UT_VALVE — Two-position valve, cylinder or damper

UT_VALVE — Two-position valve, cylinder or damper

Opens and closes any two-position actuator and supervises its limit switches:

  • solenoid valves and cylinders with spring return (one coil),
  • double-solenoid valves held in position (two coils),
  • bistable / latching solenoids that need only a pulse (two coils),
  • motorised on/off valves and dampers (drive to the limit, then stop).

Hand/Off/Auto/OOS is built in, like the motors. The shared logic (mode, safe
position, protections, stroke count) is UT_VALVE_CORE.

Pins

Pin Type Default What to wire
in AutoOpen BOOL FALSE Auto command: TRUE = open, FALSE = close
in OpenLs BOOL FALSE Open limit switch
in ClosedLs BOOL FALSE Closed limit switch
in Interlock BOOL TRUE FALSE drives to safePosition in every mode
in DriveFault BOOL FALSE Actuator thermal / fault relay
in SwHand, SwAuto BOOL FALSE Selector switch (if modeSource uses it)
in Reset BOOL FALSE Fault reset (rising edge)
in Permissive BOOL TRUE FALSE: no move away from the safe position starts; it never forces safe
in LocalOpen / LocalClose BOOL FALSE Local pushbuttons (Hand), each on its rising edge
in LocalStop BOOL FALSE Local stop pushbutton (Hand; held: stops and keeps stopping). Motorised: stops where it is
out OpenOut BOOL Open coil / the single solenoid / motor open
out CloseOut BOOL Close coil / motor close (unused for spring return)
out IsOpen BOOL Confirmed open
out IsClosed BOOL Confirmed closed
out Fault BOOL A trip is holding it in the safe position
out State UT_STATE OFF = closed, ON = open, STARTING = opening, STOPPING = closing
inout Data UT_VALVE_DATA The valve's record

Record UT_VALVE_DATA (shared by every UT_VALVE* block)

Settings

Field Type Default Meaning
valveType UT_VALVE_TYPE UT_VT_SPRING See types
modeSource UT_MODE_SOURCE UT_SRC_HMI As motors. The mode starts at Off and is retained
resetByOff BOOL TRUE Switching to Off resets MANUAL faults
restartAfterReset BOOL FALSE After a MANUAL reset, move again without a new command
retryWindow TIME T#1h Window for RETRY counts
useOpenLs / useClosedLs BOOL TRUE / TRUE Which limits are fitted
openTime / closeTime TIME T#10s / T#10s Travel timeout. Without that limit, the travel is taken as complete after this
pulseTime TIME T#500ms Coil pulse length for bistable valves
reversalDelay TIME T#500ms Motorised: pause with both outputs off before driving the other way
safePosition UT_SAFE_POS UT_SAFE_CLOSED On interlock, Off mode or a trip: UT_SAFE_CLOSED, UT_SAFE_OPEN, UT_SAFE_HOLD
saveEvery TIME T#12h How often the stroke count is saved for a power cut (T#0s = not kept)
simulate BOOL FALSE Positions follow the commands after the travel time, protections suppressed
powerUp UT_POWERUP UT_PU_LAST After a power cut: UT_PU_LAST the mode comes back; UT_PU_OFF back to Off (and its safe position) until the operator selects it again. See conventions

The three-position, modulating and floating blocks keep their own settings, commands
and status in a second record of their own (Pos3, Modul, Floating), so a
two-position valve carries none of them. See 3POS,
MOD and FLOAT. reversalDelay is in this
record and is used by every motorised or floating valve.

UT_VALVE_TYPE:

Value Outputs
UT_VT_SPRING OpenOut held while open, off = close (spring)
UT_VT_DOUBLE_HELD OpenOut held while open, CloseOut held while closed
UT_VT_DOUBLE_PULSE OpenOut / CloseOut pulsed for pulseTime, once per move (bistable)
UT_VT_MOTOR OpenOut / CloseOut on until the limit (or the travel time), then off. Hand can stop mid-travel.

UT_SAFE_HOLD stops a motorised valve where it is; the coil types keep their
coils as they were.

Protections (each a UT_PROTECTION; response and reset set per protection)

Field Bit Default response · delay · reset Raised when
openTimeout 0 TRIP · 0 · RETRY (2, recover 1 min) Didn't reach open within openTime (only with the open limit fitted)
closeTimeout 1 TRIP · 0 · RETRY (2, recover 1 min) Didn't reach closed within closeTime
bothLimits 2 TRIP · 0 · AUTO Both limits on (switch fault). Clears when one drops
positionLost 3 TRIP · 1 s · AUTO Left an end position with no command, for the delay
noMovement 4 OFF · 2 s · RETRY Still on the end limit it should have left, for the delay (set response to use it)
drive 5 TRIP · 0 · AUTO DriveFault input. A motorised valve also stops driving
(position deviation) 6 MOD / FLOAT only Their deviation (MOD, FLOAT)
(position feedback) 7 MOD / FLOAT only Their posFeedback
(configBad) 8 fault or warning A setting is invalid (see Bad settings)

faultId names the lowest-numbered protection tripped. A RETRY on a travel
timeout repeats the move, which often frees a sticky valve. A timeout set to
WARN keeps the valve where it was sent and warns until it arrives.

