Conventions — how every block behaves

Conventions — how every block behaves

Read this once and every block will feel familiar.

Names

  • Every block, record type and enum value starts with UT_.
  • Pins are PascalCase plain English: Feedback, Overload, Interlock.
  • Record fields are camelCase: feedbackDelay, overload.reset.
    • cmdXxx: an HMI command. The block acts on it once and clears it (see
      HMI commands).
    • grpXxx: written by a group block (station, duty). Don't write these yourself.
  • Reserved words that can't be used as names: step, now, time, action, method, min, max, set.

Zero is off

The first value of every enum (0) is the off / none / safest choice, and every
mode starts at 0 = Off. A freshly loaded program does nothing until someone
chooses otherwise, and an enum left at its default never surprises anyone.

There are two exceptions, both about what happens after a power cut, where the
unattended plant carrying on is the safe default:

  • UT_POWERUP, whose first value UT_PU_LAST keeps a device's mode over a power
    cut (see Power-up): a freshly loaded program still starts Off, and an
    unattended pump left in Auto carries on after a power cut.
  • UT_RUN_POWERUP (UT_RUN_LIMIT, UT_ZONE_SEQ),
    whose first value UT_RPU_RESUME lets a run or zone program that was going at a
    power cut carry on with what it had left, as a commercial irrigation controller
    does (UT_RPU_RESTART and UT_RPU_NONE are the other choices). A freshly loaded
    program still starts nothing.

Pin order

  1. The first input is the main signal and should always be wired.
  2. The first output is the main result.
  3. The record (Data, or an array such as Pumps) comes last.

Ladder / FBD rule (important)

Library blocks run on EN. If the rung feeding EN is false, the block doesn't
run
and its outputs freeze. Give every library block its own unconditional
rung
and wire commands into named pins. See ladder-rules.md.

Defaults

  • Unwired permissives/interlocks default to TRUE (OK). Unwired fault inputs default to FALSE (healthy).
  • Optional sensors are not installed until you say so (installed := FALSE).
  • Every setting has a working default.

Inputs are TRUE = active

Inputs are TRUE = active; wire NC contacts through NOT at the pin. A fault
input is TRUE when tripped, a button TRUE when pressed, a switch TRUE when it
signals. The device blocks have no "NC" setting: a normally-closed contact (an overload
aux, a thermistor relay, a stop button, a flow switch) is inverted with NOT at
the pin or in the I/O mapping, e.g. Overload := NOT M1_OL_NC. A broken wire then
reads as tripped / pressed, the safe side.

Invalid settings

An invalid or out-of-range setting never runs anything that could damage
equipment.
A setting that is not a number, infinite, negative where it can't be,
or out of range either falls back to a safe value and raises a warning
(wrnConfig, Warning), or, where no fallback is safe, keeps the device off with
a fault until it is fixed. Each block's doc lists its checks.

Interlock vs permissive

Stops a running device Blocks a start Applies in Hand
Interlock yes yes yes
Permissive no yes yes

Neither is a fault. The device shows UT_STATE_INTERLOCKED.


Protections — every fault works the same way

Every protection in every block (overload, dry run, high pressure, travel
timeout…) is a UT_PROTECTION. Its response and how it resets are separate
choices, so latching is always optional:

UT_PROTECTION (settings + status in one)

Field Type Meaning
response UT_RESPONSE UT_RESP_OFF (0, ignored) · UT_RESP_WARN (alarm only, the device keeps running) · UT_RESP_TRIP (stop the device)
delay TIME The condition must last this long
reset UT_RESET_MODE UT_RST_AUTO (0) · UT_RST_RETRY · UT_RST_MANUAL, see below
recover TIME AUTO/RETRY: the cause must be gone this long before the device runs again (also the retry wait). A reset with the cause gone skips it
maxRetries INT RETRY: attempts allowed within the device's retryWindow, then it becomes MANUAL
active BOOL status: the condition is present now (after the delay)
tripped BOOL status: the protection is holding the device off, or warning
retries INT status: attempts used in the current window
count UDINT status: total events (not kept over a power cut)
timeLeft TIME status: the countdown in progress: the delay still to run while the condition is present, or the recover / retry wait still to go while an AUTO or RETRY trip holds and its cause has gone. T#0s when nothing counts

Reset modes

Mode Cause can be observed (overload, high pressure, limit switch…) One-off event (failed to start, travel timeout, max run…)
UT_RST_AUTO Clears by itself once the cause has gone for recover, or at once on a reset Clears after recover (or at once on a reset), and the device tries again (unlimited)
UT_RST_RETRY As AUTO, but only maxRetries times in retryWindow; after that MANUAL. A reset clears it at once and starts a fresh count. retryWindow T#0s = no window: the count is cleared only by a reset or a power cycle As AUTO, limited to maxRetries
UT_RST_MANUAL Stays until a reset and the cause has gone Stays until a reset

Example: a sump pump overload. Overload uses UT_RST_AUTO. The maintenance
person resets the overload relay in the panel, the cause goes, and the pump goes
straight back into service. Nobody needs to touch an HMI.

Ways to reset a MANUAL fault (any one of these)

  1. the block's Reset pin (a panel pushbutton);
  2. the HMI command cmdReset;
  3. switching the device to Off and back (resetByOff := TRUE, the default),
    so a selector switch is a reset.

Restart after a fault clears

  • After an AUTO/RETRY recovery, the device resumes if it's still asked to run.
    That's the point of choosing auto recovery. A motor in Hand is not "still
    asked": a trip drops its hand start (as the interlock does), so the operator
    presses start again.
  • After a MANUAL reset, a maintained run command must cycle (go FALSE and back to
    TRUE) before the device restarts, unless restartAfterReset := TRUE.

The status of a tripped device says how the trip will clear, by its prefix (see
Status): Fault: overload clears by itself, Retrying: no run feedback retries, Latched: overload needs a reset, Locked: no run feedback has used up its retries. The
wait still to run is in the record's timeLeft (and faultClearIn on the motors),
and in the protection's own timeLeft and retries.

