is set, and every output is 0 (nothing divides by zero), when a
    needed dimension is 0, negative, not a number or over 10 km (10 000 000 mm), fraction is not
    above 0 and up to 1, density is negative, an outlet is wider than the
    silo, the dead volume fills the whole vessel, or a unit is unknown.
  • Level % (levelPct) is not the same as percent: percent is the share
    of the volume, levelPct the level within a working range, e.g. an effluent
    sump with pctLow := 500.0 (L, mm) and pctHigh := 1800.0 (overflow) shows
    0 % at the stop level and 100 % at overflow. levelOffset is added to both,
    as to Level. A range that is not a number or not rising uses the whole
    height and shows Setting: level % range; the volumes are not affected.

Status codes

statusCode is a UT_STATUS and faultId a UT_FAULT (an HMI reads their numbers);
statusText is the two in words, changed only when one of them changes.

statusCode faultId statusText When
UT_ST_OK OK Normal: the contents are in percent, volume, levelPct …
UT_ST_WARNING UT_F_LEVEL_BAD Warning: level signal bad Level is not a number or infinite (wrnLevel): the last values are held
UT_ST_WARNING UT_F_LEVEL_ABOVE_FULL Warning: level above full overfull
UT_ST_WARN_SETTING UT_F_LEVEL_RANGE Setting: level % range pctLow / pctHigh not a number or pctHigh not above pctLow: the whole height is used
UT_ST_CONFIG UT_F_DIAMETER Config: diameter wrnConfig, by the first problem found: diameter 0 or not a number
UT_ST_CONFIG UT_F_TANK_HEIGHT Config: tank height Height 0 or not a number
UT_ST_CONFIG UT_F_LENGTH_WIDTH Config: length / width Length or width 0 or not a number
UT_ST_CONFIG UT_F_CONE Config: cone / outlet Cone height or outlet negative, an outlet wider than the silo, or no height at all
UT_ST_CONFIG UT_F_FRACTION Config: fraction fraction not above 0 and up to 1
UT_ST_CONFIG UT_F_DENSITY Config: density Negative or not a number
UT_ST_CONFIG UT_F_DEAD_VOLUME Config: dead volume Negative, not a number, or it fills the tank
UT_ST_CONFIG UT_F_LEVEL_OFFSET Config: level offset Not a number or too big
UT_ST_CONFIG UT_F_UNIT Config: unit unknown levelUnit, volumeUnit or massUnit