UT_ALARM_TABLE — All of a site's alarms in one block

UT_ALARM_TABLE — All of a site's alarms in one block

Every alarm of a project in one array, one row each, with the siren (horn), the
beacon and one status line for the whole site. Each row has its own on and off
delay, warn or trip, and how it clears: by itself, latched until reset, or
retrying a few times and then locking out. The block holds no texts: the HMI shows
the row numbers, states and codes in its own words.

For alarms that need shelving, priorities and time stamps, use
UT_ALARM per alarm with UT_ANNUNCIATOR.

Pins

Pin Type Default What to wire
in Silence BOOL FALSE Rising edge: silence the siren. A new alarm sounds again. Does not acknowledge
in Reset BOOL FALSE Rising edge: acknowledge every alarm, and reset the latched and locked-out ones whose condition has gone
out AnyWarning BOOL A warning alarm is on
out AnyTrip BOOL A trip alarm is on: stop the plant (or use each row's q)
out AnyUnacked BOOL An alarm waits for acknowledging (flash the lamp, e.g. with UT_FLASHER)
out Siren BOOL Sound the siren / horn
out Beacon BOOL Light the beacon: an alarm is on, or waits for acknowledging
inout Alarms ARRAY[*] OF UT_AT_ALARM One row per alarm: its settings, its condition and its state
inout Data UT_ALARM_TABLE_DATA HMI commands and the summary

Number the rows from 1 (ARRAY[1..n]). The row number is the alarm's number for
the HMI and SCADA, and 0 means "none" in first and latest: a row 0 never shows
in the status line. Put the most important alarms in the lowest rows.

Using it

VAR
  AlmTab : UT_ALARM_TABLE;
  Alarms : ARRAY[1..20] OF UT_AT_ALARM;  (* 1 = sump high-high, 2 = pump 1 overload, ... *)
  AlmSt  : UT_ALARM_TABLE_DATA;
END_VAR

IF FirstScan THEN
  Alarms[1].response := UT_RESP_TRIP;
  Alarms[1].onDelay := T#5s;
  Alarms[1].code := UT_F_HIGH_HIGH;
  Alarms[2].response := UT_RESP_TRIP;
  Alarms[2].reset := UT_RST_MANUAL;
  Alarms[2].code := UT_F_OVERLOAD;
END_IF;

Alarms[1].in := SumpHighHigh;
Alarms[2].in := M1.Fault;
AlmTab(Silence := SilenceBtn, Reset := ResetBtn, Alarms := Alarms, Data := AlmSt);
Horn := AlmTab.Siren;
Beacon := AlmTab.Beacon;

One alarm UT_AT_ALARM

Your logic writes in every scan. The settings have working defaults: a row with
only in wired is a warning that sounds the siren and clears by itself.

Field Type Default Meaning
in BOOL FALSE The condition, written by your logic every scan
response UT_RESPONSE UT_RESP_WARN UT_RESP_OFF (the alarm is switched off) · UT_RESP_WARN (a warning) · UT_RESP_TRIP (the plant must stop: use q or AnyTrip)
reset UT_RESET_MODE UT_RST_AUTO UT_RST_AUTO: clears by itself when the condition goes · UT_RST_MANUAL: latched, stays on until Reset · UT_RST_RETRY: clears by itself, but locks out after too many raises (below)
onDelay TIME T#0s The condition must last this long to raise the alarm
offDelay TIME T#0s And be gone this long to clear it, or to allow its reset
maxRetries USINT 3 RETRY: raises that may clear by themselves in the window. The next one locks out (0 = the first one locks out)
retryWindow TIME T#0s RETRY: the window, from the first raise counted. T#0s = no window: the count clears only on a Reset
siren BOOL TRUE This alarm sounds the siren
rearm TIME T#0s Silenced or acknowledged but still on after this long: it sounds again and needs acknowledging again. T#0s = never
code UT_FAULT UT_F_CONDITION What it is, for the status line and SCADA (e.g. UT_F_OVERLOAD, UT_F_HIGH_HIGH, UT_F_DRY_RUN)
state UT_AT_STATE Status: below
q BOOL Status: the alarm is on (ACTIVE, LATCHED or LOCKED)
unacked BOOL Status: waits for acknowledging
retries USINT Status: raises counted in the retry window
cond, inPrev, silenced, t, tWin, tAck Kept by the block. Don't write them

States UT_AT_STATE

No. State Condition q Next
0 UT_AT_NORMAL Gone The condition lasts onDelay → ACTIVE (RETRY past its count: LOCKED)
1 UT_AT_ACTIVE Present yes Gone for offDelay: MANUAL → LATCHED; AUTO / RETRY → RETURNED if not yet acknowledged, else NORMAL
2 UT_AT_RETURNED Went before it was acknowledged Reset → NORMAL; the condition again → ACTIVE
3 UT_AT_LATCHED Gone (MANUAL) yes Reset → NORMAL; the condition again → ACTIVE
4 UT_AT_LOCKED Present or gone yes Reset once the condition has gone → NORMAL. The condition again: stays LOCKED and is annunciated again
5 UT_AT_OFF (ignored) response set to WARN or TRIP → NORMAL

