UT_VESSEL — Level → volume, percent, mass
UT_VESSEL — Level → volume, percent, mass
Converts a level into contents for common tank and silo shapes. For odd shapes
use a strapping table with UT_LINEARISE. Replaces
SiloVolumeCalculator, DividedSiloVolumeCalculator and volumeToWeight.
Pins
| Pin | Type | Default | What to wire | |
|---|---|---|---|---|
| in | Level |
REAL | 0.0 | Level from the sensor, in levelUnit (m by default; mm, cm or % of the full height) |
| out | Volume |
REAL | In volumeUnit (m³ by default; L or ML) |
|
| out | Percent |
REAL | Of total volume | |
| out | Mass |
REAL | Volume × density, in massUnit (kg by default; t) |
|
| out | Free |
REAL | Space left, in volumeUnit |
|
| inout | Data |
UT_VESSEL_DATA |
Record UT_VESSEL_DATA
| Field | Type | Default | Meaning |
|---|---|---|---|
shape |
UT_VESSEL_SHAPE | UT_SHAPE_VERTICAL | UT_SHAPE_VERTICAL (flat-bottom vertical cylinder), UT_SHAPE_CONE (silo: cylinder over a cone/hopper), UT_SHAPE_HORIZONTAL (horizontal cylinder, flat ends), UT_SHAPE_RECT (rectangular), UT_SHAPE_SPHERE |
diameter |
REAL | 1.0 | In levelUnit (m by default) |
height |
REAL | 1.0 | Straight-section height, in levelUnit (CONE: the cylinder above the hopper; 0 = hopper only) |
length / width |
REAL | 1.0 / 1.0 | Horizontal / rectangular, in levelUnit |
coneHeight |
REAL | 0.0 | Hopper height, in levelUnit |
outletDiameter |
REAL | 0.0 | Hopper outlet, in levelUnit |
levelUnit |
UT_LEVEL_UNIT | UT_LEVEL_M | Unit of Level, levelOffset and the dimensions: UT_LEVEL_M (0), UT_LEVEL_MM, UT_LEVEL_CM; or UT_LEVEL_PCT (Level and levelOffset in % of the full level height: the height, the hopper plus the cylinder, or the diameter of a horizontal tank or sphere; the dimensions are then in metres) |
volumeUnit |
UT_VOL_UNIT | UT_VOL_NONE | Unit of Volume, Free, volume, totalVolume, free and deadVolume: UT_VOL_NONE (0) and UT_VOL_M3 = m³, UT_VOL_L = litres, UT_VOL_ML = megalitres |
massUnit |
UT_MASS_UNIT | UT_MASS_KG | Unit of Mass, mass and totalMass: UT_MASS_KG (0) or UT_MASS_T (tonnes) |
levelOffset |
REAL | 0.0 | Added to Level (sensor zero above or below the vessel bottom), in levelUnit |
fraction |
REAL | 1.0 | Share of the vessel (0.5 = your divided silo) |
density |
REAL | 1000.0 | kg/m³ (water 1000; for a specific gravity, SG × 1000) |
deadVolume |
REAL | 0.0 | Unusable volume below the outlet, in volumeUnit, taken off your share's contents and total |
volume, totalVolume, percent, mass, totalMass, free |
REAL | Status, in the units above | |
overfull |
BOOL | Status: level above the top (the outputs show full) | |
wrnConfig |
BOOL | The settings don't make a vessel; every output is 0 | |
wrnLevel |
BOOL | Level is not a number or infinite; the outputs hold their last values |
|
statusCode |
UT_STATUS | Status: OK, or what is wrong (see Status codes) | |
faultId |
UT_FAULT | Status: the warning or the setting the status is about (UT_F_NONE when OK) |
|
statusText |
STRING(30) | Status: statusCode and faultId in words, e.g. Config: diameter. The contents are in percent / levelPct |
|
pctLow |
REAL | 0.0 | levelPct is 0 % at this level (empty, or the stop level L), in levelUnit, like Level |
pctHigh |
REAL | 0.0 | levelPct is 100 % at this level (the overflow level). pctLow and pctHigh both 0 = the whole height |
levelPct |
REAL | Status: the level as a % of pctLow … pctHigh, the easy number for an operator. Never below 0; above 100 between pctHigh and the top |
