Sparkplug: reporting to a SCADA system

Sparkplug: reporting to a SCADA system

Sparkplug B is MQTT with rules, and it is what SCADA systems and IoT platforms
(Ignition, a historian, a cloud SCADA) expect a remote site to speak. This page
is the Sparkplug blocks on a site: what to wire, what each pin does, and what to
check when it does not report.

Block What it is
MQTT_CLIENT the connection - broker, TLS, login, Wi-Fi, Ethernet or cellular
SPARKPLUG_NODE the Sparkplug node, a layer on that connection. One per client
SPARKPLUG_STRUCT a whole STRUCT as metrics - one per group of values
SPARKPLUG_METRIC one value that is not in a struct
SPARKPLUG_COMMAND a write from SCADA that the program decides about
SPARKPLUG_DEVICE a device under the node that can go offline by itself
MQTT_CLOCK the controller's clock, so the timestamps are real

The pins that matter

SPARKPLUG_NODE

Pin Set it to
GROUP the site or customer, e.g. 'Plant1'
NODE this controller, e.g. 'pumps1'. GROUP + NODE must be unique
CLIENT the MQTT_CLIENT it rides on
PRIMARY_HOST the SCADA system's host ID. The node then sends nothing while SCADA is offline, and sends everything again when it comes back
BORN TRUE when SCADA has the full metric list and data is flowing
CLOCK_SET TRUE when the timestamps are real time
LAST_ERROR what it is waiting for, in words

Everything about the connection is MQTT_CLIENT's - TRANSPORT, HOST,
SECURITY, the login on MQTT_CONFIG, the Wi-Fi on MQTT_ARDUINO or
NETWORK:

TRANSPORT Where Who brings the network up
MQTT_RUNTIME_TCP the OpenPLC Runtime. The default the computer
MQTT_ARDUINO_WIFI a board's Wi-Fi NETWORK (node-uio), or MQTT_ARDUINO
MQTT_ARDUINO_ETHERNET a board's Ethernet MQTT_CLIENT with MQTT_ARDUINO
MQTT_CELLULAR the modem on the GSM HAT GSM_MODEM (modbee-gsm)
MQTT_LINK_EXTERNAL a transport wired to EXTERNAL_LINK whoever made it

Moving a site from Wi-Fi to cellular is one pin on MQTT_CLIENT and one on
the clock. SECURITY does not change with it: on the Node every TLS setting
works on Wi-Fi, Ethernet and cellular alike, because the TLS runs on the
controller rather than in the modem (page 03, "TLS on a board").

For a secure link to the site's own broker use SECURITY := MQTT_TLS_PINNED
with TRUST_NEW := TRUE on MQTT_CLIENT, and a login on MQTT_CONFIG.
Nothing to install or define: the client learns the broker's key on its first
connection, keeps it over power cuts (turn on persistent storage), and refuses
any other key after that. MQTT_TLS_VERIFY is for a broker somebody signed
for, such as a cloud platform, and needs that CA in the board package.

One connection for everything

Sparkplug runs over MQTT, and so does everything else a site says. The node is
a layer on the client's session, not a second connection: one radio, one
login, one session for Sparkplug, your own MQTT topics and firmware updates
(OTA_NODE, modbee-ota) alike.

What Sparkplug needs of that session the node takes on every CONNECT:

  • the Will is its NDEATH. A connection carries one Will, so there is no
    MQTT_PRESENCE on a client with a Sparkplug node (it says MQTT_REFUSED):
    the birth and death certificates are the presence. And one node per client -
    a second node needs a second MQTT_CLIENT.
  • the session is always clean, whatever MQTT_CONFIG says.
  • the transmit buffer holds the birth certificate.

A node started on a session that is already up reconnects it once, so the next
CONNECT carries the NDEATH - every other block on the client sees one reconnect.
The same happens when the primary host goes offline, which Sparkplug requires.
A deliberate goodbye from MQTT_CLIENT - CONNECT := FALSE, or a new broker
address - publishes the NDEATH too. ENABLE := FALSE on the node sends the
NDEATH and leaves the connection to everything else on it.

One task. The client, the node and every SPARKPLUG_* block run in the
network task (page 10). In any other task a block says MQTT_WRONG_TASK and
does nothing.

