UT_RAMP — Rate-limited setpoint

UT_RAMP — Rate-limited setpoint

Moves an output toward a target at a set rate: soft speed changes, gentle valve
moves, setpoint ramps for heating.

Pins

Pin Type Default What to wire
in In REAL 0.0 Target
in RateUp REAL 10.0 Units per RateUnit rising (0 = jump)
in RateDown REAL 10.0 Units per RateUnit falling (0 = jump)
in RateUnit UT_RATE_UNIT UT_PER_SEC The rates are per second (UT_PER_SEC), minute, hour or day, e.g. a temperature setpoint ramped in °C per minute
in Track BOOL FALSE Output follows In immediately (e.g. while stopped)
out Out REAL The ramped value
out Ramping BOOL Out ≠ In: still moving
out BadInput BOOL In or a rate is not a number: Out is held

How it works

  • Out moves toward In at RateUp or RateDown and stops exactly on In. It
    never overshoots, and a target reversed mid-ramp turns straight round.
  • A rate of 0 (or infinity) means no limit: Out jumps. The sign of a rate is
    ignored, so −5 acts as 5.
  • After a restart Out starts at 0 and ramps up to In. Wire Track to start
    from In instead; when Track goes FALSE the ramp carries on from there.
  • Timing uses real elapsed time, so the rate is the same at any task interval,
    and very slow rates (0.001 per second) still add up exactly.
  • A NaN or infinite In, or a NaN rate, holds Out where it is and sets
    BadInput (Ramping is FALSE meanwhile). The time it lasted does not count,
    so Out does not jump to catch up afterwards. Track does not follow a bad In.

Using it

SpeedRamp(In := SpeedSP, RateUp := 5.0, RateDown := 10.0, Track := NOT Running);
DriveSpeed := SpeedRamp.Out;   (* Hz, 5 Hz/s up, 10 Hz/s down *)