10 - Scan rate

10 - Scan rate

Almost every "Modbus is slow" complaint is the task interval rather than the
bus, and there is one change that fixes it.

The one rule

MODBUS_NODE is the only block that touches the wire, and it does one
poll's worth of work per call.
It transmits, it receives, it retries, it times
out — once, then returns.

So the node's task interval is the floor on how fast anything happens. A
node called every 20 ms cannot start a request more often than every 20 ms,
however fast the bus is and however little there is to carry.

Put it, and every block given it, in a fast task of their own; your
application stays where it is and trades values with them through globals:

task interval priority holds
APP_TASK T#20ms 0 the machine - no Modbus block at all
NET_TASK T#1ms on the Runtime 20 MODBUS_NODE and every block given it

Declare the node in the network program, never in a global list. OpenPLC
locks every access to a shared global, and a block instance is one: a machine
task that so much as names a global MODBUS_NODE waits for the network task to finish
with it - before the block's own task check has run. Measured on a Node UIO with
the client global and one block of it in the 20 ms task: the broker went away,
the network task's scans stretched while it reconnected, the machine task sat
199 ms behind it and OpenPLC stopped the PLC. MODBUS_WRONG_TASK stops a race; only
keeping the instance out of the global list stops the wait. Plain values in the
list are fine - each access is a copy.

Every block given the node runs in the node's task. OpenPLC runs each task
on a thread of its own, and the library underneath is single-threaded: a
MODBUS_READ in another task would be inside the node while the node's own
scan is - one thread adding to its queue while the other walks it. So each
block checks, and in any other task does nothing and says MODBUS_WRONG_TASK.
It never races and never waits: a lock that waited would hold your application
back by the node's scan.

VAR_GLOBAL  (* PLANT: each written by one task only *)
  rFlow     : REAL;   (* written by net - what was read *)
  rSpeedSp  : REAL;   (* written by main - what to write *)
END_VAR

PROGRAM net                                  (* NET_TASK *)
  VAR
    node : MODBUS_NODE;
    flow : MODBUS_READ;
    sp   : MODBUS_WRITE;
  END_VAR
  node( TRANSPORT := MODBUS_RUNTIME_SERIAL, SERIAL_DEVICE := '/dev/ttyUSB0',
        SERIAL_BAUD := 38400, ROLE := MODBUS_ROLE_CLIENT );
  flow( NODE := node, REQ := TRUE, UNIT := 2,
        FC := MODBUS_FC03_READ_HOLDING_REGISTERS, ADDRESS := 100,
        VALUE := PLANT.rFlow );
  sp  ( NODE := node, REQ := TRUE, UNIT := 2, FC := MODBUS_FC_AUTO,
        ADDRESS := 200, VALUE := PLANT.rSpeedSp );
END_PROGRAM

That is the whole of it. Everything below explains why it matters and what to
expect once you have done it.

What the bus itself costs

Modbus RTU sends 11 bits per character — a start bit, eight data bits, a parity
bit and a stop bit. Everything else follows from that.

One read, request and response, including the silence that frames it:

baud 1 register 10 registers 100 registers 100 read one at a time
9600 25 ms 46 ms 252 ms 2.5 s
19200 13 ms 23 ms 126 ms 1.3 s
38400 6 ms 12 ms 63 ms 0.6 s
115200 2 ms 4 ms 21 ms 0.2 s

Add the device's own turnaround, which for a small drive or meter is commonly
another 5 to 20 ms and is not something you can change.

Two things fall straight out of that table.

Read ranges, not addresses. A hundred registers as one request costs 126 ms
at 19200. The same hundred read one at a time costs 1.3 seconds — ten times
worse, for exactly the same data. This is the single biggest lever you have.

The bus is slower than your scan, by a lot. At 19200 a single read takes
about 13 ms, which is thirteen scans of a 1 ms task. Your program is never
waiting on your program; it is waiting on the wire. That is exactly why nothing
here blocks.

Why a 1 ms task, when a read takes 13 ms

Because the node does not spend 13 ms working. It spends 13 ms waiting, and
it checks for progress each time it is called.

  • Called every 1 ms, it notices the response about 1 ms after it lands, and
    starts the next request straight away.
  • Called every 20 ms, it notices up to 20 ms late, and then the next request
    waits for the following call. A 13 ms transaction becomes a 40 ms one.

