UT_SPEED_CTRL — Constant pressure / flow / level with a speed drive

UT_SPEED_CTRL — Constant pressure / flow / level with a speed drive

Holds a pressure, flow, level or temperature at a setpoint by varying a drive's
speed. Typical uses: irrigation and stock-water pumps on a VSD, booster sets,
constant-pressure town supply, borehole pumps, duct-pressure fans, cooling-tower fans.

It has the full set of field features: pipe fill (fill the mains gently before
regulating, which stops water hammer), sleep / wake (stop when demand stops and
restart on a pressure drop), a flow limit, and guard rails against a badly
tuned or failing loop
: hunting detection with a fallback speed, a burst-pipe /
lost-prime check, an overpressure override, sensor-failure handling and output
rate limiting.

The control loop is inside the block, because pipe fill, sleep, overrides and
the fallback have to take the output away from the loop and hand it back without a
bump. If you'd rather use OpenPLC's PID, set loop := UT_LOOP_EXTERNAL; the block
then takes the speed from ExtSpeed (wire Data.spActive to the PID's setpoint) and
still applies every phase, limit and protection around it.

What the speed follows is a setting, control: the PID on Pv (pressure or level,
the default), the PID on the Flow pin, or a fixed speed. Each has three presets,
NORMAL, LOW and HIGH, chosen with preset by the operator, the HMI, SCADA or your
logic. For example a travelling irrigator working near the sump needs only a low
pressure: switch preset to LOW and the pump holds spLow instead of sp.

An operator can run the pump at a manual speed (cmdManual, manualSpeed) without
losing the overpressure and burst protections, which a drive's own Hand would bypass.

Chain: UT_SPEED_CTRL.Run → UT_PUMP.Demand; UT_PUMP.RunCmd → UT_MOTOR_VSD.AutoCmd;
UT_SPEED_CTRL.Speed → UT_MOTOR_VSD.AutoSpeed; UT_MOTOR_VSD.Running → Running.

Pins

Pin Type Default What to wire
in Enable BOOL FALSE Control wanted (a schedule, UT_ZONE_SEQ.PumpDemand, a switch)
in Pv REAL 0.0 The pressure or level, e.g. UT_ANALOG_IN.Value. Controlled with control PV; highPv always watches it, whatever control is
in PvGood BOOL TRUE Pressure / level sensor healthy (UT_ANALOG_IN.Good)
in Sp REAL 0.0 PV control: the setpoint when spSource := UT_SP_PIN (e.g. per-zone pressure from UT_ZONE_SEQ); it overrides sp, spLow and spHigh
in Running BOOL TRUE Drive running (UT_MOTOR_VSD.Running). Unwired: assumed running when asked
in Flow REAL 0.0 Flow: controlled with control FLOW; also for the flow limit and low-flow sleep (optional otherwise)
in ExtSpeed REAL 0.0 Speed % from an external PID (loop := UT_LOOP_EXTERNAL)
in Reset BOOL FALSE Rising edge: reset MANUAL protections
in MoreAvailable BOOL FALSE A group block can still add a pump (UT_PUMP_CASCADE wires it): lowPvAtMax waits until it cannot. Unwired: no change
out Run BOOL Pump wanted (→ UT_PUMP.Demand or UT_MOTOR_VSD.AutoCmd)
out Speed REAL Speed request % (→ UT_MOTOR_VSD.AutoSpeed); 0 when not running
out Phase UT_SC_PHASE UT_SC_IDLE, UT_SC_FILLING, UT_SC_CONTROL, UT_SC_BOOST, UT_SC_SLEEP, UT_SC_FALLBACK, UT_SC_MANUAL
out AtSetpoint BOOL The value under control (pv) within atSpBand (CONTROL, BOOST or SLEEP)
out MoreNeeded BOOL At max speed and still short of the band for stageDelay: one more pump
out LessNeeded BOOL At min speed for stageDelay: one less pump
out Fault BOOL A trip is in effect (the pump is stopped, or held at the fallback speed)
out Warning BOOL A warning, a failed sensor with FALLBACK / HOLD, or invalid settings
inout Data UT_SPEED_CTRL_DATA The controller's settings and status (below)