HMI commands

Field Type Meaning
cmdMode INT 0 Off · 1 Hand · 2 Auto · 3 OOS (acts when a new value arrives; the block sets it back to −1)
cmdOpen / cmdClose BOOL Hand open / close (close wins when both arrive). MOD / FLOAT: handSp to 100 / 0 %
cmdStop BOOL Hand stop (stop wins): motorised UT_VALVE / 3POS stop driving; MOD / FLOAT stay where they are (handSp = the position now). A stop read TRUE blocks every Hand move in that scan, so one held TRUE keeps the valve stopped
cmdReset BOOL Reset MANUAL protections

The three-position Hand position cmdPos is in UT_VALVE_3POS's record (Pos3), and
the floating valve's cmdHome in UT_VALVE_FLOAT's (Floating).

Every BOOL command acts once, on its rising edge, and is cleared by the block, also by
the valve blocks that don't use it: one held TRUE (a Modbus coil left on, a debugger
force) acts once, and a Hand valve closed by the interlock does not re-open when the
interlock returns with cmdOpen still held.
A command left in the record at power-up does not act. Commands outside Hand (and
Hand commands while interlocked, or not permitted away from safe) are ignored. A master
that rewrites a command every poll goes through UT_CMD.

Status fields

mode, state, isOpen, isClosed, moving, interlocked, position : REAL
(100 open, 0 closed, 50 between; measured / estimated for MOD and FLOAT; −1 = unknown,
FLOAT not homed),
lastOpenStroke / lastCloseStroke : TIME (measured limit-to-limit travel times,
a wear indicator; only with the limit fitted), strokes : UDINT (completed moves,
kept over a power cut as of the last saveEvery), fault, warning, configBad (a setting is
invalid, bit 8: see Bad settings),
faultCode : DWORD, faultId : UT_FAULT, statusCode : UT_STATUS and
statusText : STRING(30) (what it is doing or what holds it back, see
Status; every valve block has its own list). The variants keep their own
status in their own record: targetPos / actualPos (3POS), demand (MOD / FLOAT),
notHomed (FLOAT).

Added for time visibility and "why it stopped" (at the end of the record):

Field Type Meaning
notPermitted BOOL Permissive is FALSE: no move away from the safe position starts
travelElapsed TIME How long the move under way has been driving (0 when not moving). MOD: the ramp under way (a reversal starts a new one)
timeLeft TIME The countdown the status shows: travel left, the reversing pause, a fault's recover / retry wait
stopReason UT_STOP Why the valve last went back to its safe position (below; UT_STOP_NONE = none since power-up), kept until the next time
lastFaultCode DWORD The faultCode bits of the last trip, kept after it clears, until the next trip
lastFault UT_FAULT Its name (the lowest bit), e.g. UT_F_CLOSE_TIMEOUT, kept the same way
trips UDINT Trips since power-up (not kept over a power cut)

Why it went back to safe (stopReason, the common
stop reasons): it is set when the valve stops
being asked away from its safe position, from what held it in that scan, so the
record shows one scan after the move back starts.

stopReason Words (UT_STOP_TEXT) When
UT_STOP_DEMAND_ENDED Auto: demand ended Auto: AutoOpen (AutoPos, AutoSp) went back to the safe position
UT_STOP_OPERATOR Stopped: operator Hand: a close, stop or a move to the safe position
UT_STOP_SWITCHED_OFF Stopped: switched off The mode changed to Off or OOS
UT_STOP_INTERLOCK Stopped: interlock Interlock dropped
UT_STOP_FAULT Stopped: fault A trip (or a bad setting); lastFault says which

How it works

  • Mode (UT_MODE_SELECT): Off → safePosition. Hand → cmdOpen /
    cmdClose / cmdStop and the LocalOpen / LocalClose / LocalStop buttons.
    Auto → follows AutoOpen. OOS → every output off,
    protections suppressed, no fault or warning reported; the position is found again afterwards.
  • Safe position on Off, interlock, or any trip. In Hand an interlock also
    puts the Hand request back to the safe position, so the valve does not move
    by itself when the interlock returns. In Auto it follows AutoOpen again.
  • Permissive FALSE: no move away from the safe position starts (Auto waits, a
    Hand request away from safe is dropped, status UT_ST_NOT_PERMITTED, Not permitted); a move toward
    the safe position is always allowed, and a valve already away stays where it is
    (unlike the interlock, it never forces safe). When it returns, Auto follows
    AutoOpen again; Hand needs a new command.
  • After a MANUAL reset the valve stays in the safe position until it gets a
    new command (AutoOpen changes, or a new Hand command), unless restartAfterReset.
    AUTO / RETRY recovery puts it back where it is asked to be.
  • Moves: a move ends on its limit, or after the travel time when that limit
    isn't fitted. A limit that makes and drops again within the travel time is
    treated as a flicker: the valve carries on (a motorised one keeps driving)
    and only the real arrival counts as one stroke.
  • Motorised: a reversal waits reversalDelay with both outputs off. Hand
    cmdStop stops it mid-travel (State ON, position 50).
  • Power-up: the position comes from the limit switches, no false fault.
    In Hand the valve stays where it is (a spring valve is closed); in Off it goes
    to safePosition; in Auto it follows AutoOpen. With powerUp = UT_PU_OFF
    the mode comes back Off, so the valve goes to its safe position until the
    operator selects a mode again.
  • OpenOut and CloseOut are never on together.