A ModBee Node, Wi-Fi now

wifi ( ENABLE := TRUE, SSID := CFG.wifiSsid, PASSWORD := CFG.wifiKey );
clock( TRANSPORT := MQTT_LINK#MQTT_ARDUINO_WIFI );
mqtt ( TRANSPORT := MQTT_LINK#MQTT_ARDUINO_WIFI, HOST := CFG.scadaBroker,
       CLIENT_ID := 'plant1-pumps' );
sp   ( CLIENT := mqtt, GROUP := 'Plant1', NODE := 'pumps1',
       PRIMARY_HOST := 'scada' );
core ( NODE := sp, DATA := STS, DEADBAND := 0.01 );
sets ( NODE := sp, DATA := CMD, WRITABLE := TRUE );

The same Node, cellular later

modem( CONNECT := TRUE, APN := CFG.gsmApn );
clock( TRANSPORT := MQTT_LINK#MQTT_CELLULAR );
mqtt ( TRANSPORT := MQTT_LINK#MQTT_CELLULAR, HOST := CFG.scadaBroker,
       CLIENT_ID := 'plant1-pumps' );

Nothing else changes - sp and every struct block stay as they were. The
modbee-gsm library being in the project is what switches cellular on; there is
no build setting.

Firmware updates, from SCADA

OTA_SPARKPLUG (modbee-ota) puts an OTA_NODE's updates on this node as
metrics - Firmware/Version, Firmware/State, Firmware/Progress,
Firmware/Offered, Firmware/Status - and takes Node Control/Firmware Accept,
Apply, Confirm and the rest as commands, so an update can be run from the
SCADA screens. The image itself travels on the OTA node's own topics, over the
same connection.

ota  ( CLIENT := mqtt, BASE := 'plant1/pumps1/ota', VERSION := '1.4.0',
       AUTO_APPLY := FALSE );
otasp( NODE := ota, SPARKPLUG := sp );

Put every MQTT and Sparkplug block in the network task, not the logic task
(page 10). On an ESP32 opening the socket and the TLS handshake run on a task
of their own and hold neither; on a board without threads opening the socket
holds the block's task, over cellular for a second or two.

How many metrics

Controller Metrics per node (node and devices together) Devices
a board (ModBee Node UIO, any ESP32) as many as memory holds as many as memory holds
OpenPLC Runtime as many as memory holds as many as memory holds

Nothing is reserved up front. The node's tables grow with what the blocks
declare, and its buffers are sized to its own birth certificate when it first
connects - in PSRAM on a board that has it, so a hundred metrics cost the
internal RAM nothing. On a board a metric takes 320 bytes there (32 of them
what each scan reads: one cache line), a STRING 280 more, and a writable one
80 for the writes waiting on it (624 for a STRING). A SPARKPLUG_STRUCT keeps
12 bytes per declared member
in internal RAM - what each scan walks - and nothing for a member SKIP leaves
out or the node refuses. A metric memory cannot hold is refused: the declaring
block's ERROR (or SKIPPED on a STRUCT) says so, and SPARKPLUG_NODE's
LAST_ERROR reads "out of memory for metrics or devices".

A SPARKPLUG_HOST likewise tracks as many nodes, and metrics per node, as
memory holds, on a board and the Runtime alike, and its LAST_ERROR says when
memory ran out.

A SPARKPLUG_STRUCT takes every value in its STRUCT - nested STRUCTs and
arrays included.

One struct block, not a block per value

Every value in a SPARKPLUG_STRUCT is its own metric, named by its path -
the same names BeeBus uses:

In the STRUCT Metric name
levelMm : REAL levelMm
pump : S_PUMP with hours : REAL pump.hours
spare : ARRAY[1..3] OF REAL spare[1], spare[2], spare[3] (from 1, whatever the bounds)

PREFIX goes in front of every name: PREFIX := 'Cmd/' turns systemMode
into the metric Cmd/systemMode. Use it to keep two structs' names apart, or to
put a group in its own folder at the SCADA end.

Per-member settings. A member that needs its own units, deadband or display
range gets an entry in SETTINGS, an ARRAY OF SPARKPLUG_MEMBER:

SPARKPLUG_MEMBER
NAME the member's path, without PREFIX. Case does not matter. An array or nested STRUCT by name (spare, pump) covers every value in it
UNITS engineering units, sent in the birth (engUnit)
DEADBAND its own deadband, in its units. 0 = every change
DEADBAND_PCT its own deadband as a % of the value last sent
LOW, HIGH the range a SCADA gauge or trend should show (engLow, engHigh). Equal = none
PULSE for a command: the PLC puts the member back to 0 this long after a write. T#0s = keep it
SKIP TRUE leaves the member out - not a metric at all (an internal counter, the spares). FALSE puts back one an earlier entry left out, with this entry's numbers. Read once, when the metrics are declared
VAR
  sp      : SPARKPLUG_NODE;
  core    : SPARKPLUG_STRUCT;
  coreSet : ARRAY[1..3] OF SPARKPLUG_MEMBER := [
              (NAME := 'levelMm', UNITS := 'mm', DEADBAND := 10.0,
               LOW := 0.0, HIGH := 3000.0),
              (NAME := 'pressureBar', UNITS := 'bar', DEADBAND := 0.02),
              (NAME := 'pumpHours', UNITS := 'h', DEADBAND := 0.1)];
END_VAR