Each block's record also has fault (any trip), warning (any warning),
faultCode : DWORD (one bit per protection), and faultId : UT_FAULT (the
highest-priority active one, by name). faultCode and faultId cover warnings
too
: a protection set to WARN sets its bit and faultId while it is raised, as a
TRIP does.

UT_LEVEL — a protection with a setpoint

Used for analog alarm levels (HH/H/L/LL), current limits and so on: every
UT_PROTECTION field plus

Field Type Meaning
sp REAL Setpoint
deadband REAL Must come back past sp ∓ deadband to clear (stops chatter)

UT_MEAS — a measurement that might be a switch, a transmitter, both, or nothing

Pumps and controllers watch measurements (pressure, flow, suction level) that
vary from site to site. Each one is a UT_MEAS:

Field Type Default Meaning
installed BOOL FALSE Is anything fitted at all?
sensor UT_SENSOR UT_SENSOR_SWITCH UT_SENSOR_SWITCH · UT_SENSOR_ANALOG (transducer/meter) · UT_SENSOR_BOTH. More types can be added later without breaking projects.
highSwitch UT_LEVEL_ID per block Which level the high switch triggers: UT_LVL_NONE (0, no high switch fitted), UT_LVL_HIHI, UT_LVL_HI
lowSwitch UT_LEVEL_ID per block Which level the low switch triggers: UT_LVL_NONE, UT_LVL_LO, UT_LVL_LOLO
hiHi, hi, lo, loLo UT_LEVEL per block Setpoints (analog) and response/reset for each level
onlyWhenRunning BOOL per block Only check while the equipment runs (e.g. discharge pressure)
maskAtStart BOOL per block Ignore the low levels during the start mask / prime
value REAL status: live analog value

So a site with just a high-pressure switch sets installed := TRUE,
sensor := UT_SENSOR_SWITCH, highSwitch := UT_LVL_HIHI, lowSwitch := UT_LVL_NONE.
A site with a transducer sets sensor := UT_SENSOR_ANALOG and the four setpoints.
H and L are warnings by default, so abnormal conditions can be dealt with
before they become trips.


Device modes — UT_MODE

Value Code Meaning
UT_MODE_OFF 0 Off / safe position. The default.
UT_MODE_HAND 1 Operator control (HMI buttons, local pushbuttons). Interlocks still apply.
UT_MODE_AUTO 2 Program control (AutoCmd pin or a group block)
UT_MODE_OOS 3 Out of service (maintenance): outputs off, faults and alarms suppressed
  • The mode starts at Off. Whatever the operator selects is retained inside the
    block
    . After a power cut it comes back as the device's powerUp says (see
    Power-up): by default in the mode it was left in.
  • An HMI changes the mode by writing cmdMode (an INT): 0 Off, 1 Hand, 2 Auto,
    3 OOS. The block applies it once and sets cmdMode back to -1 ("no request");
    see HMI commands.
    The actual mode is in mode.

Where the mode comes from — modeSource : UT_MODE_SOURCE

Value Meaning
UT_SRC_HMI (0) HMI cmdMode, retained
UT_SRC_SWITCH Physical selector pins SwHand / SwAuto (neither = Off)
UT_SRC_REMOTE Selector Off/Hand act locally; selector Auto hands control to the HMI mode (local/remote)

Power-up

What a device's mode does after a power cut is a per-device setting,
powerUp : UT_POWERUP in its record (a PLC stop / start counts as a power-up too):

Value After a power cut For example
UT_PU_LAST (default) The mode comes back as it was, from the first scan An unattended effluent pump stays in Auto and carries on
UT_PU_OFF The mode comes back Off; the operator selects it again. A selector found in Hand or Auto is held at Off until it is moved A quarry conveyor someone must restart on purpose
  • A motor in Hand always needs a fresh start after a power cut (EN 60204-1),
    whatever powerUp says: the motor blocks never keep a Hand start.
  • UT_HOA, whose Hand switches an output straight on, has handPowerUp : UT_HAND_POWERUP: UT_HPU_OFF (default) a Hand comes back Off; UT_HPU_KEEP
    Hand and its output come back.
  • ForceOff on UT_MODE_SELECT holds a mode at Off
    without losing the choice (a plant-wide off, an isolator's auxiliary contact).
  • Plant-level Off / Manual / Auto is UT_SYSTEM_MODE.

Device state — UT_STATE (one colour map for every device)

UT_STATE_OFF (0) · UT_STATE_STARTING · UT_STATE_ON · UT_STATE_STOPPING ·
UT_STATE_INTERLOCKED · UT_STATE_WARNING (running with a warning) · UT_STATE_FAULT ·
UT_STATE_INVALID · UT_STATE_OOS. For valves: OFF = closed, ON = open, STARTING/STOPPING = moving.

Status: every critical block says what it is doing and why

Any block that can stop equipment (motors, pumps, pump stations, duty and cascade
groups, speed control, valves, dosing, run limits, sequencers, interlocks, vessels)
has these status fields in its record, updated every scan:

Field Type What it is
statusCode UT_STATUS The one main thing happening, or holding it back, right now
faultId UT_FAULT Which fault, warning or setting the status is about. UT_F_NONE when none. Blocks that have no faults or settings to name leave it out
statusText STRING(30) The two in words (UT_STATUS_TEXT), for a person looking at the PLC online. Written only when the code or the fault changes

The text never holds a number. The numbers that go with a status are in their own
fields: timeLeft for the countdown, statusUnit on the group blocks for the pump
or unit (its array index) the status is about, and counts such as runningCount.

HMIs and SCADA read the codes. UT_STATUS, UT_FAULT and UT_STOP are
enumerations. An HMI, Modbus or SCADA sees an enumeration as a number: the
member's position in its list, counting from 0, as in the tables below. The
debugger shows the name. Keep the words, alarm texts, colours and history in the
HMI or SCADA, keyed on the numbers. Each device has its own fields in its own
record: read them directly (Pump1.statusCode, Pump1.faultId).

