UT_MOTOR_VSD — Variable speed drive

UT_MOTOR_VSD — Variable speed drive

Runs a VSD/VFD over hard-wired I/O (run, running, ready and fault relays, speed
reference and feedback). It adds speed limits, ramps, a skip band, a hand speed,
speed-deviation supervision and a drive-reset pulse. Modes, interlocks and the
common protections are as UT_MOTOR (it is
UT_MOTOR_CORE and a speed reference).

Pins

Pin Type Default What to wire
in AutoCmd BOOL FALSE Run request (Auto)
in AutoSpeed REAL 100.0 Speed request in Auto, % (e.g. from PID)
in Feedback BOOL FALSE Drive "running" relay
in DriveReady BOOL TRUE Drive "ready" relay: FALSE blocks a start; lost while running, see driveNotReady. Unwired = not used
in DriveFault BOOL FALSE Drive fault relay
in SpeedFb REAL -1.0 Actual speed % (−1 = not wired: deviation check off)
in Thermistor, Current, Interlock, Permissive, SwHand, SwAuto, LocalStart, LocalStop, Reset As UT_MOTOR (TRUE = active; a NC contact through NOT at the pin)
out Run BOOL Drive run command
out SpeedRef REAL Speed reference %, after the clamp, skip band and ramp (0 when stopped)
out SpeedRefRaw UINT SpeedRef scaled to rawMin..rawMax, for %QW
out DriveReset BOOL Pulse to the drive's reset input
out Running, Fault, Warning, Auto, State As UT_MOTOR
out Ready BOOL As UT_MOTOR, and the drive is ready
out AtSpeed BOOL Running at the reference (see below)
inout Data UT_MOTOR_DATA Shared motor record (UT_MOTOR)
inout Vsd UT_MOTOR_VSD_DATA The drive's settings, protections and status (below)

Record UT_MOTOR_VSD_DATA (pin Vsd)

Field Type Default Meaning
minSpeed / maxSpeed REAL 0.0 / 100.0 Clamp, in %. Pumps usually need a minimum (e.g. 30). Held to 0..100 (see Invalid settings)
accelRate / decelRate REAL 0.0 / 0.0 Ramp on the reference, in % per rateUnit (0 = no ramp here, let the drive ramp)
rateUnit UT_RATE_UNIT UT_PER_SEC Time unit of accelRate / decelRate: UT_PER_SEC (0, % per second) or UT_PER_MIN (% per minute); UT_PER_HOUR and UT_PER_DAY work too
skipLow / skipHigh REAL 0.0 / 0.0 Resonance skip band (off while skipHigh ≤ skipLow)
handSpeed REAL 50.0 Speed used in Hand (HMI-adjustable)
rawMin / rawMax REAL 0.0 / 65535.0 SpeedRefRaw at 0 % and 100 % (either way round, e.g. 0 / 27648; each in 0..65535, not equal)
resetPulse TIME T#500ms Length of the DriveReset pulse (0 = one scan)
ratedHz / ratedRpm REAL 0.0 / 0.0 The motor's frequency and speed at 100 % (nameplate, e.g. 50 Hz, 1460 rpm), for speedHz / speedRpm. 0 = not worked out; negative, NaN or infinite: a warning (rated Hz / rpm), not worked out
speedHz / speedRpm (status) REAL The speed in Hz / rpm: from SpeedFb when wired, else the reference (0 when not set up)
speedRef / speedFb (status) REAL The reference and the feedback

The deviation limit and time are the speedDev protection's own sp and delay.

Also used in the motor record Data

Field Type Meaning
isVsd (status) BOOL TRUE, set every scan: a group knows this pump has a speed
grpSpeed (group) REAL Written by a UT_PUMP_CASCADE: the Auto speed while the group owns the record

Protections (bits as UT_MOTOR)

drive is in Data; speedDev and driveNotReady are in Vsd:

Field Bit Default response · delay · reset Raised when
drive 7 TRIP · 0 · AUTO DriveFault is on. A drive that resets itself returns to service
speedDev 8 WARN · 10 s · AUTO · sp 10 % (UT_LEVEL) Feedback more than sp % off the reference for delay, while running and with SpeedFb wired
driveNotReady 10 WARN · 0 · AUTO DriveReady went FALSE while running. OFF ignores it; WARN warns and keeps running; TRIP stops the drive. It stays raised while DriveReady stays FALSE (also after the drive has stopped), and clears recover after it is back

The overload is inside the drive, so there's no Overload pin. The other
protections are UT_MOTOR's.