coreSet[1].DEADBAND := CFG.levelDeadband;   // a setting may follow CFG
core(NODE := sp, DATA := CORE, SETTINGS := coreSet);
  • A member with an entry takes its deadband; one without takes the block's
    DEADBAND/DEADBAND_PCT (REAL and LREAL members only).
  • Entries apply in order: one for spare and then one for spare[2] gives
    spare[2] the second's settings and the rest of the array the first's.
    SKIP too: [(NAME := 'sts', SKIP := TRUE), (NAME := 'sts.value', SKIP := FALSE, DEADBAND := 10.0)] leaves out all of sts but sts.value,
    which takes the second entry's deadband.
  • The settings are read again whenever they change, so they may be written from
    CFG on every scan. Units and ranges go out in the birth, so a change to them
    shows at the next birth.
  • BAD_SETTING names the first entry that could not be used, counting from 1 -
    a NAME that is no member, a negative number, a deadband on a BOOL or STRING -
    and ERROR stays on until it is fixed. The other entries still apply.
  • A TIME member says ms by itself.

Report by exception, and deadbands

Sparkplug sends a value only when it changes. A level transmitter that jitters
by a few millimetres would still send every scan - over a metered cellular link
that is most of the bill. A deadband says how much a value must move before it
is worth a message:

Block Pins Applies to
SPARKPLUG_STRUCT DEADBAND (in the members' units), DEADBAND_PCT (% of the value) REAL and LREAL members only
SPARKPLUG_METRIC DEADBAND (in VALUE's units) a numeric VALUE
  • The move is measured from the value last sent, not the last scan, so a
    slow drift still adds up and is reported.
  • The block's DEADBAND covers REAL and LREAL members only. BOOLs and STRINGs
    always report every change - a deadband would freeze a bit, a FAULT
    included. An integer, or an analog that needs its own number, gets a
    SETTINGS entry.
  • A value SCADA wrote is always reported back, whatever the deadband - SCADA
    watches for that echo to know the write took.
  • With both DEADBAND and DEADBAND_PCT set, a move must clear both.
  • A birth, and a STRUCT's PERIOD heartbeat, always carry every value as it
    is.

When a STRUCT sends

MODE Sends Its members otherwise
MQTT_ON_CHANGE what moved, past its deadband; all of them every PERIOD (if set) go with any report
MQTT_ON_INTERVAL all of them, every PERIOD held: never with other blocks' reports
MQTT_ON_REQUEST all of them on REQ's rising edge held
MQTT_CHANGED_EVERY what moved past its deadband since it was last sent, together, every PERIOD on the node's clock (every set with the same PERIOD in one message); nothing when none moved held
  • "All of them" is the block's own members, never the rest of the node.
  • One message a scan, for every block. A STRUCT (or a SPARKPLUG_METRIC)
    does not send: it marks what is to go and asks, and SPARKPLUG_NODE sends
    ONE NDATA - and one DDATA for each online device with something to say - on
    its next scan, carrying everything on the node that moved. The values are
    the ones the blocks set; the message's timestamp is when the node sends it.
    A STRUCT's SENT counts the message on the scan after it asked, and its
    ERROR/MQTT_QUEUE_FULL then says one could not be queued (it asks again).
  • The birth carries every member: a device coming online sends the whole
    set in its DBIRTH, and PERIOD counts from that birth. ENABLE going TRUE
    sends an MQTT_ON_INTERVAL set at once, and an MQTT_CHANGED_EVERY set's
    changes at once. Nothing is sent for a device that is offline.
  • A held set switched off (ENABLE FALSE) still keeps its values current
    in the node, so a birth carries them as they are; nothing is sent for it.
  • MQTT_CHANGED_EVERY is for a metered link. A logged value checked every
    15 minutes goes only when it has moved past its deadband; one that sits still
    costs nothing. The same mode with a short PERIOD (10 s) and ENABLE wired
    to "someone is viewing" streams a screen's values without sending the ones
    that did not move. Alarms that must reach SCADA at once stay MQTT_ON_CHANGE.

Writes from SCADA

  • WRITABLE := TRUE on a STRUCT lets SCADA write its members. The value lands
    in the STRUCT, and the next message reports it back - that is how SCADA sees
    the write took.