The block always shows the most important reason, in this order (top first).
UT_STATUS_KIND gives the kind of any status:

Order Kind (UT_KIND) What it means Example statusText
1 UT_KIND_CONFIG A setting keeps it off until it is fixed Config: valve type
2 UT_KIND_FAULT A trip holds it off, or it runs in a fallback Latched: overload · Fault: dry run
3 UT_KIND_HELD Held or waiting (not a fault): why it isn't running when asked Waiting: restart delay · Blocked: interlock · Not permitted · Hand: press start · Waiting: turn in group
4 UT_KIND_WARNING It runs, but something needs looking at: shown over "Running" Warning: current signal · Setting: full load current
5 UT_KIND_NORMAL Normal operation Running: Auto · Starting · Stopping · Running: group
6 UT_KIND_NORMAL Idle, nothing wanted Off · Idle

Rules:

  • The words start with their kind (Config:, Fault:, Retrying:, Latched:,
    Locked:, Warning:, Setting:, Waiting:, Blocked:, Not permitted,
    Hand:, Running, Starting, Stopping, Off, Idle; mode blocks show their
    mode: Auto, Manual: running (local)), then the detail.
  • A device that is asked to run but is not running always says why.
  • A status means the same in every block: UT_ST_RESTART_DELAY is a restart delay,
    UT_ST_INTERLOCK an interlock, wherever it appears. Each block's doc lists the
    statuses it uses.
  • Show the status on the HMI next to the device; for a whole-site text line feed the
    statuses into UT_MSG_QUEUE.

Fault prefixes

A warning, fault or configuration status is a prefix followed by the words of the
fault or setting in faultId. The prefix tells you how the problem behaves:

Status Prefix Meaning
UT_ST_FAULT Fault: A trip that resets by itself once the cause has gone (AUTO)
UT_ST_FAULT_RETRY Retrying: A trip that retries (RETRY), with retries still left
UT_ST_FAULT_RESET Latched: A trip that needs a reset (MANUAL)
UT_ST_FAULT_LOCKED Locked: A RETRY trip whose retries are used up: it needs a reset
UT_ST_WARNING Warning: It runs, but something needs looking at
UT_ST_WARN_SETTING Setting: A setting is not valid; a safe value is used instead
UT_ST_CONFIG Config: A setting is not valid and keeps the device off until it is fixed

For example Retrying: no run feedback, Latched: overload, Setting: full load current, Config: valve type. A setting with no words of its own reads a setting.

The numbers

The tables below give every member with its number, in list order from 0. These
numbers are fixed: a member added to the library later goes at the very end of its
list, so no number ever moves and an HMI's lists stay right after a library update.
The statuses up to UT_ST_CONFIG are grouped by kind; the ones after it (from
UT_ST_FIXED_SPEED) are not, so take a status's kind from the Kind column or from
UT_STATUS_KIND, never from its position.

UT_STATUS, UT_FAULT, UT_STOP and UT_KIND have the base type USINT (IEC 61131-3 Ed. 3,
UT_STATUS : USINT (UT_ST_IDLE, ...)): one byte each, and an HMI or SCADA reads them as
a USINT (0..255).

UT_STATUS: what the block is doing (statusCode)

