UT_ALARM — One alarm (ISA-18.2 states)
UT_ALARM — One alarm (ISA-18.2 states)
Turns a condition into a properly managed alarm: on/off delays, acknowledge,
latching, operator shelving, suppress-by-design (Inhibit), out-of-service,
priority and counts. Group alarms with UT_ANNUNCIATOR by
putting their records in an array. The alarm's message is kept in the HMI, by the
alarm's number (its place in the array); the record holds no text.
Pins
| Pin | Type | Default | What to wire | |
|---|---|---|---|---|
| in | In |
BOOL | FALSE | The alarm condition |
| in | Inhibit |
BOOL | FALSE | Suppressed by design (e.g. low-flow alarm while the pump is off) |
| in | Ack |
BOOL | FALSE | Rising edge: acknowledge |
| in | Clock |
DT | unwired | Real-time clock for the time stamps (e.g. UT_SCHEDULE's Data.localTime); unwired = the controller clock (UTC) |
| out | Q |
BOOL | Alarm to annunciate (active, or latched and not yet acknowledged) | |
| out | Unacked |
BOOL | Needs acknowledging (flash it) | |
| out | Active |
BOOL | Condition present now (after the delays), even while shelved or suppressed | |
| inout | Data |
UT_ALARM_DATA |
Record UT_ALARM_DATA
| Field | Type | Default | Meaning |
|---|---|---|---|
onDelay |
TIME | T#0s | The condition must last this long to raise the alarm |
offDelay |
TIME | T#0s | And be gone this long to clear it |
latch |
BOOL | FALSE | Q stays on until the condition has cleared and it's acknowledged |
ackRequired |
BOOL | TRUE | FALSE = no acknowledge needed (event / status alarm); latch then has no effect |
priority |
UT_PRIORITY | UT_PRIO_MEDIUM | |
maxShelve |
TIME | T#8h | Longest an operator may shelve it. T#0s = shelving not allowed |
shelveFor |
TIME | T#0s | How long cmdShelve shelves it. T#0s = maxShelve; longer than maxShelve is cut to it |
cmdAck |
BOOL | HMI: acknowledge | |
cmdShelve |
BOOL | HMI: shelve for shelveFor (again while shelved: starts over) |
|
cmdUnshelve |
BOOL | HMI: unshelve now | |
cmdOutOfService |
BOOL | HMI: out of service | |
cmdInService |
BOOL | HMI: back in service | |
cmdResetCount |
BOOL | HMI: count back to 0 |
|
state |
UT_ALARM_STATE | Status, see below | |
active |
BOOL | Status: same as Active |
|
unacked |
BOOL | Status: same as Unacked |
|
shelvedFor |
TIME | Status: shelve time left | |
count |
UDINT | Status: alarms raised | |
lastDuration |
TIME | Status: how long the condition lasted last time | |
sequence |
UDINT | Status: when it was last raised (milliseconds, wraps after 49 days). Orders alarms for the first-out | |
grpNew |
BOOL | Set when the alarm is raised, cleared by UT_ANNUNCIATOR (so it knows to sound the horn). Don't write it | |
raisedAt |
DT | Status: when it was last raised (from Clock) |
|
ackedAt |
DT | Status: when it was last acknowledged | |
clearedAt |
DT | Status: when its condition last cleared |
States — UT_ALARM_STATE
| State | Condition | Q | Unacked | Next |
|---|---|---|---|---|
UT_ALM_NORMAL (0) |
clear | condition → UNACKED | ||
UT_ALM_UNACKED |
present | ✔ | ✔ | ack → ACKED; clears → RTN_UNACKED |
UT_ALM_ACKED |
present | ✔ | clears → NORMAL | |
UT_ALM_RTN_UNACKED |
cleared before ack | only if latch |
✔ | ack → NORMAL; comes back → UNACKED |
UT_ALM_SHELVED |
any | expiry or cmdUnshelve |
||
UT_ALM_SUPPRESSED |
any | Inhibit off |
||
UT_ALM_OOS |
any | cmdInService |
- Out of service beats suppressed, suppressed beats shelved.
- A shelved, suppressed or out-of-service alarm is hidden completely. When it comes back
with the condition still present it's raised again as a new alarm (counted, needs
an ack); if the condition has gone it comes back NORMAL. - With
ackRequiredFALSE the alarm goes straight to ACKED; switchingackRequired
off acknowledges it. - When two commands arrive together the alarm stays live:
cmdInServicebeats
cmdOutOfService,cmdUnshelvebeatscmdShelve. - A command held on (a Modbus coil left on, a debugger force) acts only once. A command
written again in the very next scan counts as held. - An ack while shelved, suppressed or out of service does nothing.
- Negative times count as zero.
raisedAt,ackedAtandclearedAtare stamped fromClockand each keeps the
last one (DT#1970-01-01-00:00:00until the first). Unwired, the controller clock
is used, which is UTC; wire a local clock for local times.
Power cut
Nothing is kept. After a power-up the alarm is in service and not shelved, count is
0, and an alarm whose condition is still present is raised again.
Using it
LowFlowAlm(In := Flow < 2.0, Inhibit := NOT PumpRunning, Ack := AckPB, Data := Alarms[3]);