UT_MSG_QUEUE — Message ticker and site-status board

UT_MSG_QUEUE — Message ticker and site-status board

Puts the plant's status messages on one HMI text line. Every device block that can
stop equipment has a statusCode and a faultId; feed them all into one
UT_MSG_QUEUE and it shows them one at a time.

  • QUEUE (the default): a message ticker. Each new or changed message is queued,
    shown for showTime, then dropped, in the order they came.
  • ACTIVE: a site-status board, "what's wrong now". Each source has one slot
    holding its current message; when the source goes back to normal the slot goes.
    The display goes round the active ones every showTime.

A message is codes, not words: the source's status and fault. The block keeps only
the codes, and makes the words of the one message on display (Message, with
UT_STATUS_TEXT); an HMI can show its own words from MsgStatus
and MsgFault. You size the storage: the block uses the Buffer and Sources
arrays you declare, so its RAM is what you give it.

Pins

Pin Type Default What to wire
in Status UT_STATUS UT_ST_IDLE The source's status, e.g. Pump1.statusCode (from the record)
in Fault UT_FAULT UT_F_NONE Its fault, e.g. Pump1.faultId
in Src INT 1 Source number: the element of Sources this call uses
in Clock DT Optional real-time clock: each message is stamped with it
out Message STRING(30) The message on display in words, UT_STATUS_TEXT(MsgStatus, MsgFault) ('' = none)
out Count INT Messages waiting, with the one shown (QUEUE), or active (ACTIVE)
out MsgSrc INT Source of the message on display (0 when none; check Count)
out MsgStatus UT_STATUS Its status (UT_ST_IDLE when none)
out MsgFault UT_FAULT Its fault (UT_F_NONE when none)
out NewMsg BOOL On for the scan in which a message came or changed (a beep, a log trigger)
inout Buffer ARRAY[*] OF UT_MSG The slots: as many as you declare
inout Sources ARRAY[*] OF UT_MSG_SRC One element per source: the last status and fault seen. The block writes it
inout Data UT_MSG_DATA Settings and status (below)

Record UT_MSG_DATA

Field Type Default Meaning
mode UT_MQ_MODE UT_MQ_QUEUE UT_MQ_QUEUE (0): each new message once, in turn. UT_MQ_ACTIVE: each source's current message. A change starts afresh
showTime TIME T#3s Each message is on display this long (at least one scan; T#0s = one scan each)
minKind UT_KIND UT_KIND_HELD Only statuses of this kind or worse are taken (UT_STATUS_KIND). The order is normal, held, warning, fault, then configuration. UT_KIND_HELD = held / waiting, warnings, faults and configuration; UT_KIND_WARNING = warnings and worse; UT_KIND_NORMAL = every change (QUEUE: an event log, "Off" too). ACTIVE never shows UT_ST_IDLE, UT_ST_OFF or UT_ST_OK
whenFull UT_MQ_FULL UT_MQ_DROP_OLDEST UT_MQ_DROP_OLDEST (0): make room by dropping the oldest (counted in lost). UT_MQ_HOLD_NEW: keep what is there; a new message waits until there is room (its source is tried again on every call)
clearFullAfter TIME T#0s QUEUE: a buffer that stays full this long is emptied (counted in lost). T#0s = never
cmdClear BOOL HMI: QUEUE empties the queue. ACTIVE builds the list again from the sources now
cmdNext BOOL HMI: show the next message now (QUEUE drops the one on display)
count INT Status: as Count
full BOOL Status: every slot used
lost UDINT Status: messages dropped to make room, or by clearFullAfter (since power-up)
wrnConfig BOOL Status: a setting is invalid (a safe value is used), or Buffer or Sources is empty
wrnSrc BOOL Status: a call this scan had a Src outside Sources (that call is ignored)

Slot UT_MSG

Field Type Meaning
stamp DT Clock when the message came (or changed)
src INT Source number
status UT_STATUS Its status
fault UT_FAULT Its fault

Source UT_MSG_SRC (written by the block)

Field Type Meaning
status UT_STATUS The last status seen from this source
fault UT_FAULT The last fault seen from this source
known BOOL FALSE: nothing seen yet (ACTIVE builds again)

RAM. A slot holds no text, only the time stamp and three small codes, and a
source two codes and a flag, so a large buffer costs little. Size the buffer for
the messages you want to keep, not for every device: in ACTIVE mode a site rarely
has more than a handful of things wrong at once.