  • Under a DEVICE the writes are DCMDs instead of NCMDs, and they land the
    same way.

  • No write is lost. Every write to a metric waits its turn: the block
    takes one a scan, oldest first, so SCADA writing 1 and then 0 in one go
    leaves the member 1 for a scan and then 0, and the program sees both. Up to
    four writes wait per metric. A fifth that arrives before the program has
    taken any drops the oldest - the newest is always kept - and is counted on
    the block's LOST output. LOST above 0 means SCADA is writing that metric
    faster than the program scans.

  • Commands are a writable struct too, each member its own metric, written
    one at a time:

    cmds(NODE := sp, DATA := CMD.remote, PREFIX := 'Cmd/', WRITABLE := TRUE,
         SETTINGS := cmdSet);
    
    • A held signal (a run request) and a mode stay as written. With
      UT_CMD a mode acts when it changes; to ask for the same mode again, write
      -1 first.
    • A momentary command - a bit that acts on its rising edge, as UT_CMD's
      command bits do - must go back to 0 before the next one. Either SCADA
      writes the bit and then 0 (both are seen, however close together), or the
      member gets PULSE in SETTINGS (T#500ms, longer than the slowest task
      that reads it): SCADA writes the bits once, the PLC clears them, and
      writing the same command again acts again.
  • For a write the program must decide about by itself, declare it with
    SPARKPLUG_METRIC (WRITABLE := TRUE) and watch it with
    SPARKPLUG_COMMAND, called before the metric block. Set
    SPARKPLUG_COMMAND.DEVICE when the metric is under a device.

  • A write to a metric that is not writable, does not exist, or is the wrong
    type is refused and counted (REFUSED), never applied.

  • WRITABLE may go FALSE while running - remote control switched off. A write
    that arrives then is dropped at once (counted on a STRUCT's REFUSED) and
    the member is reported back unchanged, so SCADA sees the write did not take.
    It is never kept: WRITABLE coming back on does not apply an old command.

Types on the wire

Each metric's Sparkplug datatype is its IEC type: BOOL is Boolean, INT is
Int16, DINT is Int32, REAL is Float, STRING is String, and so on.

A TIME goes as an Int64 of milliseconds, both ways. Sparkplug has no
duration type. T#10s is reported as 10000, and SCADA writing 90000 sets
T#90s. A negative write is refused. A STRUCT member that is a TIME says
ms in the birth by itself.

An array or a nested STRUCT inside a SPARKPLUG_STRUCT is not one value: each
of its values is a metric of its own (see "One struct block"). An enumeration
goes as the unsigned integer it is stored as (UInt8 / UInt16 / UInt32 by its
size), both ways: the value's code, so modes and a protection's response are
visible and writable from the host. DATE and TIME_OF_DAY have no Sparkplug
type: a STRUCT member of one of those is refused and counted (SKIPPED), never
left out quietly.

Time

MQTT_CLOCK sets the controller's clock from the network: NTP over Wi-Fi or
Ethernet, the mobile network's own time over cellular, or a time wired to
UTC_IN (an RTC, GSM_TIME). Once it is set, Sparkplug's timestamps and
CURRENT_DT are real time, and SYNCED and the node's CLOCK_SET are TRUE.

Until then a board counts from when it started, so its timestamps are dates in
January 1970 - plainly not real. Set the SCADA historian to stamp a value with
the time it arrived when its timestamp is that old. The data is still good;
only the time is missing.

On the Runtime the computer keeps the time, and MQTT_CLOCK only reports it.

Changing settings while it runs

BROKER, PORT, SECURITY, TRANSPORT, USER, PASSWORD, GROUP, NODE,
PRIMARY_HOST, PROTOCOL and KEEP_ALIVE are read every scan. A change from
an HMI settings page needs no restart: the node leaves on the old settings (the
host sees its NDEATH), and births again on the new ones with the next bdSeq.
Every metric declaration, alias and device stays, so nothing else in the
program notices. The medium is rebuilt only when what it is made from changed.

A pinned key stays pinned: a different broker is refused until TRUST_NEW is
switched off and on, as for a replaced one.

Outages: SPARKPLUG_HISTORY

Sparkplug has no store-and-forward of its own. While the node is not born - no
coverage, the broker away, the host offline - nothing is sent, and after the
next birth the host sees only the values as they are then. What happened in
between, and when, is gone.

SPARKPLUG_HISTORY keeps events while the node cannot publish and sends
them after it births again, with Sparkplug's is_historical flag: the host
files each at its own time and does not overwrite the live tag with it.