No. Name Words (UT_STATUS_TEXT) Kind
0 UT_ST_IDLE Idle normal
1 UT_ST_OFF Off normal
2 UT_ST_OFF_NOT_AUTO Off: motor not in Auto normal
3 UT_ST_RUN_AUTO Running: Auto normal
4 UT_ST_RUN_HAND Running: Hand normal
5 UT_ST_STARTING Starting normal
6 UT_ST_STOPPING Stopping normal
7 UT_ST_RUN_GROUP Running: group normal
8 UT_ST_IDLE_GROUP Idle: in group normal
9 UT_ST_EXERCISING Exercising normal
10 UT_ST_PRIMING Priming normal
11 UT_ST_HIGH_FLOAT Running: high float normal
12 UT_ST_MIN_RUN Running: min run time normal
13 UT_ST_STOP_DELAY Running: stop delay normal
14 UT_ST_RUN_TIMED Running: timed normal
15 UT_ST_RUN_DEMAND Running: demand normal
16 UT_ST_RUN_TIME Running: by time normal
17 UT_ST_RUN_VOLUME Running: by volume normal
18 UT_ST_RUN_REMOTE Running: remote held normal
19 UT_ST_RUN_UNTIL_STOP Running: until stopped normal
20 UT_ST_RESUMED Running: resumed normal
21 UT_ST_RESTARTED Running: restarted normal
22 UT_ST_OPENING Opening normal
23 UT_ST_CLOSING Closing normal
24 UT_ST_OPEN Open normal
25 UT_ST_CLOSED Closed normal
26 UT_ST_MOVING Moving normal
27 UT_ST_HOMING Homing normal
28 UT_ST_AT_POSITION At position normal
29 UT_ST_BETWEEN Stopped between positions normal
30 UT_ST_POS_UNKNOWN Position unknown normal
31 UT_ST_STAR Starting: star normal
32 UT_ST_LOW_FIRST Starting: low speed first normal
33 UT_ST_SKIP_EDGE Running: at skip band edge normal
34 UT_ST_OK OK normal
35 UT_ST_BYPASSED Bypassed normal
36 UT_ST_RUNNING Running normal
37 UT_ST_STOPPED Stopped normal
38 UT_ST_STILL_TURNING Stopped: still turning normal
39 UT_ST_CHECKS_DELAY Starting: checks delayed normal
40 UT_ST_IDLE_NO_DEMAND Idle: no demand normal
41 UT_ST_IDLE_LEVEL_REACHED Idle: demand level reached normal
42 UT_ST_IDLE_HAND Idle: Hand, command off normal
43 UT_ST_AUTO Auto normal
44 UT_ST_MANUAL_LOCAL Manual: running (local) normal
45 UT_ST_MANUAL_REMOTE Manual: running (remote) normal
46 UT_ST_IDLE_MANUAL Idle: Manual, no run request normal
47 UT_ST_LOCAL Local control normal
48 UT_ST_LOCAL_REMOTE Local and remote normal
49 UT_ST_RUN_ALL Running: all steps normal
50 UT_ST_RUN_PART Running: part normal
51 UT_ST_OFF_ABORTED Off: aborted normal
52 UT_ST_RUN_STEP Running: step normal
53 UT_ST_CLEANING Cleaning normal
54 UT_ST_CLEAN_NEXT Cleaning: waiting next cycle normal
55 UT_ST_RUN_ZONE Running: zone normal
56 UT_ST_DOSE_FAST Dosing fast normal
57 UT_ST_DOSE_SLOW Dosing slow normal
58 UT_ST_SETTLING Settling normal
59 UT_ST_DOSE_FLOW Dosing: flow-paced normal
60 UT_ST_DOSE_TIMED Dosing: timed normal
61 UT_ST_DOSE_NEXT Timed: waiting next dose normal
62 UT_ST_DONE Idle: done normal
63 UT_ST_ABORTED Idle: aborted normal
64 UT_ST_IDLE_NOT_ENABLED Idle: not enabled normal
65 UT_ST_HOLDING Running: holding setpoint normal
66 UT_ST_PIPE_FILL Pipe fill normal
67 UT_ST_BOOST Boost before sleep normal
68 UT_ST_MAX_SPEED Max speed, below setpoint normal
69 UT_ST_FLOW_LIMIT Running: flow limit normal
70 UT_ST_FALLBACK Running: fallback speed normal
71 UT_ST_MANUAL_SPEED Running: manual speed normal
72 UT_ST_SLEEPING Sleeping normal
73 UT_ST_ADDING Adding a pump normal
74 UT_ST_DROPPING Dropping a pump normal
75 UT_ST_JOCKEY Jockey running normal
76 UT_ST_SWAPPING Swapping pumps (rotation) normal
77 UT_ST_LINK_OK Link OK normal
78 UT_ST_PRE_RUN Running: pre-run normal
79 UT_ST_POST_RUN Running: post-run normal
80 UT_ST_RUN_WITH_PUMP Running: with pump normal
81 UT_ST_RESTART_DELAY Waiting: restart delay held
82 UT_ST_INTERLOCK Blocked: interlock held
83 UT_ST_NOT_PERMITTED Not permitted held
84 UT_ST_HAND_PRESS_START Hand: press start held
85 UT_ST_START_BLOCKED Blocked: start block held
86 UT_ST_WAIT_GROUP Waiting: turn in group held
87 UT_ST_HAND_MAX_RUN Hand: max run, press start held
88 UT_ST_MUST_CYCLE Waiting: command must cycle held
89 UT_ST_OOS Out of service held
90 UT_ST_DEAD_TIME Waiting: dead time held
91 UT_ST_START_DELAY Waiting: start delay held
92 UT_ST_MIN_OFF Waiting: min off time held
93 UT_ST_INHIBITED Blocked: inhibit held
94 UT_ST_MOTOR_NOT_AUTO Blocked: motor not in Auto held
95 UT_ST_MOTOR_NOT_READY Blocked: motor not ready held
96 UT_ST_FULL Blocked: high float (full) held
97 UT_ST_TIMED_REST Waiting: timed rest held
98 UT_ST_STOPPED_LOW Stopped: low level held
99 UT_ST_STOPPED_FULL Stopped: full held
100 UT_ST_PAUSED Paused: not running held
101 UT_ST_ABORT Blocked: abort held
102 UT_ST_WAIT_POWERUP Waiting: start again held
103 UT_ST_NOT_HOMED Hand: not homed held
104 UT_ST_MOVE_TIMEOUT Waiting: new request held
105 UT_ST_WAIT_MAIN_FB Waiting: main contactor held
106 UT_ST_WAIT_OPEN Waiting: contactor to open held
107 UT_ST_REFUSED_LOCAL Refused: local control held
108 UT_ST_REFUSED_LOCAL_ONLY Refused: local only held
109 UT_ST_FORCED_OFF Blocked: forced off held
110 UT_ST_SELECT_MODE Waiting: select a mode held
111 UT_ST_SELECTOR_HAND Waiting: selector out of Hand held
112 UT_ST_MANUAL_MAX_RUN Manual: max run, release run held
113 UT_ST_REMOTE_REFUSED Blocked: remote run refused held
114 UT_ST_COMMS_LOST Blocked: comms lost held
115 UT_ST_RESET_NEEDED Waiting: reset held
116 UT_ST_AUTO_RESTART Waiting: auto restart held
117 UT_ST_HELD Held held
118 UT_ST_PAUSED_HOLD Paused: Hold input held
119 UT_ST_PAUSED_START Paused: press Start held
120 UT_ST_WAIT_CONDITION Waiting: step condition held
121 UT_ST_WAIT_DEMAND_DROP Waiting: demand to drop held
122 UT_ST_PAUSED_RAIN Paused: rain held
123 UT_ST_PAUSED_INPUT Paused: Pause input held
124 UT_ST_PUMP_FAULT_HOLD Blocked: pump fault held
125 UT_ST_WAIT_PUMP Waiting: pump not running held
126 UT_ST_SOAK Waiting: soak held
127 UT_ST_LOW_CARRIER Waiting: carrier flow low held
128 UT_ST_ENABLE_CYCLE Waiting: Enable must cycle held
129 UT_ST_DRIVE_NOT_RUNNING Waiting: drive not running held
130 UT_ST_STAGE_DELAY Waiting: stage delay held
131 UT_ST_PUMP_DELAY Waiting: pump own delay held
132 UT_ST_MAX_RUNNING Waiting: max running reached held
133 UT_ST_LOW_FLOAT Blocked: low float (dry) held
134 UT_ST_FAILOVER Waiting: start failed, next held
135 UT_ST_SHORTFALL Shortfall: too few available held
136 UT_ST_DRIVE_NOT_READY Blocked: drive not ready held
137 UT_ST_DEFER_MANUAL Deferred: manual held
138 UT_ST_DEFER_REMOTE Deferred: remote held
139 UT_ST_DEFER_RAIN Deferred: rain held
140 UT_ST_DEFER_SOIL Deferred: soil wet held
141 UT_ST_DEFER_SENSOR Deferred: sensor lost held
142 UT_ST_DEFER_CLEARING Deferred: clearing held
143 UT_ST_WARNING Warning: + the fault's words warning
144 UT_ST_WARN_SETTING Setting: + the fault's words warning
145 UT_ST_LINK_RESTART Link down: modem restart warning
146 UT_ST_LINK_POWER_CYCLE Link down: power cycle warning
147 UT_ST_LINK_REBOOT Link down: reboot warning
148 UT_ST_LINK_REBOOT_WAITS Link down: reboot not allowed warning
149 UT_ST_LINK_NO_STEPS Link down: no more steps warning
150 UT_ST_LINK_RETRY Link down: retry warning
151 UT_ST_LINK_REBOOTING Link down: rebooting warning
152 UT_ST_FAULT Fault: + the fault's words fault
153 UT_ST_FAULT_RETRY Retrying: + the fault's words fault
154 UT_ST_FAULT_RESET Latched: + the fault's words fault
155 UT_ST_FAULT_LOCKED Locked: + the fault's words fault
156 UT_ST_FLOAT_CONTROL Float control fault
157 UT_ST_FLOAT_LOCKOUT Float lockout fault
158 UT_ST_CONFIG Config: + the setting's words config
159 UT_ST_FIXED_SPEED Running: fixed speed normal
160 UT_ST_START_HOLD Waiting: start hold held
161 UT_ST_WAIT_PROVEN Waiting: valve proven held
162 UT_ST_FLOAT_RUN Running: on floats normal

