02 - Getting started

02 - Getting started

A PLC reading a real device, then answering one. Every step says what it does
and why, because the why is what lets you change it afterwards.

What you need

An OpenPLC Runtime and something to talk to. A drive, a meter, a
temperature controller — anything with an RS-485 port and a manual. Or, with no
hardware at all, any Modbus simulator on your own machine over TCP.

Or a board — ESP32 or similar — with an RS-485 transceiver. The only
difference is which transport you name.

You also need the library installed in the editor: Libraries → Install, and
pick modbee-modbus.stlib.

Step 1 — start a node

Make a project. Add a program called net, and in it declare a node and call
it:

PROGRAM net
VAR
    node : MODBUS_NODE;
END_VAR

node( TRANSPORT := MODBUS_RUNTIME_SERIAL,
      SERIAL_DEVICE    := '/dev/ttyUSB0',
      SERIAL_BAUD      := 19200 );

END_PROGRAM

That is a complete Modbus client. It will open the port and is ready to ask
anybody anything.

BAUD and the wiring are the only things you must get right. Parity
defaults to even, which is the Modbus default and what most devices ship with.
If your device's manual says 8N1, say so — SERIAL_PARITY := MODBUS_PARITY_NONE_8N1 —
and note that MODBUS_PARITY_NONE on its own means 8N2, which is what the
specification actually requires when parity is off.

For TCP instead:

node( TRANSPORT := MODBUS_RUNTIME_TCP,
      TCP_HOST      := '192.168.1.50' );

Step 2 — give it a task of its own

This is the one piece of setup that is not obvious and matters more than
anything else on this page.

MODBUS_NODE is the only block that touches the wire. It transmits,
receives, retries and times out — once per call. So how often it is called is
the floor on how fast anything happens.

Put it, with every block given it, in a fast task of their own, and leave
the rest of your program in a normal one:

task interval priority holds
APP_TASK T#20ms 0 the machine - no Modbus block at all
NET_TASK T#1ms on the Runtime, T#50ms on a board to start 20 MODBUS_NODE and every block given it

The two trade values through globals, each written by one task. A Modbus block
in any other task than its node's says MODBUS_WRONG_TASK and does nothing.

A node called every 20 ms spends most of the bus waiting for a task to come
round. 10 - Scan rate has the numbers.

Step 3 — check it opened

Add a status block so you can see what is happening:

VAR
    node   : MODBUS_NODE;
    health : MODBUS_STATUS;
END_VAR

node  ( TRANSPORT := MODBUS_RUNTIME_SERIAL,
        SERIAL_DEVICE    := '/dev/ttyUSB0', SERIAL_BAUD := 19200 );
health( NODE := node );

node.READY is TRUE once the port opened. If it is FALSE, node.STATUS
says why in a code and node.LAST_ERROR says it in the operating system's own
words
— "No such file or directory" for a wrong path, "Permission denied"
for a user who is not in the dialout group. Read that one first; it says far
more than a code can.

Note how node is passed to health on its NODE pin. That is how every
block gets at the link, and it must be assigned at every call — leaving it out
is a compile error. That is deliberate: a block with no node is a block that
silently does nothing.

Step 4 — read something

Now ask a device for some registers. Put this in your app program, in the
slower task:

PROGRAM app
VAR
    node : MODBUS_NODE;     (* the same instance, passed in *)
    rd   : MODBUS_READ;
    regs : ARRAY [0..3] OF WORD;
    go   : BOOL;
END_VAR

rd( NODE := node, REQ := go, UNIT := 1,
    FC := MODBUS_FC03_READ_HOLDING_REGISTERS,
    ADDRESS := 40, VALUE := regs );

A rising edge on go reads holding registers 40 to 43 from unit 1.

You did not type a length. regs is four elements, so four registers are
read. Resize the array later and the read follows it. Getting a length wrong is
the commonest mistake anyone makes on a Modbus system and the one that reads
past the end of a buffer, so the block does not ask for a number it can work
out. There is a LENGTH pin if you genuinely want a partial transfer, and
anything larger than the array is refused rather than obeyed.

The answer does not arrive on this scan. rd.BUSY goes TRUE, and some
scans later rd.DONE pulses for exactly one scan with the values in regs:

IF rd.DONE THEN
    motorSpeed := regs[0];
END_IF;

If it failed, rd.ERROR pulses instead and rd.STATUS says why.
MODBUS_TIMEOUT means nothing answered. MODBUS_REFUSED means the device
answered and said no — which is progress, because it proves the wiring works.

Holding go high is safe. It reads once on the edge, not once a scan.

Step 5 — a value that keeps itself up to date

Most of what a PLC reads, it wants to keep reading. That is MODBUS_WATCH:

VAR
    level     : MODBUS_WATCH;
    tankLevel : ARRAY [0..1] OF WORD;
END_VAR

level( NODE := node, UNIT := 1,
       FC := MODBUS_FC04_READ_INPUT_REGISTERS,
       ADDRESS := 30, EVERY := T#2s,
       VALUE := tankLevel );

No request pin. Every two seconds it decides a read is due, hands it to the
same queue everything else uses, and the answer lands in tankLevel.

And it tells you how much to believe it. This is the part worth
understanding:

IF level.QUALITY = MODBUS_QUALITY_GOOD AND tankLevel[0] > 900 THEN
    closeInletValve := TRUE;
END_IF;

Without that check, a device that quietly failed leaves tankLevel[0] holding
the last number it ever sent — plausible, steady, and wrong. QUALITY is what
separates a live reading from a fossil. See
05 - Reading and writing.

Step 6 — be a device yourself

Turn it round: let a SCADA package or an HMI read your PLC. Tell the node to
answer as well as ask, and say what lives where:

VAR
    node    : MODBUS_NODE;
    pub     : MODBUS_MAP;
    trend   : ARRAY [0..9] OF WORD;
END_VAR

node( TRANSPORT := MODBUS_RUNTIME_SERIAL,
      SERIAL_DEVICE    := '/dev/ttyUSB0', SERIAL_BAUD := 19200,
      ROLE      := MODBUS_ROLE_BOTH,
      SERIAL_UNIT_ID   := 7 );

pub( NODE := node, TABLE := MODBUS_INPUT_REGISTERS,
     ADDRESS := 100, VALUE := trend );

SERIAL_UNIT_ID := 7 is the address other devices call your PLC by. trend now is
input registers 100 to 109 — a client reading them gets whatever the array
holds at that instant. Nothing is copied and there is no request pin, because
once bound the variable is the register.

MODBUS_INPUT_REGISTERS is read-only, so nobody can write it. Use
MODBUS_HOLDING_REGISTERS for something you want a client to be able to
change. See 04 - Being a device.

What you have

A PLC that reads a device on demand, keeps one value permanently fresh with a
quality you can interlock on, and answers a SCADA package on the same wire.

Next: 03 - The node block