How it works

  • Call it once per source per scan, all calls on the same instance, Buffer,
    Sources and Data. Give each call its own Src. The order of the calls is
    the order of messages that arrive in the same scan.
  • Sources[Src] keeps the last status and fault seen from that source. Nothing is
    taken until one of them changes, so 20 sources cost a few number compares each a
    scan. A countdown is not a change: the time left is in the device's record
    (timeLeft), not in the message.
  • A status below minKind is not taken; in ACTIVE mode it (or UT_ST_IDLE,
    UT_ST_OFF, UT_ST_OK) removes that source's slot and the rest move up.
  • ACTIVE: a new fault with the same status (one protection taking over from
    another) updates the source's slot in place; if it is on display, Message
    changes at once.
  • QUEUE: a source that changes status or fault again before its first message is
    shown gets a second message. Use ACTIVE when only the latest matters.
  • NewMsg stays on for the rest of the scan in which a message came, whichever
    call took it; cmdClear and cmdNext act once per scan. (TIME() is the same
    for the whole scan, which is how the block knows a new scan has started.)
  • MsgSrc and Src count however you number your Sources array:
    ARRAY[1..20] OF UT_MSG_SRC takes sources 1..20, ARRAY[0..9] OF UT_MSG_SRC
    sources 0..9.
    Buffer can start at any index too. An empty Buffer keeps nothing.
  • Every loop is bounded by the arrays you declare; there are no WHILE loops.
  • Nothing is retained: after a power cut the buffer starts empty, and every source
    with a status of minKind or worse comes back in on its first call.

Using it

VAR
  Msgs : UT_MSG_QUEUE;
  MsgBuf : ARRAY[1..8] OF UT_MSG;          (* 8 messages at a time *)
  MsgSrc : ARRAY[1..6] OF UT_MSG_SRC;      (* sources 1..6 *)
  MsgCfg : UT_MSG_DATA := (mode := UT_MQ_ACTIVE, showTime := T#4s);
  HmiLine : STRING(30);
END_VAR

Msgs(Status := Pump1Data.statusCode, Fault := Pump1Data.faultId, Src := 1, Clock := SiteClock,
     Buffer := MsgBuf, Sources := MsgSrc, Data := MsgCfg);
Msgs(Status := Pump2Data.statusCode, Fault := Pump2Data.faultId, Src := 2, Clock := SiteClock,
     Buffer := MsgBuf, Sources := MsgSrc, Data := MsgCfg);
Msgs(Status := StationData.statusCode, Fault := StationData.faultId, Src := 3, Clock := SiteClock,
     Buffer := MsgBuf, Sources := MsgSrc, Data := MsgCfg);
Msgs(Status := DoseData.statusCode, Fault := DoseData.faultId, Src := 4, Clock := SiteClock,
     Buffer := MsgBuf, Sources := MsgSrc, Data := MsgCfg);
(* a plain condition with no status record: give it a status of its own *)
Msgs(Status := SEL(HighLevelFloat, UT_ST_IDLE, UT_ST_WARNING), Fault := UT_F_HIGH,
     Src := 5, Buffer := MsgBuf, Sources := MsgSrc, Data := MsgCfg);
HmiLine := Msgs.Message;    (* or the HMI's own words for Msgs.MsgStatus / MsgFault *)

In Ladder or FBD, give each call its own unconditional rung (see
ladder-rules.md); the calls share the instance.

For a ticker of events, leave mode at QUEUE.
For a "what's wrong now" board next to an overview screen, use ACTIVE.

Bad settings

A negative showTime acts as 3 s, an unknown minKind as UT_KIND_HELD, a negative
clearFullAfter as T#0s, an unknown mode as QUEUE and an unknown whenFull
as DROP_OLDEST; each sets wrnConfig. An empty Buffer or Sources also sets
wrnConfig.