Record UT_SPEED_CTRL_DATA

What the speed follows, and the presets

Field Type Default Meaning
control UT_SC_CTRL UT_SC_CTRL_PV UT_SC_CTRL_PV (0): the PID holds Pv (pressure or level) at the setpoint. UT_SC_CTRL_FLOW: the PID holds the Flow pin at the flow setpoint. UT_SC_CTRL_FIXED: a fixed speed, no PID. See Control
preset UT_SC_PRESET UT_PRESET_NORMAL Which setpoint or fixed speed is used: UT_PRESET_NORMAL (0), UT_PRESET_LOW or UT_PRESET_HIGH. Set by the operator, the HMI, SCADA or your logic
sp REAL 0.0 PV: the NORMAL setpoint (e.g. bar). Must be set. 0 (or not a number) with Enable gives a configBad warning and no run
spLow / spHigh REAL 0.0 / 0.0 PV: the LOW and HIGH setpoints. 0 = sp is used
flowSp REAL 0.0 FLOW: the NORMAL flow setpoint, in the units of Flow. Must be set for FLOW: 0 (or not a number) with Enable gives configBad and no run
flowSpLow / flowSpHigh REAL 0.0 / 0.0 FLOW: the LOW and HIGH flow setpoints. 0 = flowSp is used
fixedSpeed REAL 100.0 FIXED: the NORMAL speed, % (e.g. run)
fixedSpeedLow REAL 50.0 FIXED: the LOW speed, % (e.g. a slow run at low level)
fixedSpeedHigh REAL 100.0 FIXED: the HIGH speed, % (e.g. priming)

Setpoint and loop

Field Type Default Meaning
spSource UT_SP_SOURCE UT_SP_RECORD PV control: UT_SP_RECORD (0) uses sp / spLow / spHigh by preset; UT_SP_PIN uses the Sp pin, whatever the preset
spRamp REAL 0.0 Setpoint change rate, units per rateUnit (0 = step)
reverseActing BOOL FALSE FALSE: below setpoint → speed up (pressure, flow). TRUE: above setpoint → speed up (emptying a tank, cooling). The pipe fill is skipped
loop UT_LOOP UT_LOOP_INTERNAL UT_LOOP_INTERNAL (0) or UT_LOOP_EXTERNAL
kp REAL 5.0 % speed per unit of error (negative: configBad)
ti TIME T#5s Integral time (0 = no integral)
td TIME T#0s Derivative time (usually 0 for pumps)
deadband REAL 0.0 Error ignored inside this
minSpeed / maxSpeed REAL 30.0 / 100.0 % (minimum keeps the pump above its shut-off head and cooled). min > max: configBad
startSpeed REAL 40.0 Speed on start, held until Running; the loop carries on from it
rateLimit REAL 5.0 Max output change, % per rateUnit (0 = none). Limits the damage a bad tune can do
rateUnit UT_RATE_UNIT UT_PER_SEC Time unit of every rate in the record, rateLimit, spRamp and pipeFill.rate: UT_PER_SEC (0, per second) or UT_PER_MIN (per minute); UT_PER_HOUR and UT_PER_DAY work too. Example: rateLimit := 300.0, rateUnit := UT_PER_MIN is the same as the default 5 %/s
atSpBand REAL 0.2 ± band for AtSetpoint, sleep, staging and notReaching

Pipe fill pipeFill : UT_SC_FILL_DATA

Field Type Default Meaning
mode UT_FILL_MODE UT_FILL_OFF UT_FILL_OFF · UT_FILL_FIXED runs at speed · UT_FILL_RAMP ramps the setpoint from Pv to sp at rate under the loop
speed REAL 50.0 FIXED: fill speed, %
target REAL 0.0 The fill is complete when Pv reaches this (0 = 90 % of sp); RAMP also waits for the ramp to finish
rate REAL 0.1 RAMP: setpoint rise, units per rateUnit (of the main record: per second by default)
timeout UT_PROTECTION TRIP · 10 min · RETRY (2) The fill never completes (burst main, open valve). Each retry fills again

The fill runs every time the pump starts from IDLE (Enable, or a restart after a
trip), not after a sleep. Leaving FALLBACK or MANUAL, a run whose line is not full
yet (no fill completed, and Pv never at the fill target since the start) fills
first, so a sensor that was bad at the start, or dipped during the fill, does not
skip it.

