UT_PUMP — Pump control and protection

UT_PUMP — Pump control and protection

Decides when a pump should run and protects the pump using whatever
instruments the site has. Pressure, flow and suction can each be a switch, a
transducer/meter, both, or not fitted at all. Each has four levels (HH, H, L, LL):
H and L warn early that something is wrong, HH and LL trip. Every protection can
recover by itself, retry a set number of times, or latch, which you choose per
protection.

It drives a motor block: RunCmd → motor AutoCmd, Healthy → motor Interlock.
The motor block owns Hand/Off/Auto and the electrical protection (overload,
thermistor, feedback). Because Healthy is the motor's interlock, a pump trip
(dry run, high pressure…) stops the motor in Hand too. For speed-controlled
pumps, put UT_SPEED_CTRL in front of it.

Pins

Pin Type Default What to wire
in Demand BOOL FALSE Run request, in every mode: DEMAND runs while it is TRUE; EMPTY pumps down now to stopPoint; FILL fills now to stopPoint or the high float; TIMED runs the on/off cycle. From UT_RUN_LIMIT.RunCmd, UT_SPEED_CTRL.Run, UT_ZONE_SEQ.PumpDemand. Ignored while a station owns the pump
in Pv REAL 0.0 Level/pressure for the EMPTY/FILL control modes
in HighFloat BOOL FALSE High-level float, TRUE = made (EMPTY: runs the pump; FILL: stops it). Not used while a station owns the pump. A float that opens at high level: NOT at the pin
in Running BOOL FALSE Motor running (UT_MOTOR.Running)
in MotorReady BOOL TRUE Motor ready (UT_MOTOR.Ready)
in MotorAuto BOOL TRUE Motor in Auto (UT_MOTOR.Auto)
in Pressure REAL 0.0 Discharge pressure transducer (if pressure.sensor is analog)
in PressureHigh BOOL FALSE High-pressure switch, TRUE = pressure high (an NC contact: NOT at the pin)
in PressureLow BOOL FALSE Low-pressure switch, TRUE = pressure low (an NC contact: NOT at the pin)
in Flow REAL 0.0 Flow meter (if flow.sensor is analog)
in FlowSwitch BOOL FALSE Flow switch, TRUE = flow present. A contact that opens on flow: NOT at the pin
in Suction REAL 0.0 Suction pressure or source tank/well level (analog)
in DryRun BOOL FALSE Dry-run float / probe / low-suction switch, TRUE = dry. A float that is made with water (fail-safe on a broken wire): NOT at the pin
in SealLeak BOOL FALSE Seal-leak / moisture probe relay
in ExtFault BOOL FALSE Any other pump trip (bearing temperature relay, vibration switch…)
in PrimeDone BOOL FALSE Pipe filled, if not detected from pressure or flow (see prime)
in Reset BOOL FALSE Reset for MANUAL protections (panel button, rising edge)
in Inhibit BOOL FALSE Stops the pump's own runs at once and blocks them, without a fault: a system off, a tariff period. Status Blocked: inhibit. It does not stop a motor in Hand: for that use the motor's Interlock or ForceOff
in Permissive BOOL TRUE FALSE blocks a start (status Not permitted); a running pump carries on
in StartHold BOOL FALSE TRUE makes a start wait (status Waiting: start hold), e.g. while a stirrer pre-runs. Unlike Permissive, the pump stays Available: a station keeps it called and does not fail over to another pump. A running pump carries on
out RunCmd BOOL → motor AutoCmd
out Healthy BOOL → motor Interlock. FALSE = a pump trip is holding it off
out Available BOOL Healthy, motor ready and in Auto, not inhibited and permitted (or running): can run if asked (stations)
out Fault BOOL Any trip
out Warning BOOL Any warning (an abnormal condition to look at)
out Priming BOOL Pipe-fill phase
inout Data UT_PUMP_DATA The pump's record