Record UT_ALARM_TABLE_DATA

Field Type Meaning
cmdSilence BOOL HMI: silence the siren
cmdReset BOOL HMI: acknowledge all, reset what can be reset
statusCode UT_STATUS Status: the first trip, else the first warning, else OK (below)
faultId UT_FAULT Status: that alarm's code
statusText STRING(30) Status: the two in words, e.g. Latched: overload
first INT Status: the row shown in the status line (0 = none)
latest INT Status: the row raised last (0 = none yet)
onCount INT Status: alarms on (q)
tripCount INT Status: trip alarms on
unackedCount INT Status: alarms waiting for acknowledging

The commands act once, on their rising edge, and the block clears them. A command
held on (a Modbus coil left on) acts once.

Status

The status line names one alarm: the lowest row with a trip on, else the lowest
row with a warning on. A trip in row 9 beats a warning in row 1. The words are the
prefix and the alarm's code (UT_STATUS_TEXT). The text is
rebuilt only when the code or the fault changes. The numbers are in
conventions.

statusCode faultId statusText When
UT_ST_FAULT its code Fault: <code>, e.g. Fault: overload The first trip is ACTIVE
UT_ST_FAULT_RESET its code Latched: <code> The first trip is LATCHED (MANUAL, the condition has gone)
UT_ST_FAULT_LOCKED its code Locked: <code>, e.g. Locked: dry run The first trip is LOCKED
UT_ST_WARNING its code Warning: <code>, e.g. Warning: high No trip on; the first warning is on (ACTIVE, LATCHED or LOCKED alike)
UT_ST_WARN_SETTING UT_F_SETTING Setting: a setting No alarm on, and a row has a negative time
UT_ST_OK OK No alarm on

A row with no code of its own reads condition, e.g. Warning: condition.

How it works

  1. Delays. The condition must last onDelay to raise the alarm, and be gone
    offDelay to clear it. Each delay counts from the last change of in, so a
    pulse shorter than onDelay is ignored.
  2. Raise. The alarm goes ACTIVE (or LOCKED, below), waits for acknowledging,
    and sounds the siren if its siren is TRUE. latest is set to its row.
  3. Clear. When the condition has gone: AUTO and RETRY alarms go to RETURNED until
    acknowledged (or straight to NORMAL if already acknowledged); MANUAL alarms go to
    LATCHED and stay on until Reset.
  4. Retry and lockout (RETRY). Each raise is counted (retries) from the first in
    the window. Up to maxRetries raises clear by themselves; the next one within
    retryWindow goes LOCKED and stays on until a Reset with the condition gone.
    When the window has passed, the count starts again. With retryWindow T#0s
    the count clears only on a Reset.
  5. Reset (the pin or cmdReset) acknowledges every alarm. For each alarm whose
    condition has gone (and stayed gone offDelay), it also clears retries and
    puts a LATCHED, LOCKED or RETURNED alarm back to NORMAL. Pressed while the
    condition is still there, it only acknowledges.
  6. Siren. An alarm sounds while its siren is TRUE, it waits for acknowledging,
    it is not silenced, and its condition is present (ACTIVE, or LOCKED with the
    condition back). So the siren stops on Silence, on Reset, or when the
    condition goes; the beacon stays on until it is acknowledged.
  7. Silence (the pin or cmdSilence) silences the alarms sounding now. It does
    not acknowledge them. A new alarm, raised later, sounds again.
  8. Re-arm. An alarm whose condition is still present rearm after it was
    silenced or acknowledged waits for acknowledging again and sounds again (if
    siren). T#0s = never.
  9. Beacon is on while any alarm is on (q) or waits for acknowledging. It is
    steady: flash a lamp from AnyUnacked if you want one.
  10. Response OFF switches a row off: its state is OFF, nothing is annunciated,
    its retries are cleared. Set back to WARN or TRIP, it starts at NORMAL.
  11. Changing a LATCHED alarm's reset from MANUAL to AUTO or RETRY puts it back to
    NORMAL.

Invalid settings

  • A negative onDelay, offDelay, retryWindow or rearm works as T#0s, with
    Setting: a setting while no alarm is on.
  • An unknown response acts as WARN, an unknown reset as AUTO.

Power cut

The block keeps nothing: every alarm starts NORMAL, and a condition still present
raises it again (after onDelay). This assumes the Alarms array is not RETAIN:
a retained array keeps the states with the settings. Write the settings from your
program instead (as in the example).