UT_SYSTEM_MODE — The plant's mode: Off / Manual / Auto

UT_SYSTEM_MODE — The plant's mode: Off / Manual / Auto

Most sites have one mode for the whole plant on top of the device modes: Off
(nothing runs), Manual (run while someone holds a run request) and Auto
(the program runs the plant), often with a choice of auto programs. UT_SYSTEM_MODE
is that, with local / remote and a safe manual run.

Pins

Pin Type Default What to wire
in LocalRun BOOL FALSE Local manual run request, held: a run button held, a run switch, the local HMI's run button
in RemoteRun BOOL FALSE Remote manual run request, held (SCADA)
in RemoteEnabled BOOL TRUE FALSE: local control, RemoteRun is refused
in CommsOk BOOL TRUE FALSE: the remote link is down, RemoteRun is dropped (wire UT_WATCHDOG's NOT CommsFail)
in SwManual / SwAuto BOOL FALSE Plant selector switch (when modeSource uses it)
in ForceOff BOOL FALSE TRUE holds the plant Off (an e-stop healthy relay dropped, a tariff block). The chosen mode comes back after
out Mode UT_SYS_MODE UT_SYS_OFF · UT_SYS_MANUAL · UT_SYS_AUTO
out IsOff / IsManual / IsAuto BOOL
out AutoType INT The auto type chosen (1 … autoTypes). Your program reads it while IsAuto
out ManualRun BOOL Run now: Manual, with a run request held
out Changed BOOL One scan: the mode or the auto type has just changed
inout Data UT_SYSTEM_MODE_DATA Settings, commands and status

Record UT_SYSTEM_MODE_DATA

Field Type Default Meaning
modeSource UT_MODE_SOURCE UT_SRC_HMI UT_SRC_HMI (cmdMode) · UT_SRC_SWITCH (SwManual / SwAuto) · UT_SRC_REMOTE (selector Off and Manual local, Auto hands over to cmdMode)
powerUp UT_POWERUP UT_PU_LAST After a power cut or PLC stop / start: UT_PU_LAST the mode comes back; UT_PU_OFF back to Off
autoTypes INT 1 Auto types offered: 1 … autoTypes (below 1 acts as 1)
manualMaxRun TIME T#0s A manual run stops after this (0 = no limit)
cmdMode INT −1 HMI: 0 Off · 1 Manual · 2 Auto. Acts once when a new value arrives; anything else ignored. Set back to −1
cmdAutoType INT −1 HMI: 1 … autoTypes. Acts once when a new value arrives; anything else ignored. Set back to −1
mode UT_SYS_MODE status
autoType INT status: the auto type chosen (kept over a power cut)
manualRun BOOL status: a manual run is on
runFrom UT_CMD_FROM status: who holds it: UT_FROM_LOCAL · UT_FROM_REMOTE (local first when both) · UT_FROM_NONE
runTime TIME status: how long the manual run has lasted (0 when not running)
timeLeft TIME status: manual run time left (0 without manualMaxRun)
remote BOOL status: RemoteEnabled
statusCode UT_STATUS status: see Status codes
faultId UT_FAULT status: the setting that keeps it off (UT_F_MANUAL_MAX_RUN), else UT_F_NONE
statusText STRING(30) status: statusCode and faultId in words, e.g. Manual: running (remote). The auto type is in autoType, the time left in timeLeft

How it works

The mode works as a device mode (UT_MODE_SELECT): from the
HMI, a selector, or both, starting at Off, with powerUp deciding what comes back
after a power cut. The auto type is kept over a power cut in every case.
Commands act once, when a new value arrives; with two masters put
UT_CMD in front of cmdMode.

Manual run: ManualRun is on in Manual while a run request is held:
LocalRun, or RemoteRun while RemoteEnabled and CommsOk. Drop it and the
run stops. A request must be released and given again before it runs:

  • after a power cut or PLC start (a run switch left on doesn't start the plant);
  • after the mode changes (entering Manual with the button held);
  • after the remote side was refused (local control) or cut off (comms lost),
    so a stale SCADA request never restarts it;
  • after manualMaxRun has run out.

Auto: the block only says Auto and which type. Your program runs the plant from
IsAuto and AutoType. A manual request does nothing in Auto.

Retained: only the mode (as UT_MODE_SELECT) and the auto type, each saved only
when it changes.

Status codes

statusCode is a UT_STATUS (an HMI reads its number); statusText is the same in words.

statusCode statusText When
UT_ST_OFF Off Mode Off
UT_ST_IDLE_MANUAL Idle: Manual, no run request Manual, no run request held
UT_ST_AUTO Auto Auto (the type chosen is in autoType)
UT_ST_MANUAL_LOCAL Manual: running (local) A manual run held by LocalRun (timeLeft with manualMaxRun)
UT_ST_MANUAL_REMOTE Manual: running (remote) A manual run held by RemoteRun
UT_ST_FORCED_OFF Blocked: forced off ForceOff
UT_ST_SELECT_MODE Waiting: select a mode UT_PU_OFF, selector found in Manual or Auto at power-up: move it
UT_ST_MUST_CYCLE Waiting: command must cycle A run request must be released and given again
UT_ST_MANUAL_MAX_RUN Manual: max run, release run manualMaxRun ran out
UT_ST_REMOTE_REFUSED Blocked: remote run refused RemoteRun under local control
UT_ST_COMMS_LOST Blocked: comms lost RemoteRun dropped: CommsOk FALSE
UT_ST_CONFIG + UT_F_MANUAL_MAX_RUN Config: manual max run manualMaxRun negative: no manual run until fixed

Using it

Plant(LocalRun := PanelRunPB, RemoteRun := SCADA_Run, RemoteEnabled := NOT LocalSw,
      CommsOk := NOT ScadaLink.CommsFail, Data := PlantMode);   (* autoTypes := 2 *)
IrrigationEnable := Plant.IsAuto AND Plant.AutoType = 1;
PumpDownEnable := Plant.IsAuto AND Plant.AutoType = 2;
Pump1Demand := Plant.ManualRun OR (Plant.IsAuto AND LevelHigh);