Sleep / wake sleep : UT_SC_SLEEP_DATA

Field Type Default Meaning
enable BOOL FALSE Sleep when the demand has gone. Switching it off wakes the pump
speed REAL 35.0 At or below this speed ...
flow REAL 0.0 ... or Flow below this (0 = not used) ...
delay TIME T#30s ... with Pv not below the band, for this long: boost, then sleep
boost REAL 5.0 % of sp added before sleeping (tops up the tank / accumulator). 0: sleep straight away
boostTime TIME T#10s How long the boost lasts. If Pv falls wakeDrop below sp during it, the boost is dropped and the pump carries on
wakeDrop REAL 0.3 Wake when Pv is this far below sp (above it, reverse acting) ... Not a number, infinite or negative: a setting warning and 0 is used, so the pump always wakes (as soon as Pv is below sp)
wakeDelay TIME T#2s ... for this long ...
minSleep TIME T#30s ... and the pump has slept at least this long

Limits and overrides (independent of the loop)

Field Bit Type Default Meaning
flowLimit REAL 0.0 Speed is reduced to hold Flow at this (end-of-curve / sprinkler blow-out protection). The cap moves at up to rateLimit (per rateUnit; 5 %/s if 0), in proportion to the excess, full rate at 20 % over. The loop's integral is pulled down with it. 0 = off
highPv 2 UT_LEVEL TRIP · AUTO · sp 0 Overpressure (sp 0 = off). WARN: speed straight to minSpeed while high. TRIP: the pump stops; it restarts (with the fill) when the trip clears
lowPvAtMax 3 UT_LEVEL TRIP · 60 s · RETRY (3, recover 5 min) · sp 0 On by default. It waits while MoreAvailable (a group can still add a pump). At the top speed allowed (max, or the flow limit) with Pv still low in CONTROL / BOOST: a sensor stuck low, a burst pipe, lost prime, a worn pump. sp 0 = below half the setpoint in use (direct acting only); set sp for a fixed level (it then applies reverse acting too). response := UT_RESP_OFF turns it off. With a long main and no pipe fill, set pipeFill or a longer delay
pipeFill.timeout 4 UT_PROTECTION see above
notReaching 5 UT_PROTECTION WARN · 2 min · AUTO Pv outside atSpBand that long in CONTROL while not at a speed limit (undersized or badly tuned)
hunting 6 UT_PROTECTION WARN · AUTO The loop oscillates (below). TRIP = run at fallbackSpeed (phase FALLBACK) until it clears
huntCycles / huntWindow / huntBand INT / TIME / REAL 6 / T#60s / 0.3 Hunting = huntCount above huntCycles (1..15): Pv crossing sp more than that many times in about one huntWindow, each swing over huntBand peak to peak (a crossing counts once Pv is huntBand/2 past sp the other way). huntWindow 0 = off. See Hunting
pvFail 1 UT_PVFAIL UT_PVFAIL_STOP Sensor bad (PvGood FALSE, Pv NaN or infinite): UT_PVFAIL_STOP (0, fault, pump stops), UT_PVFAIL_FALLBACK (warning, run at fallbackSpeed), UT_PVFAIL_HOLD (warning, hold the last speed; a sleeping pump stays asleep)
pvRecover TIME T#5s The sensor must be good this long before control resumes
fallbackSpeed REAL 60.0 Used on sensor failure or a hunting trip
stageDelay TIME T#30s For MoreNeeded / LessNeeded
retryWindow TIME T#1h RETRY counts
restartAfterReset BOOL FALSE After a MANUAL reset of a stopped controller, restart without Enable cycling
manualSpeed REAL 50.0 Manual: the speed the operator sets, % (held inside minSpeed..maxSpeed and the flow limit). Not a number or outside 0..100: minSpeed and a setting warning (bit 7)

Bit 0 of faultCode is configBad (no run). Bit 7 is a setting that is invalid but
has a safe fallback (a warning; it runs). faultId names the most important one:
UT_F_OVERPRESSURE, UT_F_SENSOR_BAD, UT_F_LOW_AT_MAX (burst), UT_F_PIPE_FILL,
UT_F_HUNTING, UT_F_NOT_REACHING, then the setting (bit 0: the setting named, below;
bit 7: UT_F_SETTING).

