UT_ANALOG_OUT — Analog output (eng → raw, clamp, ramp, hand, fail value)

UT_ANALOG_OUT — Analog output (eng → raw, clamp, ramp, hand, fail value)

Turns an engineering value (e.g. % speed, % valve) into the raw value for an analog
output card. It adds limits, a rate limit, a hand value, and a defined value on
interlock.

Pins

Pin Type Default What to wire
in In REAL 0.0 Engineering demand (Auto), e.g. the PID output
in Interlock BOOL TRUE FALSE → failValue (or hold), in Hand too
in Hand BOOL FALSE Use handValue (or set cmdMode)
out Out REAL Engineering value actually output
out OutRaw UINT For %QW
out Limited BOOL Clamped or ramping
inout Data UT_ANALOG_OUT_DATA

Record UT_ANALOG_OUT_DATA

Field Type Default Meaning
engMin / engMax REAL 0.0 / 100.0 Engineering range
rawMin / rawMax REAL 0.0 / 65535.0 Raw values at engMin / engMax (e.g. 0 / 27648)
outMin / outMax REAL 0.0 / 100.0 Output clamp (either order works)
rampUp / rampDown REAL 0.0 / 0.0 Rate limit rising / falling, engineering units per rateUnit (0 = off)
failValue REAL 0.0 Output while Interlock is FALSE (at once, no ramp)
holdOnInterlock BOOL FALSE TRUE: hold the output instead of failValue
handValue REAL 0.0 Output in Hand. Tracks In while in Auto, so switching to Hand is bumpless
cmdMode INT -1 HMI: 1 Hand, 2 Auto. Acts when a new value arrives; set back to −1; other codes are ignored
out, raw, hand Status: Out, OutRaw, in Hand now
wrnBadInput BOOL The demand is NaN or infinite: the output holds
wrnConfig BOOL engMin = engMax, or a NaN / infinite range or limit, or an unknown rateUnit
rateUnit UT_RATE_UNIT UT_PER_SEC rampUp / rampDown are per second, minute (UT_PER_MIN), hour or day

How it works

  • Auto / Hand: Hand if the Hand pin is TRUE or the HMI chose Hand
    (cmdMode 1). The HMI choice starts in Auto.
  • Clamp, then ramp: the demand is clamped to outMin..outMax, then Out moves
    towards it at no more than rampUp / rampDown per rateUnit (timed from real
    elapsed time): a slow valve opening of 10 % per minute is rampUp 10 with
    UT_PER_MIN. An unknown rateUnit sets wrnConfig and the output does not ramp.
    At power-up the output starts from 0 and ramps.
  • cmdMode acts once when a new valid value arrives: one held or rewritten acts
    once. A master that rewrites it every poll goes through UT_CMD.
  • Interlock FALSE: failValue at once (also in Hand), or the last output with
    holdOnInterlock. When it returns, the output ramps back from there.
  • OutRaw is clamped to 0..65535, so it never wraps; a clamp shows on Limited.
  • Power cut: nothing is kept. The HMI choice starts in Auto again. (handValue
    lives in your record: declare the record RETAIN to keep it.)

Using it

SpeedOut(In := SpeedPid.Q, Interlock := PumpRunning, Data := SpeedOutCfg);
%QW0 := SpeedOut.OutRaw;