Status

statusCode, faultId and statusText say the one main thing the valve is
doing, or what holds it back, so a technician can see on the HMI why it is not where
it was asked to be. The most important reason wins: configuration > fault > held /
waiting > warning > position > Off. The words hold no numbers: the position is in position. The time left
(travel, a pause, a fault's recover / retry wait) is in timeLeft. The text is
rebuilt only when the status or the fault changes. Where the valve is (the rows
marked (this block)) comes from the block's last scan, so it shows one scan after
it changes. The numbers are in conventions.

statusCode Words When
UT_ST_OFF Off Mode Off (it goes to its safe position)
UT_ST_OPENING Opening (this block) timeLeft is the travel time left when a travel time applies
UT_ST_CLOSING Closing (this block) As opening
UT_ST_OPEN Open (this block) Confirmed open (limit, or the travel time without one)
UT_ST_CLOSED Closed (this block) Confirmed closed
UT_ST_BETWEEN Stopped between positions (this block) Held where it is (a Hand stop on a motorised valve, or safePosition HOLD)
UT_ST_POS_UNKNOWN Position unknown (this block) Not moving and no limit or travel time says where it is
UT_ST_INTERLOCK Blocked: interlock Interlock FALSE: at its safe position (every mode but OOS)
UT_ST_MUST_CYCLE Waiting: command must cycle After a MANUAL reset in Auto: it stays safe until the Auto request changes (unless restartAfterReset)
UT_ST_OOS Out of service
UT_ST_NOT_PERMITTED Not permitted (this block) Permissive FALSE holds back a move away from the safe position
UT_ST_DEAD_TIME Waiting: dead time (this block) Motorised: the pause before driving the other way (timeLeft)
UT_ST_WARNING Warning: <fault> A protection set to WARN is raised
UT_ST_WARN_SETTING Setting: <setting> An invalid setting, a safe value in use (settings below)
UT_ST_FAULT Fault: <fault> Tripped, AUTO: clears by itself once the cause has gone for recover (timeLeft while it counts)
UT_ST_FAULT_RETRY Retrying: <fault> Tripped, RETRY: the protection's retries of maxRetries (timeLeft while it counts)
UT_ST_FAULT_RESET Latched: <fault> Tripped, MANUAL: a reset (pin, cmdReset, Off) once the cause has gone
UT_ST_FAULT_LOCKED Locked: <fault> RETRY used up: now as MANUAL
UT_ST_CONFIG Config: <setting> An invalid setting: every output off until it is fixed

<fault> is faultId, one of: UT_F_OPEN_TIMEOUT (open timeout) · UT_F_CLOSE_TIMEOUT (close timeout) · UT_F_BOTH_LIMITS (both limits) · UT_F_POS_LOST (position lost) · UT_F_NO_MOVEMENT (did not move) · UT_F_ACTUATOR (actuator fault).
<setting> with UT_ST_WARN_SETTING is one of: UT_F_SAVE_EVERY (save every) · UT_F_RETRY_WINDOW (retry window) · UT_F_MODE_SOURCE (mode source) · UT_F_SAFE_POSITION (safe position); with UT_ST_CONFIG one of: UT_F_VALVE_TYPE (valve type) · UT_F_TRAVEL_TIME (open / close time) · UT_F_REVERSAL_DELAY (reversal delay) · UT_F_PULSE_TIME (pulse time, must be above 0).

Using it

V1(AutoOpen := FillValveCmd, OpenLs := V1_Open, ClosedLs := V1_Closed,
   Interlock := NOT TankHigh, Data := Valve1);
V1_Solenoid := V1.OpenOut;

Bad settings

A setting that is not a number, negative or unknown never drives the valve somewhere
it could do damage. configBad is set and faultCode bit 8, and faultId names the
setting (the lowest priority). A negative saveEvery keeps nothing; a negative retryWindow
uses the default 1 h; an unknown modeSource uses the HMI (warnings).

  • Refused (a fault, every output off): an unknown valveType; a negative openTime,
    closeTime or reversalDelay; a bistable pulseTime of 0 or less. It drives again
    once the setting is valid.
  • Warning (a safe value is used): an unknown safePosition (closed).
  • An unknown enum value can only come from a raw HMI write.