Record UT_PUMP_DATA

Control

Field Type Default Meaning
pumpMode UT_PUMP_MODE UT_PM_DEMAND UT_PM_DEMAND (0): run while Demand · UT_PM_EMPTY: start when Pv ≥ startPoint, stop when Pv ≤ stopPoint; Demand pumps down now · UT_PM_FILL: start when Pv ≤ startPoint, stop when Pv ≥ stopPoint; Demand fills now · UT_PM_TIMED: cycles onTime/offTime while Demand (starting with the on phase)
demandStopAtPv BOOL FALSE DEMAND: Pv ≤ stopPoint ends the demand as a normal stop (no fault): status UT_ST_STOPPED_LOW and stopReason UT_STOP_LOW_LEVEL. It runs again once Pv ≥ startPoint or when Demand is given again. The effluent sump's L stop in every mode
startPoint / stopPoint REAL 80.0 / 20.0 EMPTY/FILL. Points the wrong way round (or equal, or not a number) → setpoints warning, no start
onTime / offTime TIME T#5m / T#5m TIMED. onTime 0 = never runs; offTime 0 = runs continuously
startDelay / stopDelay TIME T#0s The request must last this long to start / be gone this long to stop
minRunTime / minOffTime TIME T#0s Anti-short-cycle (trips always stop at once). Power-up counts as a stop
startMask TIME T#10s Low levels with maskAtStart ignored after the motor starts
retryWindow TIME T#1h Window for RETRY counting (all protections)
resetByOff BOOL TRUE The motor leaving Auto (selector to Off) resets MANUAL faults
exerciseInterval / exerciseTime TIME T#0s / T#30s Anti-seize run of an idle pump (0 = off). Not while a station owns the pump, nor in FILL with the high float made
highFloatHold TIME T#2m EMPTY: keep running this long after HighFloat clears, then Pv decides again

Measurements (each a UT_MEAS)

Field Default set-up Typical use
pressure not installed · switch · high switch → HH, low switch → LL · onlyWhenRunning · low levels masked at start · HH trip RETRY (3, delay 1 s, recover 1 min) · H warn (5 s) · L warn (5 s) · LL trip RETRY (3, delay 2 s, recover 5 min) · placeholder sp 10 / 8 / 2 / 1, deadband 0.2 HH = closed valve / deadhead. H = partial blockage. L = high demand / leak. LL = burst main / lost prime
flow not installed · switch · low switch → LL (the block feeds it NOT FlowSwitch: no flow) · onlyWhenRunning · masked at start · HH off · H warn (5 s) · L warn (5 s) · LL trip RETRY (3, delay 2 s, recover 5 min) · placeholder sp 120 / 100 / 20 / 10, deadband 2 LL = no flow (dry, air-locked, blocked). H = burst pipe / end of curve. L = clogging intake or impeller
suction not installed · switch · low switch (the DryRun pin) → LL · checked when stopped too (blocks a start) · LL trip AUTO (delay 1 s, recover 2 min) · others off · placeholder sp 10 / 8 / 2 / 1, deadband 0.2 Dry-run protection on the source: well, dam, tank, suction pressure

Set the setpoints for the site: the values above are placeholders. The pressure and
flow switches are wired to PressureHigh / PressureLow and FlowSwitch; the
suction switch is DryRun. There are no NC settings: every switch pin is TRUE when it
signals (high, low, dry, flow present). Wire a contact that works the other way through
NOT at the pin.

Other protections (each a UT_PROTECTION)

Field Default Raised when
sealLeak WARN, AUTO SealLeak input
extFault TRIP, AUTO ExtFault input
primeTimeout TRIP, RETRY (3, recover 2 min) Not primed in prime.timeout
maxRun OFF, delay T#4h (the maximum continuous run time), reset MANUAL Ran too long: burst main, stuck float. MANUAL so a stuck run cannot repeat itself every recover. maxRunLeft counts down
setpoints WARN EMPTY/FILL points the wrong way round

Priming (prime : UT_PUMP_PRIME)

Field Type Default Meaning
enable BOOL FALSE Prime at every start
doneBy UT_PRIME_DONE UT_PRIME_PRESSURE UT_PRIME_PRESSURE: pressure above L (transmitter above pressure.lo.sp, or the low-pressure switch clear) · UT_PRIME_FLOW: flow above L (meter above flow.lo.sp, or the flow switch showing flow) · UT_PRIME_INPUT: the PrimeDone pin
timeout TIME T#60s Not primed in this time from the moment the motor runs → primeTimeout
holdTime TIME T#2s The primed condition must last this long (with the motor running)

Priming starts when the motor is seen running (the rising edge of Running), so the
motor's restart delay, a start inhibit or the contactor time never count as priming
time, and lasts until primed or the pump stops. While priming, low levels with
maskAtStart are masked and Priming is TRUE (a VSD can run a fill speed from it);
primeLeft counts down the time left and the status shows Priming: 1 m 20 s left.