How it works
- The level is measured up from the bottom (CONE: from the hopper outlet) and
clamped: below 0 is empty, above the top is full withoverfullset. - The partial cone volume is computed at the actual fill height. This fixes the
overestimate in the original. - Units. The dimensions are in the same unit as the level, so the tank
drawing and the transmitter can be typed in as they are: with
levelUnit := UT_LEVEL_MMa 2.4 m tank isdiameter := 2400.0. With
UT_LEVEL_PCTthe level is a share of the full height and the dimensions are
in metres (the % needs the real size to give a volume). The volumes and the
mass each have their own unit setting, so an HMI showing litres or tonnes
needs no maths in the program. Density is always kg/m³ (SG × 1000). - Example: a 2400 mm × 3000 mm vertical water tank, radar in mm, HMI in litres:
levelUnit := UT_LEVEL_MM, diameter := 2400.0, height := 3000.0, volumeUnit := UT_VOL_L. A level of 1500 mm gives 6786 L (50 %). The same tank
with the radar scaled 0–100 %:levelUnit := UT_LEVEL_PCT, diameter := 2.4, height := 3.0, and 50 % gives the same 6786 L. wrnConfigis set, and every output is 0 (nothing divides by zero), when a
needed dimension is 0, negative, not a number or over 10 km (10 000 000 mm),fractionis not
above 0 and up to 1,densityis negative, an outlet is wider than the
silo, the dead volume fills the whole vessel, or a unit is unknown.- Level % (
levelPct) is not the same aspercent:percentis the share
of the volume,levelPctthe level within a working range, e.g. an effluent
sump withpctLow := 500.0(L, mm) andpctHigh := 1800.0(overflow) shows
0 % at the stop level and 100 % at overflow.levelOffsetis added to both,
as toLevel. A range that is not a number or not rising uses the whole
height and showsSetting: level % range; the volumes are not affected.
Status codes
statusCode is a UT_STATUS and faultId a UT_FAULT (an HMI reads their numbers);
statusText is the two in words, changed only when one of them changes.
statusCode |
faultId |
statusText |
When |
|---|---|---|---|
UT_ST_OK |
OK |
Normal: the contents are in percent, volume, levelPct … |
|
UT_ST_WARNING |
UT_F_LEVEL_BAD |
Warning: level signal bad |
Level is not a number or infinite (wrnLevel): the last values are held |
UT_ST_WARNING |
UT_F_LEVEL_ABOVE_FULL |
Warning: level above full |
overfull |
UT_ST_WARN_SETTING |
UT_F_LEVEL_RANGE |
Setting: level % range |
pctLow / pctHigh not a number or pctHigh not above pctLow: the whole height is used |
UT_ST_CONFIG |
UT_F_DIAMETER |
Config: diameter |
wrnConfig, by the first problem found: diameter 0 or not a number |
UT_ST_CONFIG |
UT_F_TANK_HEIGHT |
Config: tank height |
Height 0 or not a number |
UT_ST_CONFIG |
UT_F_LENGTH_WIDTH |
Config: length / width |
Length or width 0 or not a number |
UT_ST_CONFIG |
UT_F_CONE |
Config: cone / outlet |
Cone height or outlet negative, an outlet wider than the silo, or no height at all |
UT_ST_CONFIG |
UT_F_FRACTION |
Config: fraction |
fraction not above 0 and up to 1 |
UT_ST_CONFIG |
UT_F_DENSITY |
Config: density |
Negative or not a number |
UT_ST_CONFIG |
UT_F_DEAD_VOLUME |
Config: dead volume |
Negative, not a number, or it fills the tank |
UT_ST_CONFIG |
UT_F_LEVEL_OFFSET |
Config: level offset |
Not a number or too big |
UT_ST_CONFIG |
UT_F_UNIT |
Config: unit unknown |
levelUnit, volumeUnit or massUnit |
Last updated 2 hours ago