UT_VALVE_FLOAT — Floating (3-point) valve or damper

UT_VALVE_FLOAT — Floating (3-point) valve or damper

Positions an actuator that only has raise and lower contacts (no positioner),
common on HVAC mixing valves, irrigation and motorised dampers. It estimates the
position from the run time. Position feedback is used if fitted, and the estimate
re-syncs at the ends. Mode, fail action and protections work as
UT_VALVE (UT_VALVE_CORE).

Pins

Pin Type Default What to wire
in AutoSp REAL 0.0 Position request in Auto, %. NaN / infinite is ignored
in PosFb REAL -1.0 Position feedback % (exactly −1 = not fitted, estimate used)
in OpenLs / ClosedLs BOOL FALSE Optional end switches (exact re-sync, the move stops on them)
in Interlock BOOL TRUE FALSE → failPosition
in DriveFault, SwHand, SwAuto, Reset As UT_VALVE
in Permissive BOOL TRUE FALSE: the valve moves only toward failPosition (a move away from it waits; a Hand one is dropped); it never forces it
in LocalOpen / LocalClose / LocalStop BOOL FALSE Local pushbuttons (Hand, rising edge): handSp 100 %, 0 %, or stop where it is (held: keeps stopping)
out Raise BOOL Open/raise contact
out Lower BOOL Close/lower contact (never with Raise)
out Position REAL Measured or estimated %; −1 = unknown (not homed, no feedback)
out Fault BOOL A trip is holding it at the fail action
out State UT_STATE OFF closed, ON open, STARTING raising, STOPPING lowering, INVALID stopped with the position unknown
inout Data UT_VALVE_DATA Shared valve record (UT_VALVE)
inout Floating UT_VALVE_FLOAT_DATA The floating settings, protections, command and status (below)

Record UT_VALVE_FLOAT_DATA (pin Floating)

Field Type Default Meaning
strokeTime TIME T#60s Full stroke time (from the actuator data plate)
minPulse TIME T#500ms Shortest move: a smaller correction is not made, and a move lasts at least this (except Off, an interlock or a trip: a move away from the fail position stops at once)
deadband REAL 1.0 % error ignored (never less than the travel in one scan, so it can't hunt)
overTravel TIME T#5s Extra drive at 0 %/100 % to re-sync the estimate
homeOnStart BOOL TRUE Drive closed at power-up (a full stroke and the over-travel) to sync, in Off and Auto. In Hand it stays put (position unknown) until Auto or cmdHome
failPosition REAL 0.0 Position on interlock / fault / Off (−1, any value below 0 or not a number = stay where it is)
openThreshold / closedThreshold REAL 98.0 / 2.0 isOpen / isClosed, OFF state; with feedback, the end of an end move
handSp REAL 0.0 Hand position; tracks the Auto request. Hand cmdOpen / cmdClose (in Data) set it to 100 / 0 %, cmdStop to the position now
deviation UT_LEVEL WARN · 10 s · AUTO · sp 5 With feedback: stopped more than sp % from the request (faultCode bit 6)
posFeedback UT_PROTECTION TRIP · 500 ms · AUTO Feedback NaN, infinite or outside −5…105 % (falls back to the estimate; faultCode bit 7)
cmdHome BOOL FALSE HMI: home now (any mode but OOS; not with good feedback). Cleared by the block
notHomed BOOL Status: not homed and no feedback: the position is unknown (Position −1)
demand REAL Status: the position asked for, %

In the valve record Data: reversalDelay (T#500ms, the pause before changing
direction), position, the modes, the other protections, the HMI commands and the
status.

How it works

  • The estimate adds or takes away 100 % × run time / strokeTime while Raise /
    Lower are on. Good feedback replaces it; an end switch sets it to 0 / 100 %.
  • A request of 0 % (or 100 %) drives to the end and on for overTravel, then
    stops and doesn't drive again until the request leaves the end.
  • A move never lasts longer than strokeTime + overTravel. If it runs out of
    time (stuck, or a move to 0 % / 100 % whose end never comes, e.g. frozen
    feedback), it isn't repeated until the request changes; with feedback the
    deviation warning shows it.
  • Power-up: with homeOnStart it homes first in Off and Auto. In Hand it does
    not move: Position is −1, notHomed TRUE, State INVALID, and a new handSp is
    not acted on, until it goes to Auto (it homes, then follows AutoSp), Off or an
    interlock (it homes on the way to the fail position), or the operator sends
    cmdHome (it homes and stays closed, handSp 0). With feedback it starts where
    the feedback says (in Hand it stays there). Without either, in Hand it does not
    move until the operator changes handSp.
  • cmdHome at any time re-homes it (a full stroke and the over-travel, then on to
    the request), with the reversal pause if it was raising.
  • travelElapsed is how long the move under way has driven; timeLeft its time
    left at the stroke speed (a homing move: the full stroke and over-travel left).
  • cmdHome acts once, on its rising edge: one held TRUE homes once.
  • OOS and a drive trip: both contacts off.