Prime next start only (cmdPrimeNext): sets primeNext; the next start primes
as with enable. primeNext clears after a completed prime and stays set if the run
stops before the prime completes (or times out). It is not kept over a power cut.
cmdPrimeCancel (or the PrimeCancel pin) withdraws it before that start; a prime
already running carries on.

A prime that can never finish is a configuration fault (status Config: prime needs pressure installed / Config: prime needs flow installed, the pump is held off):
with enable or primeNext, doneBy PRESSURE or FLOW names a measurement that is
not installed, or a switch with no low switch.

Diagnosis (warnings that point at the likely cause)

diagnosis : UT_PUMP_DIAG, from the levels in effect (H or HH = high, L or LL = low),
first match wins:

Value Pattern Likely cause
UT_DIAG_NORMAL (0)
UT_DIAG_BLOCKED pressure high + flow low closed valve, blocked line, deadhead
UT_DIAG_BURST pressure low + flow high burst pipe, open hydrant
UT_DIAG_SUCTION suction low (L or LL) source running low, blocked foot valve or strainer
UT_DIAG_NO_LIFT pressure low + flow low air lock, dry, worn impeller, wrong rotation

HMI commands

Field Type Meaning
cmdReset BOOL Reset MANUAL protections
cmdExercise BOOL Exercise run now (if idle and available)
cmdPrimeNext BOOL Prime on the next start only (sets primeNext)
cmdPrimeCancel BOOL Withdraw prime next start (clears primeNext)

Each acts once, on its rising edge, and is cleared by the block; a held command acts
once.

Status fields

state : UT_STATE (FAULT · STARTING · WARNING · ON · STOPPING · OFF), runCmd,
demand (asked to run, after the delays), running, healthy, available,
priming, masked, runTime : TIME (this run), exercising, highFloat (the high
float is acting: EMPTY made or in its hold, FILL made), pvBad (Pv not a number in
EMPTY/FILL: the last decision is held), configBad (a setting is invalid, bit 18),
stationOwned, diagnosis, fault, warning, faultCode : DWORD, faultId : UT_FAULT
(the first trip by the bit order below, else the first warning),
statusCode : UT_STATUS and statusText : STRING(30) (what it is doing or what holds
it back, see Status).

More status fields:

Field Type Meaning
demandStopAtPv BOOL Setting, see Control
cmdPrimeNext BOOL HMI command, see Priming
cmdPrimeCancel BOOL HMI command, see Priming
primeNext BOOL A one-shot prime is armed
primeLeft TIME The prime's time still to run while priming: prime.runTime when done by TIME, else up to prime.timeout (0 otherwise)
maxRunLeft TIME Time before maxRun trips (0 when it is OFF, tripped or the pump is stopped)
timeLeft TIME The countdown that goes with the status: a delay, priming, a fault's recover / retry wait… (0 = none)
timeLeftOf UT_STATUS The statusCode that countdown belongs to (UT_ST_IDLE = none)
phaseTime TIME Time in the current phase: running (runTime) or stopped (idleTime)
idleTime TIME Time since the pump last ran (0 while running)
nextExerciseIn TIME Time to the next exercise run (0 when exercise is off, or running)
inhibited BOOL The Inhibit pin is holding its runs off
startHold BOOL StartHold is making a start wait (FALSE while the run command is on). A station does not fail over from a pump while this is set
stopReason UT_STOP Why the last run ended (below)
lastFaultCode / lastFault DWORD / UT_FAULT The trip bits and the name of the last trip, kept after it clears until the next trip
trips UDINT Trips since power-up

Stop reasons (stopReason)