Invalid settings

  • No run (configBad, bit 0, a warning while Enable): an unknown control; with
    PV or FLOW, the setpoint in use (by preset and spSource) 0, not a number or
    infinite (so FLOW needs flowSp); kp negative or not a number; minSpeed / maxSpeed not a number,
    min < 0, max ≤ 0 or min > max; startSpeed or fallbackSpeed not a number;
    rateLimit negative or not a number; an unknown rateUnit.
  • Warning, safe value used (bit 7, Warning): sleep.wakeDrop not a number,
    infinite or negative → 0; atSpBand → 0; deadband → 0; spRamp → 0 (a step);
    td negative → 0; sleep.boost outside 0..100 → no boost; an unknown pvFail →
    STOP (the safe side). Warned only (the block already acts safely): an unknown
    spSource (record sp), loop (internal) or pipeFill.mode; ti negative (no
    integral); startSpeed / fallbackSpeed outside min..max (clamped); manualSpeed, or
    the fixed speed in use, not a number or outside 0..100 (minSpeed used); pipeFill.speed
    or sleep.speed outside 0..100; pipeFill.target, pipeFill.rate, sleep.flow,
    flowLimit, huntBand negative or not a number; huntCycles outside 1..15; a
    negative huntWindow, pvRecover, stageDelay or sleep time; a protection with a
    bad time or setpoint.

HMI

Field Type Meaning
cmdReset BOOL Reset MANUAL protections (acts once, cleared by the block)
cmdManual BOOL Run at manualSpeed instead of the loop (phase MANUAL), until cmdAuto
cmdAuto BOOL Back to the loop, bumpless (it carries on from the manual speed). With cmdManual in the same scan, cmdAuto wins

Each command acts once, on its rising edge, and is cleared by the block.

Manual speed (phase UT_SC_MANUAL, manual TRUE): the pump runs at manualSpeed,
reached at the rateLimit. Enable still starts and stops it (manual stays selected
while it is off), and these still act: the overpressure override and trip (highPv),
lowPvAtMax at the top speed (burst / lost prime), the flow limit, the rate limit and
a failed sensor with pvFail STOP (the overpressure check needs the sensor). No pipe
fill, sleep, hunting or notReaching in manual; MoreNeeded / LessNeeded stay
FALSE. Manual is not kept over a power cut: the loop is back in control.

Status fields

spActive (setpoint in use: ramped, fill ramp or boost), pv (the value under control
now: Pv, or Flow with FLOW control), error (in the acting direction), pTerm, iTerm, dTerm, speed, phase, huntCount (crossings in
about the last huntWindow, see Hunting), sleeping, flowLimiting,
pvBad, configBad (no run), fault, warning, faultCode : DWORD,
faultId : UT_FAULT, statusCode : UT_STATUS and statusText : STRING(30) (what the
loop is doing or what holds it back, below), and (at the end of the record):

Field Type Meaning
manual BOOL Manual speed selected
timeLeft TIME The countdown in progress: the fill timeout (FILLING), the boost (BOOST), minSleep then the wake delay (SLEEP), the sleep delay, MoreNeeded / LessNeeded's stageDelay while running under the loop, or the recover / retry wait of the tripped protection shown. 0 = none
phaseTime TIME Time in the current phase (the sleep time while asleep, the fill time while filling)
stopReason UT_STOP Why the pump last stopped (Run dropped): UT_STOP_DEMAND_ENDED (Enable off), UT_STOP_FAULT (a trip or a failed sensor with STOP), UT_STOP_SETTING (configBad), UT_STOP_ASLEEP (Asleep: demand met). UT_STOP_NONE = none since power-up. The words are UT_STOP_TEXT's
lastFaultCode DWORD The trip bits (1 sensor, 2 overpressure, 3 low at max, 4 fill, 5 not reaching, 6 hunting) of the last trip, kept after it clears
lastFault UT_FAULT Its name, e.g. UT_F_OVERPRESSURE
trips UDINT Trips since power-up