UT_FAULT: which fault, warning or setting (faultId)

No. Name Words Kind
0 UT_F_NONE (none) none
1 UT_F_OVERLOAD overload fault / warning
2 UT_F_MOTOR_HOT motor too hot fault / warning
3 UT_F_NO_FEEDBACK no run feedback fault / warning
4 UT_F_FEEDBACK_LOST feedback lost fault / warning
5 UT_F_WELDED contactor welded fault / warning
6 UT_F_CURRENT_HIGH current high fault / warning
7 UT_F_CURRENT_LOW current low fault / warning
8 UT_F_DRIVE drive fault fault / warning
9 UT_F_CURRENT_BAD current signal fault / warning
10 UT_F_SPEED_DEV speed deviation fault / warning
11 UT_F_CHANGEOVER changeover fault / warning
12 UT_F_DRIVE_NOT_READY drive not ready fault / warning
13 UT_F_DRY_RUN dry run fault / warning
14 UT_F_PRESSURE_HH pressure HH fault / warning
15 UT_F_PRESSURE_LL pressure LL fault / warning
16 UT_F_NO_FLOW no flow fault / warning
17 UT_F_FLOW_HH flow HH fault / warning
18 UT_F_SUCTION_HH suction HH fault / warning
19 UT_F_PRIME failed to prime fault / warning
20 UT_F_EXTERNAL external fault fault / warning
21 UT_F_MAX_RUN ran too long fault / warning
22 UT_F_SEAL_LEAK seal leak fault / warning
23 UT_F_PRESSURE_H pressure high fault / warning
24 UT_F_PRESSURE_L pressure low fault / warning
25 UT_F_FLOW_H flow high fault / warning
26 UT_F_FLOW_L flow low fault / warning
27 UT_F_SUCTION_H suction high fault / warning
28 UT_F_SUCTION_L suction low fault / warning
29 UT_F_POINTS start/stop points fault / warning
30 UT_F_PV_BAD Pv not a number fault / warning
31 UT_F_SENSOR_BAD sensor bad fault / warning
32 UT_F_OPEN_TIMEOUT open timeout fault / warning
33 UT_F_CLOSE_TIMEOUT close timeout fault / warning
34 UT_F_BOTH_LIMITS both limits fault / warning
35 UT_F_POS_LOST position lost fault / warning
36 UT_F_NO_MOVEMENT did not move fault / warning
37 UT_F_ACTUATOR actuator fault fault / warning
38 UT_F_POS_DEVIATION pos. deviation fault / warning
39 UT_F_POS_FEEDBACK position signal fault / warning
40 UT_F_TRANSDUCER transducer fault / warning
41 UT_F_LEVEL_BAD level signal bad fault / warning
42 UT_F_NO_PUMP no pump ready fault / warning
43 UT_F_FLOAT_DISAGREE level vs high float fault / warning
44 UT_F_CLEAN_TIME cleaning too long fault / warning
45 UT_F_FLOW_BAD flow signal bad fault / warning
46 UT_F_FLOW_SHORT flow staging short fault / warning
47 UT_F_HIGH_FLOW high flow fault / warning
48 UT_F_OVERPRESSURE overpressure fault / warning
49 UT_F_LOW_AT_MAX low at max speed fault / warning
50 UT_F_PIPE_FILL pipe fill time fault / warning
51 UT_F_NOT_REACHING below setpoint fault / warning
52 UT_F_HUNTING loop hunting fault / warning
53 UT_F_START_FAILED failed to start fault / warning
54 UT_F_DOSE_NO_FLOW no dose flow fault / warning
55 UT_F_DOSE_TOO_LONG dose too long fault / warning
56 UT_F_PUMP_TOO_SMALL pump too small fault / warning
57 UT_F_TOLERANCE out of tolerance fault / warning
58 UT_F_FLOW_NAN Flow not a number fault / warning
59 UT_F_ACTUAL_NAN Actual not a number fault / warning
60 UT_F_STALLED stalled fault / warning
61 UT_F_UNDERSPEED underspeed fault / warning
62 UT_F_OVERSPEED overspeed fault / warning
63 UT_F_PULSES_STOPPED turning when off fault / warning
64 UT_F_PULSES_FAST pulses too fast fault / warning
65 UT_F_HIGH_HIGH high-high fault / warning
66 UT_F_HIGH high fault / warning
67 UT_F_LOW low fault / warning
68 UT_F_LOW_LOW low-low fault / warning
69 UT_F_VALUE_BAD value not a number fault / warning
70 UT_F_STEP_NO_STOP step not stopped fault / warning
71 UT_F_STEP_NO_FB step no feedback fault / warning
72 UT_F_STEP_FB_LOST step fb lost fault / warning
73 UT_F_STEP_TIMEOUT step timed out fault / warning
74 UT_F_NO_STEPS no steps to run fault / warning
75 UT_F_ZONE_FLOW zone flow fault / warning
76 UT_F_PUMP_FAULT pump fault fault / warning
77 UT_F_LEVEL_ABOVE_FULL level above full fault / warning
78 UT_F_CONDITION condition fault / warning
79 UT_F_IO_MISSING IO module missing fault / warning
80 UT_F_IO_BAD IO channel bad fault / warning
81 UT_F_IO_FORCED IO forced fault / warning
82 UT_F_NO_PRE_RUN no pre-run fault / warning
83 UT_F_BELOW_MIN below minimum fault / warning
84 UT_F_ABOVE_MAX above maximum fault / warning
85 UT_F_NOT_ABOVE not above related fault / warning
