UT_PROTECT — One protection: delay, response and reset
UT_PROTECT — One protection: delay, response and reset
The protection every device block uses for its faults, and usable on its own for
any condition that should warn or stop something. You work out the condition;
the record decides what happens. See conventions.
Pins
| Pin | Type | Default | What to wire | |
|---|---|---|---|---|
| in | Cause |
BOOL | FALSE | The condition is present now (overload, no feedback, high pressure…) |
| in | ResetReq |
BOOL | FALSE | Reset request this scan (a pushbutton edge, an HMI command) |
| in | RetryWindow |
TIME | T#1h | RETRY counts trips within this window. T#0s = no window: the count is cleared only by a reset (or a power cycle), so trip number maxRetries + 1 always latches |
| out | Trip |
BOOL | Hold the device off | |
| out | Warn |
BOOL | Warning in effect | |
| out | Event |
BOOL | One scan: the condition has just become active (after the delay) | |
| out | Reset |
BOOL | One scan: a latched trip or warning was reset | |
| out | BadSetting |
BOOL | A setting is invalid: a negative delay, recover or RetryWindow, or a negative maxRetries with RETRY. It acts as 0 (see below). FALSE while the response is OFF |
|
| inout | Prot |
UT_PROTECTION | Settings and status |
Record UT_PROTECTION
| Field | Type | Default | Meaning |
|---|---|---|---|
response |
UT_RESPONSE | UT_RESP_OFF | UT_RESP_OFF ignore · UT_RESP_WARN warn only · UT_RESP_TRIP stop |
delay |
TIME | T#0s | The condition must last this long |
reset |
UT_RESET_MODE | UT_RST_AUTO | UT_RST_AUTO · UT_RST_RETRY · UT_RST_MANUAL |
recover |
TIME | T#10s | AUTO / RETRY: the condition must be gone this long before the trip clears |
maxRetries |
INT | 3 | RETRY: trips allowed in RetryWindow; the next one latches (0 = the first trip latches) |
active, tripped, retries, count |
Status: condition present, held, retries used, total events | ||
timeLeft |
TIME | Status: the countdown in progress: the delay still to run while the condition is present, or the recover / retry wait still to go while an AUTO or RETRY trip holds and its condition has gone. T#0s when nothing counts (no condition, the condition still holding a trip, a MANUAL trip or used-up RETRY waiting for a reset, a warning) |
How it works
| Response | AUTO | RETRY | MANUAL |
|---|---|---|---|
| WARN | Warn while the condition is present |
as AUTO | Warn until reset |
| TRIP | Trip until the condition has been gone recover |
as AUTO, but trip number maxRetries + 1 within the window latches |
Trip until a reset with the condition gone |
- A reset while the condition is still present is refused.
- A reset also clears the retry count; a quiet window clears it by itself (not with
RetryWindowT#0s: then only a reset or a power cycle clears it). - Invalid settings act as 0, the safe side: a negative
delayorrecoveracts
at once, a negativeRetryWindowis no window, a negativemaxRetrieslatches on
the first trip.BadSettingtells the device block, which raises a config warning. - Setting
responseto OFF clears everything at once. timeLeftis the countdown an HMI shows next to the fault. For a simple
display, UT_RESET_TEXT turns it into ", auto reset in 25 s"
or ", retrying 2 of 3 in 25 s".
Using it
HighTemp(Cause := Temp > 85.0, ResetReq := ResetPB, Prot := HighTempCfg);
Heater := HeatCmd AND NOT HighTemp.Trip;
For block builders: UT_PROT_RUN
The same logic as a function, UT_PROT_RUN, which the device blocks use inside. A
function has no instance of its own, so the protection record is not copied: the
block that owns the protection keeps its working state in a UT_PROT_ST and passes
both in every scan.
| Pin | Type | What to wire | |
|---|---|---|---|
| in | TNow |
TIME | TIME() of this scan |
| in | Cause, ResetReq, RetryWindow |
As the block's pins above | |
| inout | Prot |
UT_PROTECTION | Settings and status |
| inout | St |
UT_PROT_ST | The working state, one per protection. Its trip, warn, event, reset and badSetting are the block's Trip, Warn, Event, Reset and BadSetting. Not for HMIs |
| returns | BOOL | Trip |
x := UT_PROT_RUN(TNow := TIME(), Cause := Temp > 85.0, ResetReq := ResetPB,
RetryWindow := T#1h, Prot := HighTempCfg, St := HighTempSt);