UT_ANNUNCIATOR — Alarm group: horn, lamp, first-out, ack / silence / test

UT_ANNUNCIATOR — Alarm group: horn, lamp, first-out, ack / silence / test

Drives a panel horn and alarm lamp (or beacon) for a group of
UT_ALARMs. It follows the standard annunciator sequence: a new
alarm gives a fast flash plus the horn; after acknowledge the lamp goes steady;
an alarm cleared but not acknowledged gives a slow flash. It also identifies which
alarm came first.

Pins

Pin Type Default What to wire
in Ack BOOL FALSE Rising edge: acknowledge all (panel button)
in Silence BOOL FALSE Rising edge: silence the horn without acknowledging
in LampTest BOOL FALSE Lamp and horn on while held
out Horn BOOL
out Lamp BOOL Fast flash = new, steady = acknowledged, slow flash = cleared/unacked
out AnyActive BOOL Any alarm present
out AnyUnacked BOOL Any alarm waiting for acknowledgement
out FirstOut INT Array index of the first alarm in the current event (none: one below the first index, so 0 for ARRAY[1..n])
out Highest UT_PRIORITY Highest priority present (UT_PRIO_LOW when none)
out ActiveCount INT Alarms present
inout Alarms ARRAY[*] OF UT_ALARM_DATA The group's alarm records
inout Data UT_ANNUN_DATA

Record UT_ANNUN_DATA

Field Type Default Meaning
hornPriority UT_PRIORITY UT_PRIO_LOW Only alarms at or above this sound the horn
hornTimeout TIME T#0s The horn stops by itself after this (0 = never)
reHorn TIME T#0s Sound again after this while still unacknowledged (0 = off)
fastFlash TIME T#250ms New alarm: lamp on this long, off this long (0 = steady)
slowFlash TIME T#1s Cleared, not acknowledged: lamp on this long, off this long (0 = steady)
cmdAck BOOL HMI: acknowledge all
cmdSilence BOOL HMI: silence the horn
firstOut INT Status: same as FirstOut. The HMI shows that alarm's message by its index
activeCount INT Status: alarms present
unackedCount INT Status: alarms waiting for acknowledgement

How it works

Alarms in the group Lamp
any new (UNACKED) fast flash
else any cleared, not acknowledged (RTN_UNACKED) slow flash
else any present and acknowledged steady
none off
  • Horn: sounds for each new alarm at or above hornPriority, until Ack,
    Silence, hornTimeout, or until nothing at that priority is left to acknowledge
    (e.g. acknowledged one by one on the HMI). A new alarm after a silence sounds it again.
  • Ack writes cmdAck into every unacknowledged alarm in the group; each alarm
    acknowledges itself on its next call. The horn stops at once.
  • First-out: the event starts when the first alarm appears in a quiet group. The
    alarm with the earliest sequence is the first-out (alarms raised in the same
    millisecond: the lowest index). It stays until the event is over, i.e. no alarm is
    present or waiting for acknowledgement.
  • Shelved, suppressed and out-of-service alarms are ignored completely.
  • A flash shorter than the PLC scan can't be shown: the lamp then changes every scan.
  • A command held on acts only once.
  • An empty group is fine: everything stays off.

Using it

VAR  PumpAlarms : ARRAY[1..3] OF UT_ALARM_DATA;  END_VAR

A1(In := P1Fault, Data := PumpAlarms[1]);
A2(In := P2Fault, Data := PumpAlarms[2]);
A3(In := HighLevel, Data := PumpAlarms[3]);
Panel(Ack := AckPB, Silence := SilencePB, LampTest := TestPB, Alarms := PumpAlarms, Data := PanelCfg);
Siren := Panel.Horn;
Beacon := Panel.Lamp;