The shared reasons (conventions) and the pump's own:

stopReason Words (UT_STOP_TEXT) When the run ended
UT_STOP_DEMAND_ENDED Auto: demand ended The request dropped (Demand, the level reached the stop point, a TIMED off phase)
UT_STOP_OPERATOR Stopped: operator A Hand run ended
UT_STOP_SWITCHED_OFF Stopped: switched off The motor left Auto while the pump was running it
UT_STOP_FAULT Stopped: fault A pump trip (lastFault says which)
UT_STOP_MAX_RUN Stopped: max run time maxRun tripped
UT_STOP_INHIBITED Stopped: inhibited The Inhibit pin
UT_STOP_GROUP Stopped: group The station stopped it
UT_STOP_LOW_LEVEL Stopped: low level Demand reached the stop point (DEMAND with demandStopAtPv, or an EMPTY pump-down)
UT_STOP_FULL Stopped: full FILL: the high float, or Demand filled to the stop point
UT_STOP_EXERCISE_DONE Done: exercise An exercise run finished
UT_STOP_BY_MOTOR Stopped: by the motor The motor stopped while commanded (its trip, interlock, feedback): the motor's own stopReason says why

Group fields, written by UT_PUMP_STATION: grpActive (set by the
station every scan, cleared by the pump), grpRun, grpRank, grpSkipped, and
grpRunTime : TIME (the run time the station has counted since power-up, for its
HOURS rotation; the station sets it back to 0 on its first scan after a power cut, also in a RETAIN record).

Fault code bits (lowest = most important; faultId names the first trip, else the first warning)

Bit Protection faultId (words)
0 suction.loLo UT_F_DRY_RUN (dry run)
1 pressure.hiHi UT_F_PRESSURE_HH (pressure HH)
2 pressure.loLo UT_F_PRESSURE_LL (pressure LL)
3 flow.loLo UT_F_NO_FLOW (no flow)
4 flow.hiHi UT_F_FLOW_HH (flow HH)
5 suction.hiHi UT_F_SUCTION_HH (suction HH)
6 primeTimeout UT_F_PRIME (failed to prime)
7 extFault UT_F_EXTERNAL (external fault)
8 maxRun UT_F_MAX_RUN (ran too long)
9 sealLeak UT_F_SEAL_LEAK (seal leak)
10–15 pressure.hi, pressure.lo, flow.hi, flow.lo, suction.hi, suction.lo UT_F_PRESSURE_H, UT_F_PRESSURE_L, UT_F_FLOW_H, UT_F_FLOW_L, UT_F_SUCTION_H, UT_F_SUCTION_L (pressure high … suction low)
16 setpoints UT_F_POINTS (start/stop points)
17 Pv not a number or infinite (EMPTY/FILL, own control): a warning, the last decision is held UT_F_PV_BAD (Pv not a number)
18 A setting is invalid: a trip for a configuration fault, else a warning The setting (configuration faults, below), or UT_F_SETTING (a setting)
19 A fitted pressure, flow or suction transmitter reads NaN or infinite: a warning (its levels hold; a switch with UT_SENSOR_BOTH still acts) UT_F_SENSOR_BAD (sensor bad)

Invalid settings

  • Configuration fault (bit 18 as a trip: Healthy FALSE, the pump is held off until
    it is fixed): an unknown pumpMode; a fitted measurement with an unknown sensor,
    highSwitch (only NONE, HH, H) or lowSwitch (only NONE, L, LL); an unknown
    response in any level or protection; with prime.enable or primeNext, an unknown
    prime.doneBy, or a doneBy measurement that is not installed (or a switch with no
    low switch).
    Each of these would switch a protection off without telling anyone.
  • Warning (bit 18 as a warning, the pump runs): a negative time (it acts as 0); a
    level or protection with a bad setpoint, deadband or time (BadSetting of its check);
    an unknown reset (acts as AUTO).
  • Start/stop points the wrong way round or not a number: the setpoints protection
    (bit 16, WARN by default) and no start from Pv.