Status

statusCode, faultId and statusText say the one main thing the loop is
doing, or what holds it back. The most important reason wins: configuration > fault >
held / waiting > warning > running > idle. Enabled and not running, or running with
no drive feedback, it always shows a held, fault or configuration status. The words
hold no numbers: the setpoint in use is spActive, the speed speed, and the time
left timeLeft. The text is rebuilt only when the status or the fault changes. The
numbers are in conventions.

statusCode Words When
UT_ST_IDLE_NOT_ENABLED Idle: not enabled Enable FALSE
UT_ST_HOLDING Running: holding setpoint CONTROL: holding spActive at speed
UT_ST_PIPE_FILL Pipe fill FILLING, up to the fill target (timeLeft: the fill timeout)
UT_ST_BOOST Boost before sleep BOOST (timeLeft: the boost time left)
UT_ST_MAX_SPEED Max speed, below setpoint CONTROL at the top speed, Pv still short by more than atSpBand
UT_ST_FLOW_LIMIT Running: flow limit The flow limit holds the speed down
UT_ST_FALLBACK Running: fallback speed FALLBACK for any other reason
UT_ST_MANUAL_SPEED Running: manual speed MANUAL: the operator's speed
UT_ST_FIXED_SPEED Running: fixed speed control FIXED: running at the preset's fixed speed
UT_ST_ENABLE_CYCLE Waiting: Enable must cycle After a MANUAL reset of a stopped loop (unless restartAfterReset)
UT_ST_DRIVE_NOT_RUNNING Waiting: drive not running Run given, Running FALSE
UT_ST_SLEEPING Sleeping SLEEP; it wakes when Pv passes sp ∓ wakeDrop (timeLeft: minSleep, then the wake delay)
UT_ST_WARNING Warning: sensor bad The sensor failed with pvFail FALLBACK or HOLD (it runs), or in manual
UT_ST_WARNING Warning: <protection> A protection set to WARN, e.g. Warning: overpressure (speed at minimum)
UT_ST_WARN_SETTING Setting: a setting Bit 7: a setting is invalid, a safe value is used
UT_ST_FAULT Fault: <protection> A trip with AUTO reset, e.g. Fault: overpressure (timeLeft while the recover time counts)
UT_ST_FAULT_RETRY Retrying: <protection> A RETRY trip (the protection's retries of maxRetries, timeLeft)
UT_ST_FAULT_RESET Latched: <protection> A MANUAL trip
UT_ST_FAULT_LOCKED Locked: <protection> A RETRY trip past maxRetries
UT_ST_FAULT Fault: sensor bad The sensor failed with pvFail STOP: the pump stops
UT_ST_CONFIG Config: <setting> No run until fixed: UT_F_SETTING (an unknown control), UT_F_SETPOINT (the setpoint in use 0 or not a number: sp, spLow, spHigh, the Sp pin, or flowSp …), UT_F_KP (kp), UT_F_MIN_MAX_SPEED (min / max speed), UT_F_RATE_LIMIT (rate limit), UT_F_RATE_UNIT (rate unit), UT_F_START_SPEED (start/fallback speed)

<protection> is faultId, most important first: UT_F_OVERPRESSURE (highPv),
then (after a failed sensor with STOP) UT_F_LOW_AT_MAX (lowPvAtMax, low at max
speed: burst?), UT_F_PIPE_FILL (pipe fill time), UT_F_NOT_REACHING (below
setpoint), UT_F_HUNTING (loop hunting: a hunting trip runs on at the fallback speed
and shows here).

Hunting

A crossing is Pv passing the setpoint in use from more than huntBand/2 on one side to
more than huntBand/2 on the other. The block counts crossings in the huntWindow
under way, and starts a new window each time one has passed. huntCount is the
crossings of the window under way plus the last whole window's share of the time
still to go: just after a new window starts it is close to the last window's count,
and that part fades out as the new window runs. It drops to 0 once there has been no
crossing for a whole huntWindow. The hunting protection is raised while
huntCount is above huntCycles.