86 UT_F_NOT_BELOW not below related fault / warning
87 UT_F_LIMITS limits not valid fault / warning
88 UT_F_SETTING a setting setting
89 UT_F_FLC full load current setting
90 UT_F_CURRENT_NEEDS_FLC current needs FLC setting
91 UT_F_START_MASK start mask setting
92 UT_F_RESTART_DELAY restart delay setting
93 UT_F_HAND_MAX_RUN hand max run setting
94 UT_F_REVERSAL_DELAY reversal delay setting
95 UT_F_TRANSITION_TIME transition time setting
96 UT_F_STAR_CURRENT star current % setting
97 UT_F_STAR_NEEDS_FLC star % needs FLC setting
98 UT_F_STAR_TIME star time setting
99 UT_F_SPEED_CHANGE speed change delay setting
100 UT_F_LOW_START_TIME low start time setting
101 UT_F_MIN_MAX_SPEED min / max speed setting
102 UT_F_RAW_MIN_MAX raw min / max setting
103 UT_F_ACCEL_RATE accel / decel rate setting
104 UT_F_SKIP_BAND skip band setting
105 UT_F_HAND_SPEED hand speed setting
106 UT_F_RESET_PULSE reset pulse setting
107 UT_F_RATE_UNIT rate unit setting
108 UT_F_RATED_HZ_RPM rated Hz / rpm setting
109 UT_F_PUMP_MODE pump mode setting
110 UT_F_PRIME_DONEBY prime doneBy setting
111 UT_F_PRESSURE_SENSOR pressure sensor setting
112 UT_F_FLOW_SENSOR flow sensor setting
113 UT_F_SUCTION_SENSOR suction sensor setting
114 UT_F_RESPONSE response unknown setting
115 UT_F_PRIME_NEEDS_PRES prime: no pressure setting
116 UT_F_PRIME_NEEDS_FLOW prime: no flow setting
117 UT_F_RUN_TIME run time setting
118 UT_F_TARGET_VOLUME target volume setting
119 UT_F_SAVE_EVERY save every setting
120 UT_F_RETRY_WINDOW retry window setting
121 UT_F_MODE_SOURCE mode source setting
122 UT_F_VALVE_TYPE valve type setting
123 UT_F_TRAVEL_TIME open / close time setting
124 UT_F_PULSE_TIME pulse time setting
125 UT_F_SAFE_POSITION safe position setting
126 UT_F_THREE_POS_TYPE three-position type setting
127 UT_F_MID_TIME travel / mid time setting
128 UT_F_OUTPUT_MIN_MAX output min / max setting
129 UT_F_RAMP_RATE ramp rate setting
130 UT_F_SHUTOFF shutoff / full open setting
131 UT_F_FAIL_POSITION fail position setting
132 UT_F_OPEN_THRESHOLD open/closed limit setting
133 UT_F_DEADBAND deadband setting
134 UT_F_STROKE_TIME stroke time setting
135 UT_F_MIN_PULSE min pulse/overtravel setting
136 UT_F_STATION_MODE station mode setting
137 UT_F_STAGE1 stage 1 start / stop setting
138 UT_F_SETPOINT setpoint setting
139 UT_F_KP kp setting
140 UT_F_RATE_LIMIT rate limit setting
141 UT_F_START_SPEED start/fallback speed setting
142 UT_F_DOSE_MODE dose mode setting
143 UT_F_TIMED_ON_OFF timed on / off time setting
144 UT_F_NO_TARGET no target set setting
145 UT_F_NO_CAPACITY no capacity / ratio setting
146 UT_F_DIAMETER diameter setting
147 UT_F_TANK_HEIGHT tank height setting
148 UT_F_LENGTH_WIDTH length / width setting
149 UT_F_CONE cone / outlet setting
150 UT_F_FRACTION fraction setting
151 UT_F_DENSITY density setting
152 UT_F_DEAD_VOLUME dead volume setting
153 UT_F_LEVEL_OFFSET level offset setting
154 UT_F_LEVEL_RANGE level % range setting
155 UT_F_UNIT unit unknown setting
156 UT_F_DIST_PER_PULSE distance per pulse setting
157 UT_F_SPEED_UNIT speed unit setting
158 UT_F_MANUAL_MAX_RUN manual max run setting
159 UT_F_NO_OUTPUTS no outputs setting
160 UT_F_ALL_SKIPPED all channels skipped setting
161 UT_F_DEFAULT_SP default setpoint setting
162 UT_F_VALVE_PUMP_TIME valve / pump time setting
163 UT_F_SP_ORDER setpoint order setting
164 UT_F_LEVEL_SETTING a level setting
165 UT_F_NO_CONDITIONS no conditions setting
166 UT_F_BYPASS_TIMEOUT bypass timeout setting
167 UT_F_BAD_NEXT next outside recipe setting
168 UT_F_ENDLESS_LOOP endless loop setting
169 UT_F_STOP_STEP stop step setting
170 UT_F_CHAIN chain setting setting
171 UT_F_STEP_SETTING step setting setting
172 UT_F_GROUP_SETTING group setting setting
173 UT_F_NO_UNITS no units in array setting
174 UT_F_IO_ADDRESS IO address setting
175 UT_F_IO_NOT_FITTED IO not fitted setting
176 UT_F_IO_SHARED output used twice setting
177 UT_F_FORCE_TIME force time setting
178 UT_F_PRE_POST_RUN pre/post-run time setting
179 UT_F_DEFER_DELAY defer delay setting
180 UT_F_NOT_PROVEN valve not proven fault
181 UT_F_PUMPS_USED pumps used setting
182 UT_F_VALVE_DRIVE valve drive setting