Status

statusCode, faultId and statusText say the one main thing the valve is
doing, or what holds it back, so a technician can see on the HMI why it is not where
it was asked to be. The most important reason wins: configuration > fault > held /
waiting > warning > position > Off. The words hold no numbers: the target is in demand and the position in position. The time left
(travel, a pause, a fault's recover / retry wait) is in timeLeft. The text is
rebuilt only when the status or the fault changes. Where the valve is (the rows
marked (this block)) comes from the block's last scan, so it shows one scan after
it changes. The numbers are in conventions.

statusCode Words When
UT_ST_OFF Off Mode Off (it goes to its safe position)
UT_ST_OPEN Open (this block) At or above openThreshold
UT_ST_CLOSED Closed (this block) At or below closedThreshold
UT_ST_MOVING Moving (this block) Going to demand; timeLeft is the move's time left at the stroke speed
UT_ST_HOMING Homing (this block) Driving closed for a full stroke and the over-travel to find its position
UT_ST_AT_POSITION At position (this block) Between the thresholds, at demand
UT_ST_POS_UNKNOWN Position unknown (this block) Not homed and no feedback
UT_ST_INTERLOCK Blocked: interlock Interlock FALSE: at its safe position (every mode but OOS)
UT_ST_OOS Out of service
UT_ST_NOT_PERMITTED Not permitted (this block) Permissive FALSE holds back a move away from the safe position
UT_ST_DEAD_TIME Waiting: dead time (this block) The pause before driving the other way (timeLeft)
UT_ST_NOT_HOMED Hand: not homed (this block) Hand and the position is unknown (not homed, no feedback): it stays put until cmdHome or Auto
UT_ST_MOVE_TIMEOUT Waiting: new request (this block) A move ran for a full stroke and the over-travel without getting there (stuck, or frozen feedback): it waits for a new request
UT_ST_WARNING Warning: <fault> A protection set to WARN is raised
UT_ST_WARN_SETTING Setting: <setting> An invalid setting, a safe value in use (settings below)
UT_ST_FAULT Fault: <fault> Tripped, AUTO: clears by itself once the cause has gone for recover (timeLeft while it counts)
UT_ST_FAULT_RETRY Retrying: <fault> Tripped, RETRY: the protection's retries of maxRetries (timeLeft while it counts)
UT_ST_FAULT_RESET Latched: <fault> Tripped, MANUAL: a reset (pin, cmdReset, Off) once the cause has gone
UT_ST_FAULT_LOCKED Locked: <fault> RETRY used up: now as MANUAL
UT_ST_CONFIG Config: <setting> An invalid setting: every output off until it is fixed

<fault> is faultId, one of: UT_F_BOTH_LIMITS (both limits) · UT_F_ACTUATOR (actuator fault) · UT_F_POS_DEVIATION (pos. deviation) · UT_F_POS_FEEDBACK (position signal).
<setting> with UT_ST_WARN_SETTING is one of: UT_F_SAVE_EVERY (save every) · UT_F_RETRY_WINDOW (retry window) · UT_F_MODE_SOURCE (mode source) · UT_F_DEADBAND (deadband) · UT_F_FAIL_POSITION (fail position) · UT_F_OPEN_THRESHOLD (open/closed limit); with UT_ST_CONFIG one of: UT_F_STROKE_TIME (stroke time, must be above 0) · UT_F_MIN_PULSE (min pulse/overtravel) · UT_F_REVERSAL_DELAY (reversal delay).

Bad settings

A setting that is not a number, negative or unknown never drives the valve somewhere
it could do damage. configBad is set and faultCode bit 8, and faultId names the
setting (the lowest priority). A negative saveEvery keeps nothing; a negative retryWindow
uses the default 1 h; an unknown modeSource uses the HMI (warnings).

  • Refused (a fault, both contacts off): strokeTime 0 or less; a negative minPulse,
    overTravel or reversalDelay.
  • Warning: deadband negative or not a number (the one-scan travel is used);
    failPosition not a number (stay) or above 100; thresholds not a number (98 / 2).