Status

statusCode, faultId and statusText say the one main thing the pump is doing,
or what holds it back, so a technician can see on the HMI why it is not running
without opening the program. The most important reason wins: configuration > fault >
held / waiting > warning > running > idle. A pump asked to run (a request, an
exercise, or its run command) that is not running always shows a held, fault or
configuration status, or UT_ST_STARTING while its run command is out and the
motor's run feedback is not yet in. A warning shows over "Running" so it is seen.
The countdown is in timeLeft, and timeLeftOf says which status it belongs to.
The text is rebuilt only when the status or the fault changes (or when the text has
been cleared). A pump with Demand TRUE never says Idle. The numbers are in
conventions.

statusCode Words When
UT_ST_IDLE Idle Nothing asks it to run
UT_ST_OFF_NOT_AUTO Off: motor not in Auto Nothing asks it to run, and the motor is not in Auto
UT_ST_RUN_AUTO Running: Auto Running on its own request
UT_ST_RUN_HAND Running: Hand Running with the motor not in Auto
UT_ST_STARTING Starting Run command out, run feedback not yet in
UT_ST_STOPPING Stopping Run command off, the motor still running
UT_ST_RUN_GROUP Running: group A UT_PUMP_STATION runs it; grpRank is its place
UT_ST_EXERCISING Exercising An exercise run (timeLeft)
UT_ST_IDLE_GROUP Idle: in group A station owns it and has not called it
UT_ST_PRIMING Priming Filling the pipe; timeLeft is the time before primeTimeout
UT_ST_HIGH_FLOAT Running: high float EMPTY: the high float runs it (made, then highFloatHold, counting in timeLeft)
UT_ST_MIN_RUN Running: min run time The request has gone; minRunTime keeps it on (timeLeft)
UT_ST_STOP_DELAY Running: stop delay The request has gone; stopDelay keeps it on (timeLeft)
UT_ST_RUN_TIMED Running: timed TIMED: the on time (timeLeft)
UT_ST_RUN_DEMAND Running: demand EMPTY / FILL: Demand runs it (pump down / fill up), not the level
UT_ST_NOT_PERMITTED Not permitted Asked to run, Permissive is FALSE
UT_ST_START_HOLD Waiting: start hold Asked to run, StartHold is TRUE (shown after Not permitted)
UT_ST_MIN_OFF Waiting: min off time Asked to run inside minOffTime (timeLeft)
UT_ST_START_DELAY Waiting: start delay Asked to run, startDelay not over (timeLeft)
UT_ST_INHIBITED Blocked: inhibit Asked to run (or Demand TRUE), Inhibit is on
UT_ST_MOTOR_NOT_AUTO Blocked: motor not in Auto Asked to run, the motor is in Off, Hand or OOS
UT_ST_MOTOR_NOT_READY Blocked: motor not ready Asked to run, the motor is not ready (its trip, interlock, permissive or restart delay: the motor's own status says which)
UT_ST_FULL Blocked: high float (full) FILL: the high float is made
UT_ST_TIMED_REST Waiting: timed rest TIMED: the off time (timeLeft)
UT_ST_STOPPED_LOW Stopped: low level Demand is TRUE but its run reached the stop point; it runs again at the start point or a new Demand
UT_ST_STOPPED_FULL Stopped: full As above, in FILL
UT_ST_WARNING Warning: <fault> A protection set to WARN (e.g. Warning: seal leak), bit 17 (Warning: Pv not a number) or bit 19 (Warning: sensor bad)
UT_ST_WARN_SETTING Setting: <setting> Bit 18 as a warning: a safe value is used
UT_ST_FAULT Fault: <fault> A trip with AUTO reset, e.g. Fault: dry run; timeLeft while the recover time counts
UT_ST_FAULT_RETRY Retrying: <fault> A RETRY trip: the protection's retries of maxRetries, and the wait left in timeLeft
UT_ST_FAULT_RESET Latched: <fault> A MANUAL trip
UT_ST_FAULT_LOCKED Locked: <fault> A RETRY trip past maxRetries
UT_ST_CONFIG Config: <setting> It will not run until fixed (settings below)

<fault> is faultId: the first trip by the bit order above, else the first warning.
<setting> with UT_ST_CONFIG is one of: UT_F_PUMP_MODE (pump mode) ·
UT_F_PRIME_DONEBY (prime doneBy) · UT_F_PRIME_NEEDS_PRES (prime: no pressure) ·
UT_F_PRIME_NEEDS_FLOW (prime: no flow) · UT_F_PRESSURE_SENSOR /
UT_F_FLOW_SENSOR / UT_F_SUCTION_SENSOR (sensor or switch level unknown) ·
UT_F_RESPONSE (response unknown) · UT_F_POINTS (start/stop points wrong way
round). With UT_ST_WARN_SETTING it is the setting found, or UT_F_SETTING (a setting).