That is a threefold loss on an idle bus, and it gets worse as you add
devices, because every transaction pays it.

The node costs almost nothing when there is nothing to do: it checks the
transport, finds no bytes and returns. A 1 ms task holding one node block is
cheap.

Budgeting a bus

Add up what you are asking for and compare it with what the wire can carry.

A segment at 19200 with six devices, each watched every 500 ms for 20 registers:

one read of 20 registers   ≈  33 ms wire + ~10 ms device  ≈  43 ms
six of them                ≈ 258 ms
required every 500 ms      →  about half the bus

That leaves room for control writes and for retries. Halve the interval and
there is none, and every MODBUS_WRITE starts queueing behind a watch.

Signs you have overbooked the bus:

  • MODBUS_WATCH.QUALITY sitting at MODBUS_QUALITY_UNCERTAIN — values
    arriving, but late;
  • MODBUS_STATUS.PENDING climbing instead of hovering near zero;
  • MODBUS_QUEUE_FULL on requests that used to work;
  • a write that takes noticeably longer than it used to.

What to do about it, in order of how much it buys you:

  1. Read wider ranges. Ten registers cost barely more than one.
  2. Watch less often. A tank level does not need 200 ms.
  3. Turn off watches you are not using, with ENABLE.
  4. Raise the baud rate. 38400 halves everything in the table, and most
    modern devices manage it over a properly terminated segment.
  5. Split the bus. Two segments on two ports carry two conversations at
    once; one segment never will.

A watch cannot flood the bus

This is worth stating plainly, because it is what makes MODBUS_WATCH safe to
use freely.

A watch asks for a read every EVERY. If the previous read is still
outstanding
when the next falls due, the new one is refused as a duplicate
rather than stacked behind it. So the worst a watch can do is have one request
outstanding at a time, however short its interval.

A device that stops answering is backed off, progressively, to as little as
one attempt in sixteen. One dead unit on a segment of twenty therefore costs
that segment almost nothing, instead of consuming it with timeouts. It picks
itself up when the device returns.

Where the time actually goes

When a value seems slow, it is one of four things, and they are easy to tell
apart:

how to tell
the node's task interval it is slower than it needs to be. Check first, fix first
the bus is full PENDING climbing, QUALITY UNCERTAIN
the device is slow MODBUS_DEVICE.ROUND_TRIP is high for that unit and normal for the others
the bus is slow ROUND_TRIP is high for every unit

ROUND_TRIP is measured, not configured, and it settles the "is it the
device or the bus" argument in about ten seconds.

Two nodes, two buses

Two MODBUS_NODE instances are two independent links, and they poll
independently. Put both in the same fast task:

PROGRAM net
VAR
    fieldBus : MODBUS_NODE;
    scada    : MODBUS_NODE;
END_VAR

fieldBus( TRANSPORT := MODBUS_RUNTIME_SERIAL,
          SERIAL_DEVICE := '/dev/ttyUSB0', SERIAL_BAUD := 38400,
          ROLE := MODBUS_ROLE_CLIENT );

scada   ( TRANSPORT := MODBUS_RUNTIME_TCP,
          ROLE := MODBUS_ROLE_SERVER );
END_PROGRAM

The serial segment reads field devices; the TCP server answers SCADA. Neither
waits for the other, and a slow drive on the field bus cannot delay a SCADA
poll.

On a board

The same rule, with less room.

Measure before going fast. OpenPLC stops the PLC when a task is still in one
scan after 10 of its intervals, so a T#1ms task needs every scan of the node
under 10 ms. Bringing Wi-Fi or Ethernet up is not that - DHCP alone waits up to
a second - so a node on a network link starts at T#50ms. Check the task's
longest scan with openplc-cli debug stats on your own link before going
faster.

An RS-485 frame never holds the scan. On an ESP32 the node gives the port
a transmit buffer that holds any frame, and lets the UART drive the
transceiver's DE pin itself (page 03): the frame leaves in the background,
and the driver is released after the last stop bit.

And memory: each link costs roughly two kilobytes before any of your data, so
two links and a large register map is a real figure on a device with a few
hundred kilobytes.