Pin
NODE in-out the node
ADD in, BOOL TRUE records one event on this call - wire a one-scan pulse
SOURCE in, UINT what it is about: a pump, an alarm number, a zone
CODE in, UINT what happened: a status, fault or stop code
VALUE in, REAL a number that goes with it
NAME in, STRING(24) the metrics' prefix, 'Event'
DEPTH in, UINT events kept while away, 256. Fixed at the first call
BATCH in, UINT events per message when catching up, 20
PERIOD in, TIME between catch-up messages, T#1s
STORED out, UINT events waiting
LOST out, UDINT dropped because the buffer was full (the oldest go)
SENT out, UDINT sent since the program started
REPLAYING out, BOOL catching up
ERROR, STATUS out no memory, or the metrics could not be declared
history(NODE := sp, ADD := pumpStopped, SOURCE := 1, CODE := pump1.StopCode, VALUE := level);
history(NODE := sp, ADD := alarmRaised, SOURCE := 100 + alarmNo, CODE := 1, VALUE := 0.0);

Each event is one row of four metrics with the same timestamp:
Event/source, Event/code, Event/value and Event/seq (a count from 1
since the program started, so the host sees any gap), plus Event/lost. While
the node is born an event goes at once as live data; recorded while it is not,
it waits and goes historical, oldest first, BATCH at a time every PERIOD.

  • Events, not analogs. A level that moves every scan would fill any
    buffer. Keep the reasons, stops, alarms and day totals; counters that only go
    up reconcile the rest by themselves.
  • 256 events is about a week of a normal site, 6 KB of PSRAM (24 bytes an
    event), allocated on the first scan. Nothing of the internal heap but the
    block's own few bytes.
  • Not retained. A power cut during an outage loses the waiting events; the
    counters and the day totals still reconcile.
  • Sent at least once. Data messages are QoS 0 by the specification, so an
    event is forgotten only after the node has stayed born for half a second on
    the same birth; a link that drops in that moment sends the batch again. The
    host may see an event twice (same timestamp, same seq), never not at all.
  • The clock. An event recorded before MQTT_CLOCK has set the clock is
    kept against the board's uptime and placed on the clock once it is set.
    Events wait for the clock up to five minutes after a birth, then go with
    what they have.

Daily totals: SPARKPLUG_DAY_TOTALS

Pin
NODE in-out the node
TABLE in-out, ARRAY OF SPARKPLUG_DAY DAY : DATE, TOTAL : REAL. Retain it. Row 0 is today; the rest are closed days, newest first
NAME in, STRING(32) the metric, 'pumpedDay'
VALUE in, REAL today's running total, from your totaliser
CLOCK in, DT local date and time - the clock your totaliser rolls its day on
DAYS out, INT closed days held
SENT out, UDINT day values sent
ERROR, STATUS out the metric could not be declared, or TABLE has fewer than two rows
VAR_GLOBAL RETAIN  PUMPED_DAYS : ARRAY[0..31] OF SPARKPLUG_DAY;  END_VAR
days(NODE := sp, TABLE := PUMPED_DAYS, NAME := 'pumpedDay', VALUE := pumped.today, CLOCK := localNow);

When the date on CLOCK changes the day just ended is closed - its total is
the value VALUE had on the scan before - and moves into the table as the
newest closed day; the oldest falls off. A day that ends during a power cut is
closed when the PLC comes back, from the retained table. Nothing happens while
the clock is not set.

On every birth every closed day goes as a historical value of NAME,
stamped 00:00 of its date (the date as CLOCK has it, written as UTC: read
the date, not the hour). So a host that missed days while the link was down
fills them in, and sending a day twice lands on the same timestamp. The live
value of NAME is the last closed day.

When it does not report

LAST_ERROR What it means
waiting for Wi-Fi - is NETWORK enabled? the radio is not joined yet
no STATE from primary host 'scada' SCADA has never connected to this broker - or PRIMARY_HOST is spelt differently from SCADA's host ID
offline STATE from primary host 'scada' SCADA is down. The node waits, as it should
MQTT_CELLULAR needs the modbee-gsm library and a GSM_MODEM add the GSM library and a GSM_MODEM
a board needs the CA in MQTT_CA_CERT_PEM MQTT_TLS_VERIFY with no CA defined: use MQTT_TLS_PINNED with TRUST_NEW for the site's own broker, or add the CA to the board package
no pinned key yet - set TRUST_NEW once to learn it MQTT_TLS_PINNED on a node that has never connected
on a board, set TRANSPORT - MQTT_ARDUINO_WIFI, ... TRANSPORT was left at the Runtime's default

Next: 07 Block reference for every pin.