How it works

  • Run request: a station's grpRun while a station owns the record, otherwise
    the pumpMode and Demand. Then startDelay / stopDelay, then exercise. RunCmd
    follows it with minRunTime / minOffTime; any pump trip, and Inhibit, drop it at
    once; Permissive FALSE holds back a start; so does StartHold, which keeps the
    pump available.
  • Demand in every mode. DEMAND: runs while Demand is TRUE (with
    demandStopAtPv until Pv ≤ stopPoint). EMPTY: Demand pumps down now, to
    stopPoint, with the protections kept ("run now"). FILL: Demand fills now, to
    stopPoint or the high float. After such a stop a held Demand runs again once
    Pv is back at startPoint (the level control would start it there anyway), or
    when it is given again (a new rising edge). A Pv that is not a number holds it.
  • Station: the station sets grpActive every scan and the pump clears it after
    reading it, so if the station block stops being called the pump is back on its own
    mode from the next scan. On its first scan after power-up the pump ignores
    grpRun (a retained record must not start every pump at once).
  • Resets of MANUAL protections (and RETRY ones whose retries are used up): the
    Reset pin, cmdReset, or the motor leaving Auto (resetByOff). Refused while the
    cause is still there. A reset clears faults only: the event counts
    (count in each protection) are kept.
  • Exercise: an idle pump that is healthy, ready and in Auto runs exerciseTime
    after exerciseInterval without running (or on cmdExercise). A real request
    takes over from an exercise.
  • A Pv that is not a number (NaN, infinity) holds the pump as it is (the last good
    decision) and raises a warning (bit 17, pvBad). The floats still act.
  • High float (HighFloat, own control only, ignored while a station owns the
    pump). EMPTY: overflow backup. The pump runs while the float is made, whatever Pv
    says, and highFloatHold after it clears. After that Pv decides again: a good Pv
    above the stop point keeps it running down to the stop point; a stuck or bad Pv
    lets it stop, and the float catches the next rise. A float stuck made keeps the pump
    running until its dry-run protection (DryRun) stops it, so fit one. FILL: the tank
    is full, the pump stops while the float is made (its own stopDelay / minRunTime
    still apply) and is not exercised. DEMAND and TIMED: not used.

Power cut

Nothing is kept: every protection starts clear, with no retries used. A latched
(MANUAL) trip is forgotten; a fault that is still there trips again before the pump
can start. primeNext, stopReason, the last fault and trips start again. Power-up
counts as a stop for minOffTime.

Keep your record RETAIN (or write the settings every scan) so the settings are
there on the first scan.

Examples of set-ups

Site Settings
Sump pump with a dry-run float only suction.installed := TRUE (switch). Everything else not installed
Bore pump, pressure switch high only, auto recovery pressure.installed := TRUE, pressure.highSwitch := UT_LVL_HIHI, pressure.lowSwitch := UT_LVL_NONE, pressure.hiHi.reset := UT_RST_AUTO
Irrigation pump with transducer + flow meter pressure.sensor := UT_SENSOR_ANALOG, the four setpoints; flow.sensor := UT_SENSOR_ANALOG, setpoints; prime.enable := TRUE
Effluent sump pump, L stop in every mode, irrigation runs from UT_RUN_LIMIT pumpMode := UT_PM_DEMAND, demandStopAtPv := TRUE, stopPoint := L, startPoint := H; Demand := SumpEmpty OR RunLimit.RunCmd OR ManualRun; Inhibit := SystemOff; maxRun.response := UT_RESP_TRIP (4 h, MANUAL)
Booster with pressure switch and transducer pressure.sensor := UT_SENSOR_BOTH. Either one raises its level (the switch backs up the transducer)

Using it

Pump1(Demand := LevelHigh, Running := M1.Running, MotorReady := M1.Ready, MotorAuto := M1.Auto,
      DryRun := LowFloat, PressureHigh := P1_HiPS, Data := Pump1Data);
M1(AutoCmd := Pump1.RunCmd, Feedback := P1_Aux, Overload := P1_OL,
   Interlock := Pump1.Healthy, Data := Motor1);