UT_ANNUNCIATOR — Alarm group: horn, lamp, first-out, ack / silence / test
UT_ANNUNCIATOR — Alarm group: horn, lamp, first-out, ack / silence / test
Drives a panel horn and alarm lamp (or beacon) for a group of
UT_ALARMs. It follows the standard annunciator sequence: a new
alarm gives a fast flash plus the horn; after acknowledge the lamp goes steady;
an alarm cleared but not acknowledged gives a slow flash. It also identifies which
alarm came first.
Pins
| Pin | Type | Default | What to wire | |
|---|---|---|---|---|
| in | Ack |
BOOL | FALSE | Rising edge: acknowledge all (panel button) |
| in | Silence |
BOOL | FALSE | Rising edge: silence the horn without acknowledging |
| in | LampTest |
BOOL | FALSE | Lamp and horn on while held |
| out | Horn |
BOOL | ||
| out | Lamp |
BOOL | Fast flash = new, steady = acknowledged, slow flash = cleared/unacked | |
| out | AnyActive |
BOOL | Any alarm present | |
| out | AnyUnacked |
BOOL | Any alarm waiting for acknowledgement | |
| out | FirstOut |
INT | Array index of the first alarm in the current event (none: one below the first index, so 0 for ARRAY[1..n]) |
|
| out | Highest |
UT_PRIORITY | Highest priority present (UT_PRIO_LOW when none) |
|
| out | ActiveCount |
INT | Alarms present | |
| inout | Alarms |
ARRAY[*] OF UT_ALARM_DATA | The group's alarm records | |
| inout | Data |
UT_ANNUN_DATA |
Record UT_ANNUN_DATA
| Field | Type | Default | Meaning |
|---|---|---|---|
hornPriority |
UT_PRIORITY | UT_PRIO_LOW | Only alarms at or above this sound the horn |
hornTimeout |
TIME | T#0s | The horn stops by itself after this (0 = never) |
reHorn |
TIME | T#0s | Sound again after this while still unacknowledged (0 = off) |
fastFlash |
TIME | T#250ms | New alarm: lamp on this long, off this long (0 = steady) |
slowFlash |
TIME | T#1s | Cleared, not acknowledged: lamp on this long, off this long (0 = steady) |
cmdAck |
BOOL | HMI: acknowledge all | |
cmdSilence |
BOOL | HMI: silence the horn | |
firstOut |
INT | Status: same as FirstOut. The HMI shows that alarm's message by its index |
|
activeCount |
INT | Status: alarms present | |
unackedCount |
INT | Status: alarms waiting for acknowledgement |
How it works
| Alarms in the group | Lamp |
|---|---|
| any new (UNACKED) | fast flash |
| else any cleared, not acknowledged (RTN_UNACKED) | slow flash |
| else any present and acknowledged | steady |
| none | off |
- Horn: sounds for each new alarm at or above
hornPriority, untilAck,
Silence,hornTimeout, or until nothing at that priority is left to acknowledge
(e.g. acknowledged one by one on the HMI). A new alarm after a silence sounds it again. - Ack writes
cmdAckinto every unacknowledged alarm in the group; each alarm
acknowledges itself on its next call. The horn stops at once. - First-out: the event starts when the first alarm appears in a quiet group. The
alarm with the earliestsequenceis the first-out (alarms raised in the same
millisecond: the lowest index). It stays until the event is over, i.e. no alarm is
present or waiting for acknowledgement. - Shelved, suppressed and out-of-service alarms are ignored completely.
- A flash shorter than the PLC scan can't be shown: the lamp then changes every scan.
- A command held on acts only once.
- An empty group is fine: everything stays off.
Using it
VAR PumpAlarms : ARRAY[1..3] OF UT_ALARM_DATA; END_VAR
A1(In := P1Fault, Data := PumpAlarms[1]);
A2(In := P2Fault, Data := PumpAlarms[2]);
A3(In := HighLevel, Data := PumpAlarms[3]);
Panel(Ack := AckPB, Silence := SilencePB, LampTest := TestPB, Alarms := PumpAlarms, Data := PanelCfg);
Siren := Panel.Horn;
Beacon := Panel.Lamp;