UT_STOP: why the last run ended (stopReason)

No. Name Words (UT_STOP_TEXT)
0 UT_STOP_NONE (empty)
1 UT_STOP_DEMAND_ENDED Auto: demand ended
2 UT_STOP_OPERATOR Stopped: operator
3 UT_STOP_SWITCHED_OFF Stopped: switched off
4 UT_STOP_INTERLOCK Stopped: interlock
5 UT_STOP_FAULT Stopped: fault
6 UT_STOP_MAX_RUN Stopped: max run time
7 UT_STOP_DONE Done
8 UT_STOP_ABORTED Stopped: aborted
9 UT_STOP_INHIBITED Stopped: inhibited
10 UT_STOP_COMMS_LOST Stopped: comms lost
11 UT_STOP_GROUP Stopped: group
12 UT_STOP_LOW_LEVEL Stopped: low level
13 UT_STOP_FULL Stopped: full
14 UT_STOP_EXERCISE_DONE Done: exercise
15 UT_STOP_BY_MOTOR Stopped: by the motor
16 UT_STOP_REMOTE_OFF Stopped: remote off
17 UT_STOP_NOT_PERMITTED Stopped: not permitted
18 UT_STOP_PAUSED_LONG Stopped: paused too long
19 UT_STOP_SETTING Stopped: setting invalid
20 UT_STOP_POWER_CUT Stopped: power cut
21 UT_STOP_RAIN Stopped: rain
22 UT_STOP_PUMP_FAULT Stopped: pump fault
23 UT_STOP_STEP_TIMEOUT Stopped: step timeout
24 UT_STOP_REFUSED Stopped: recipe refused
25 UT_STOP_ABORT_CMD Stopped: aborted (HMI)
26 UT_STOP_ASLEEP Asleep: demand met
27 UT_STOP_LEVEL_BAD Stopped: level signal bad
28 UT_STOP_CLEAN_TIMEOUT Stopped: cleaning too long

Time visibility

Every block that times something shows the time, so an HMI or SCADA can show a
countdown without parsing text:

Field Type What it is
timeLeft TIME The countdown its status is showing (delay, wait, run time left …). T#0s when nothing counts
phaseTime TIME Where useful: time spent in the current phase or step so far

They are in the block's record, or are outputs on blocks without one. Every
protection has its own timeLeft (UT_PROTECTION).
The status text holds no numbers: show timeLeft beside it.
UT_TIME_TEXT turns it into short text (1 h 20 m) for a
simple display.

Why it stopped

The motor, valve, pump, pump station, pump cascade, speed-control and dose records
keep why the last run ended and the last trip, so "what happened overnight" can be
read after the fact:

Field Type What it is
stopReason UT_STOP Why the last run ended. Set when a run ends, kept until the next run ends. UT_STOP_NONE (0) = none since power-up
lastFaultCode DWORD The faultCode bits of the last trip, kept after it clears, until the next trip
lastFault UT_FAULT The last trip by name, kept the same way
trips UDINT Trips since power-up (not kept over a power cut)

UT_RUN_LIMIT and UT_ZONE_SEQ keep endReason, and UT_STEP_SEQ lastResult, of the
same type. The numbers are in the UT_STOP table
above; UT_STOP_TEXT gives the words. The common ones:

Name Words Meaning
UT_STOP_NONE (empty) No run has ended since power-up
UT_STOP_DEMAND_ENDED Auto: demand ended The Auto command or demand dropped: a normal stop
UT_STOP_OPERATOR Stopped: operator A stop in Hand: cmdStop, a stop button, HandCmd dropped
UT_STOP_SWITCHED_OFF Stopped: switched off The mode changed to Off or OOS
UT_STOP_INTERLOCK Stopped: interlock The interlock dropped
UT_STOP_FAULT Stopped: fault A protection tripped (lastFault says which)
UT_STOP_MAX_RUN Stopped: max run time A run-time limit ran out
UT_STOP_DONE Done A timed or metered run finished
UT_STOP_ABORTED Stopped: aborted Abort, cmdAbort
UT_STOP_INHIBITED Stopped: inhibited An inhibit or a plant-level off (ForceOff, system Off)
UT_STOP_COMMS_LOST Stopped: comms lost A remote run request was dropped on lost comms
UT_STOP_GROUP Stopped: group A group block (duty, station, cascade) stopped it

The other members are used by the blocks named in their docs.

Signal quality — UT_QUALITY

UT_Q_BAD (0) · UT_Q_UNCERTAIN · UT_Q_GOOD · UT_Q_SIM. A block that isn't
running reports BAD, never a stale GOOD. This matches the BeeBus topic quality.