How it works

  • The reference. Hand → handSpeed, Auto → AutoSpeed, or grpSpeed while a
    group (UT_PUMP_CASCADE) owns the record (grpActive, set by the
    group every scan); a drive no group owns never looks at grpSpeed. Clamped to
    minSpeed..maxSpeed, then kept out of the skip band, then ramped. A start begins
    from minSpeed; when the drive is stopped (Off, interlock, fault…) the reference is 0.
    A request that is not a number (NaN, infinity) keeps the last good one.
  • Skip band. The reference is never inside skipLow..skipHigh (the edges
    themselves are allowed). A request inside the band holds at the edge on the side
    the reference is coming from; a ramp crossing the band jumps over it. If
    minSpeed is inside the band, the drive starts at skipHigh.
  • Ramps use real elapsed time, so they take the same time at any scan rate.
    A lowered maxSpeed takes effect at once. The rate is in % of full speed per
    second, or per minute with rateUnit := UT_PER_MIN: accelRate := 10.0 is
    0 → 100 % in 10 s per second, or in 10 min per minute. To copy a drive's
    "0 to full speed in 20 s" ramp, use 5 %/s (accelRate := 5.0) or
    300 %/min (accelRate := 300.0, rateUnit := UT_PER_MIN).
  • SpeedRefRaw = rawMin + SpeedRef / 100 × (rawMax − rawMin), rounded, held to 0..65535.
  • DriveReady FALSE blocks a start (Ready is FALSE). Lost while running, it
    raises driveNotReady, which by default warns and keeps the drive running; set
    it to TRIP to stop the drive.
  • In simulation (simulate) the drive fault and driveNotReady still act; the
    speed feedback is taken as the reference, so speedDev does not act.
  • DriveReset pulses for resetPulse when a fault is reset (pin, cmdReset,
    or switching to Off), and also when a reset is asked for while DriveFault is
    still on: most drives hold their fault relay until they get the pulse. One reset
    request gives one pulse: a cmdReset held TRUE (or a Reset pin held on) gives
    one pulse and resets once.
  • AtSpeed: with SpeedFb wired, running and within speedDev.sp of the
    reference; without it, running and the ramp has reached its target.

Wiring the drive's relays

The drive has Wire Settings
A "ready" relay and a fault relay DriveReady and DriveFault Defaults: a fault trips; ready lost while running warns (driveNotReady WARN). Set Vsd.driveNotReady.response := UT_RESP_TRIP to stop on it
Only a fault relay (one "healthy/fault" output) It to DriveFault (TRUE = fault; a contact that opens on a fault through NOT). Leave DriveReady unwired None: DriveReady defaults to TRUE and is not used
Only a "ready" relay It to DriveReady; leave DriveFault unwired Set Vsd.driveNotReady.response := UT_RESP_TRIP, so losing it while running stops the drive

Invalid settings

A setting that would run the drive unsafely keeps it off with a fault: Fault,
wrnConfig and faultCode bit 12 "Invalid setting". That is minSpeed above
maxSpeed, minSpeed above 100, maxSpeed below 0, either one not a number, and
rawMin / rawMax not numbers, outside 0..65535 or equal. Fix the setting and the
drive is back in service (in Auto at once; in Hand press start again).

Other invalid settings fall back and warn (Warning, wrnConfig, bit 12), and
the drive runs: minSpeed below 0 (0 is used), maxSpeed above 100 (100),
accelRate / decelRate negative or not a number, or an unknown rateUnit (no
ramp here: the drive's own ramp), a skip band not a number or with skipLow above skipHigh (off),
handSpeed not a number (the last good request), a negative resetPulse (one
scan), ratedHz / ratedRpm negative, NaN or infinite (speedHz / speedRpm 0). The common settings are checked as in UT_MOTOR.

Status

statusCode, faultId and statusText say the one main thing the motor is
doing, or what holds it back, so a technician can see on the HMI why it is not
running without opening the program. A motor asked to run that is not running
always shows a held, fault or configuration status. The most important reason wins:
configuration > fault > held / waiting > warning > running > idle. A warning shows
over "Running" so it is seen. The time that goes with a status is in timeLeft.
The text is rebuilt only when the status or the fault changes. The numbers are in
conventions.