Control: PV, FLOW or FIXED, and the presets

control The speed follows Setpoint or speed by preset (NORMAL / LOW / HIGH)
UT_SC_CTRL_PV (default) The PID on Pv: a pressure or a level sp / spLow / spHigh (0 = sp); the Sp pin instead with spSource := UT_SP_PIN
UT_SC_CTRL_FLOW The PID on the Flow pin flowSp / flowSpLow / flowSpHigh (0 = flowSp)
UT_SC_CTRL_FIXED A fixed speed, no PID fixedSpeed / fixedSpeedLow / fixedSpeedHigh (100 / 50 / 100 %)
  • preset can change at any time; the new setpoint is reached at spRamp (a step
    when 0), and a new fixed speed at rateLimit.
  • FLOW: the flow is the value under control (pv, spActive, AtSetpoint,
    notReaching, hunting, the pipe-fill target and lowPvAtMax work on it), and a
    failed flow signal (not a number) is the sensor failure (pvFail). highPv still
    watches the Pv pin, so wire the pressure there to keep the overpressure
    protection.
  • FIXED: the PID is not used. The pump runs at the preset's fixed speed (phase
    UT_SC_MANUAL, status UT_ST_FIXED_SPEED), held inside minSpeed..maxSpeed and
    reached at rateLimit. PvGood FALSE does not stop it. highPv still watches
    Pv, and the other protections act as with the manual speed: lowPvAtMax at the
    top speed, the flow limit, the rate limit; a Pv that is not a number still counts
    as a failed sensor (pvFail). No fill, sleep, hunting or notReaching. The
    operator's manual speed (cmdManual, manualSpeed) wins over the fixed speed
    until cmdAuto.

On the HMI

Every PID value is in the record, for a tuning or overview screen: the settings
kp, ti, td, deadband, minSpeed, maxSpeed, rateLimit and rateUnit (the
ramp), control and preset; and the status spActive, pv, speed, error,
pTerm, iTerm, dTerm and phase.

The speed goes to the drive through UT_MOTOR_VSD: Speed to its
AutoSpeed, and its SpeedRef (%) or SpeedRefRaw (raw) to the analog output, or
through UT_IO_MAP_OUT. The drive's run, fault and ready relays are
UT_MOTOR_VSD's Feedback, DriveFault and DriveReady.

How it works

  1. Enable → Run with Speed = startSpeed, held there until Running. With the
    fill on, the fill phase runs until Pv reaches the fill target (or times out).
  2. The loop is the standard PID form (as the IEC / CODESYS PID):
    Speed = kp · (e + 1/ti · ∫e dt + td · de/dt), e = sp − Pv (Pv − sp reverse acting).
    It takes over bumplessly: the integral is loaded so it carries on from the speed
    it is given (after the start, the fill, an override or the fallback). The output is
    clamped to min/max and rate-limited. Anti-windup: the integral never integrates
    past the output limits, and stops while the output is held by a limit or by the
    rate limit.
  3. Overrides act outside the loop: overpressure → min speed or stop; flow limit →
    speed capped. Each takes priority, and the loop follows without winding up.
  4. Sleep when the demand has gone (boost, then stop); wake on a pressure drop. Hunting,
    a failed sensor or lost pressure at max speed trigger the protections above.
  5. A trip that stops the pump goes to IDLE; it restarts (with the fill) when the trip
    clears by itself (AUTO / RETRY). After a MANUAL reset, Enable must go FALSE and
    back (unless restartAfterReset), like every device in the library.

Time comes from TIME() in whole milliseconds (the rest carried to the next scan),
so the loop, the ramps and every delay behave the same at any task interval.

For block builders: UT_SPEED_CTRL_RUN

The loop is also a function, UT_SPEED_CTRL_RUN, which UT_SPEED_CTRL and
UT_PUMP_CASCADE run inside. A function has no instance of its
own, so the record is not copied: the block that owns the loop keeps its working state
in a UT_SPEED_CTRL_ST and passes it with the record every scan.

Pin Type Default What to wire
in Enable, Pv, PvGood, Sp, Running, Flow, ExtSpeed, Reset, MoreAvailable As the block's pins above (same defaults)
inout Data UT_SPEED_CTRL_DATA The loop's record
inout St UT_SPEED_CTRL_ST The loop's working state. Its Run, Speed, Phase, AtSetpoint, MoreNeeded, LessNeeded, Fault and Warning are the block's outputs. Not for HMIs
returns BOOL Run