Other shared enums

Enum Values (first = 0)
UT_PRIORITY UT_PRIO_LOW, UT_PRIO_MEDIUM, UT_PRIO_HIGH, UT_PRIO_CRITICAL
UT_RATE_UNIT UT_PER_SEC, UT_PER_MIN, UT_PER_HOUR, UT_PER_DAY
UT_VOL_UNIT UT_VOL_NONE (no conversion: the block's own unit), UT_VOL_L, UT_VOL_M3, UT_VOL_ML (megalitre)
UT_ROTATE_MODE UT_ROT_FIXED, UT_ROT_EACH_START, UT_ROT_HOURS, UT_ROT_INTERVAL
UT_POWERUP UT_PU_LAST (default: the mode comes back), UT_PU_OFF
UT_HAND_POWERUP UT_HPU_OFF (default: a Hand comes back Off), UT_HPU_KEEP
UT_RUN_POWERUP UT_RPU_RESUME (default: a run carries on), UT_RPU_RESTART, UT_RPU_NONE (declared with UT_RUN_LIMIT)
UT_CMD_FROM UT_FROM_NONE, UT_FROM_LOCAL, UT_FROM_REMOTE
UT_UNIT UT_UNIT_NONE, then pressure, flow, volume, temperature and length units (see UT_UNIT_CONV)

Simulation

Device and signal blocks have simulate : BOOL. Feedbacks follow commands after a
realistic delay, signal blocks use simValue, and quality shows UT_Q_SIM. Use it
for commissioning and FAT. In the motor blocks simulation fakes only the run
feedback
: the feedback checks (noFeedback, feedbackLost, stuck) see the
simulated one, and every other protection (overload, thermistor, drive fault,
driveNotReady, the current levels) still acts.

Retained data

Retain is kept to a minimum. Over a power cut the library keeps only, inside
the block:

  1. The device's HMI mode (UT_MODE_SELECT: every motor and valve block, and
    UT_HOA; a pump's mode is its motor block's), and the plant mode and auto type
    of UT_SYSTEM_MODE. Whether the mode is used after a power cut is the device's
    powerUp setting.
  2. Run hours, starts and valve strokes: UT_RUN_HOURS (total, service, today,
    yesterday), UT_STARTS (lifetime, today, yesterday) and the valves' stroke count.
  3. Flow / volume totals and dose totals: UT_TOTALISER (every total, with what
    it needs to stay correct and never count twice) and UT_DOSE (doses,
    dosedTotal).
  4. The progress of a run or zone program in progress, for its powerUp
    (UT_RPU_RESUME carries it on): UT_RUN_LIMIT (whether
    a run is active, how it started, whether RunHeld is on, its running time and
    volume) and UT_ZONE_SEQ (whether a program is running, how
    it started, the zone watering with its water time, volume and cycles, the pass,
    the HMI pause). Also UT_RUN_LIMIT's last-run summary, saved once per run end.

Nothing else is kept. Protection trips are not kept: a latched or MANUAL trip
is forgotten at power-up, and if the fault is still there it trips again. Inhibits,
retries, a dose in progress, a learned preact, alarm
states, leads, statistics, diagnostic counters and toggles all start fresh. (UT_TONR, like Siemens TONR and
Rockwell RTO, keeps its time only while the PLC is powered.) This needs only
Persistent Storage switched on in the project. To keep your settings across
power loss, declare your record variable RETAIN.

How often values reach storage. The controller saves all retained values
together, and only when something changed: a change after a quiet spell at once,
then at most once per period (default 10 s runtime, 1 min ESP32, 10 min other
boards). So what a block retains decides how hard it works the flash or EEPROM:

What Saved Why
The HMI mode, and presets, resets, service resets and rollovers of the counts below At once Rare, and must never come back after a power cut
Values that count up: starts, run hours, strokes, totals Every saveEvery (default T#12h) They change all the time; a PLC runs 24/7, so a power cut costs at most 12 h of counting
A run's or zone program's progress At its start and end, on a zone, pass or cycle change, and otherwise at most every progressSave (default T#1m) while it runs; nothing while idle A resume repeats at most progressSave of running; a day of irrigation is a few hundred saves

Blocks that count keep the live value in normal memory and copy it to their
retained snapshot every saveEvery. saveEvery = T#0s means the count is not
kept over a power cycle at all. At one save per 12 h even an STM32's 10,000-erase flash lasts about
13 years.

Totals and hours are accumulated as 64-bit integers with a fractional remainder,
not as REAL, so they stay exact on every target. On an AVR board LREAL is only 32-bit.

Timing

All timing uses real elapsed time (TIME(), 64-bit, constant within a scan), so
behaviour is identical at any task interval. Pulse inputs are limited by the scan rate (each doc states the limit).

No blocking code

No WHILE or REPEAT: every loop has a fixed bound. A loop is a FOR over an
array's bounds or over a small fixed count (leaving early with EXIT), or the
work is done with arithmetic. A scan can never hang, and its longest time is known.

HMI commands

  • A BOOL cmdXxx acts once, on its rising edge. The block keeps the value it
    read the scan before, acts when it goes from FALSE to TRUE, and clears it to
    FALSE. A command that is held or forced TRUE (a Modbus coil left on, a debugger
    force) acts once, not every scan, and acts again only after it has been FALSE.
  • An INT request (cmdMode, …) acts when a valid value arrives (a value that
    differs from the one read the scan before) and is set back to -1. An invalid
    value is ignored and also set back to -1.
  • Stop / Off always wins over a start in the same scan.
  • A master that rewrites a value every poll (a SCADA writing its whole register
    block each cycle), or two masters (a panel HMI and SCADA) commanding the same
    device, must not write the record's cmdXxx directly: put
    UT_CMD in front. Each master then writes its own variables,
    which nobody clears; UT_CMD reacts only to changes, applies local / remote
    (RemoteEnabled), lets stop win and passes one-scan requests into the record.
  • Settings written by an HMI or SCADA can be checked before use with
    UT_SETTING_CHECK.

Names

IEC names are case-insensitive: Count and count in one block clash.
tools/check-names.py checks this, the reserved words and the names of every
installed library block.

Groups

A group block takes an array of member records, and each member block uses one
element. See UT_PUMP_STATION and UT_DUTY.