statusCode Words When
UT_ST_OFF Off Mode Off
UT_ST_IDLE Idle Auto with nothing asking it to run
UT_ST_RUN_AUTO Running: Auto
UT_ST_RUN_HAND Running: Hand With handMaxRun: timeLeft is the time left
UT_ST_STARTING Starting Run given, run feedback not yet in
UT_ST_STOPPING Stopping Stopped, run feedback still on
UT_ST_RUN_GROUP Running: group A group (UT_DUTY, UT_PUMP_CASCADE) runs it; grpRank is its place
UT_ST_SKIP_EDGE Running: at skip band edge (this block) The speed asked for is inside the skip band: the reference holds at its edge
UT_ST_RESTART_DELAY Waiting: restart delay Asked to run, restartDelay not over yet (timeLeft counts down)
UT_ST_INTERLOCK Blocked: interlock Interlock FALSE (every mode but OOS)
UT_ST_NOT_PERMITTED Not permitted Permissive FALSE while stopped, in Hand or Auto
UT_ST_HAND_PRESS_START Hand: press start Hand and stopped: no start given, or it was dropped (a stop, a trip, the interlock, not permitted)
UT_ST_WAIT_GROUP Waiting: turn in group A group owns it and does not run it now
UT_ST_HAND_MAX_RUN Hand: max run, press start handMaxRun ended the Hand run
UT_ST_MUST_CYCLE Waiting: command must cycle After a MANUAL reset, or a local stop in Auto: AutoCmd must go off and on
UT_ST_OOS Out of service
UT_ST_DRIVE_NOT_READY Blocked: drive not ready (this block) DriveReady FALSE while stopped, in Hand or Auto (asked to run or not). Lost while running it is the driveNotReady protection: Warning: drive not ready (WARN) or a fault (TRIP)
UT_ST_WARNING Warning: <fault> A protection set to WARN is raised, or Current is NaN or infinite while a current level is in use (UT_F_CURRENT_BAD, current signal)
UT_ST_WARN_SETTING Setting: <setting> An invalid setting, a safe value in use (settings below)
UT_ST_FAULT Fault: <fault> Tripped, AUTO: clears by itself once the cause has gone for recover (timeLeft while it counts)
UT_ST_FAULT_RETRY Retrying: <fault> Tripped, RETRY: the protection's retries of maxRetries (timeLeft while it counts)
UT_ST_FAULT_RESET Latched: <fault> Tripped, MANUAL: a reset (pin, cmdReset, Off) once the cause has gone
UT_ST_FAULT_LOCKED Locked: <fault> RETRY used up: now as MANUAL
UT_ST_CONFIG Config: <setting> An invalid setting keeps the motor off

<fault> is faultId, one of: UT_F_OVERLOAD (overload) · UT_F_MOTOR_HOT (motor
too hot) · UT_F_NO_FEEDBACK (no run feedback) · UT_F_FEEDBACK_LOST (feedback
lost) · UT_F_WELDED (contactor welded) · UT_F_CURRENT_HIGH (current high) ·
UT_F_CURRENT_LOW (current low) · UT_F_DRIVE (drive fault) · UT_F_SPEED_DEV
(speed deviation) · UT_F_CHANGEOVER (changeover) · UT_F_DRIVE_NOT_READY (drive
not ready).
<setting> is one of: UT_F_FLC (full load current) · UT_F_CURRENT_NEEDS_FLC
(current needs FLC) · UT_F_START_MASK (start mask) · UT_F_RESTART_DELAY (restart
delay) · UT_F_HAND_MAX_RUN (hand max run) · a protection's name (its delay,
recover or maxRetries).
This block adds the settings UT_F_MIN_MAX_SPEED (min / max speed) · UT_F_RAW_MIN_MAX (raw min / max) (UT_ST_CONFIG when they keep it off) · UT_F_ACCEL_RATE (accel / decel rate) · UT_F_SKIP_BAND (skip band) · UT_F_HAND_SPEED (hand speed) · UT_F_RESET_PULSE (reset pulse) · UT_F_RATE_UNIT (rate unit) · UT_F_RATED_HZ_RPM (rated Hz / rpm), and uses UT_F_SPEED_DEV and UT_F_DRIVE_NOT_READY for its own protections.
The rows marked (this block) come from its own sequence and show from the scan after it changes.

Using it

P1(AutoCmd := Station.Run1, AutoSpeed := PressurePID.XOUT, Feedback := P1_Running,
   DriveReady := P1_Ready, DriveFault := P1_Fault, SpeedFb := P1_SpeedPct, Data := Pump1Drive,
   Vsd := Pump1Vsd);
P1_RunRelay := P1.Run;
P1_SpeedAO := P1.SpeedRefRaw;
P1_ResetRelay := P1.DriveReset;