UT_MEAS_CHECK — A measurement's four levels (switch, transmitter, both or none)

UT_MEAS_CHECK — A measurement's four levels (switch, transmitter, both or none)

Checks one UT_MEAS
measurement (pressure, flow, suction level…) against its HH, H, L and LL levels,
whatever is fitted on site: a transmitter, a high and/or low switch, both, or
nothing. The building block the pump and controllers use; usable on its own.

Pins

Pin Type Default What to wire
in In REAL 0.0 The transmitter's value (used when sensor is ANALOG or BOTH)
in HighSwitch BOOL FALSE The high switch is signalling, TRUE = high (used when sensor is SWITCH or BOTH). A NC contact: through NOT at the pin
in LowSwitch BOOL FALSE The low switch is signalling, TRUE = low. A flow switch that is TRUE with flow: NOT FlowSwitch at the pin
in Running BOOL FALSE The equipment runs (for onlyWhenRunning)
in Masked BOOL FALSE Start mask or priming in progress (for maskAtStart)
in ResetReq BOOL FALSE Reset request this scan
in RetryWindow TIME T#1h RETRY window
out Trip / Warn BOOL A level set to trip / warn is in effect
out HiHi / Hi / Lo / LoLo BOOL That level is in effect (trip or warning)
out Reset BOOL One scan: a latched level was reset
out BadInput BOOL A fitted transmitter reads NaN or infinity (the levels hold)
out BadSetting BOOL Installed, and a level in use has an invalid sp, deadband or time (UT_LEVEL_CHECK)
inout Meas UT_MEAS Settings and status

How it works

  • Nothing is checked unless installed.
  • A transmitter is checked against the four UT_LEVEL setpoints.
  • The high switch raises the level highSwitch names (UT_LVL_HIHI, UT_LVL_HI, or
    UT_LVL_NONE = not fitted); the low switch the level lowSwitch names. The switch
    pins are TRUE = signalling; there is no NC setting: wire a NC contact through NOT.
  • BOTH: either the switch or the transmitter raises the level, so the switch backs up
    the transmitter. Each level has one delay, one reset and one count either way.
  • onlyWhenRunning: checked only while Running. maskAtStart: the low levels are
    ignored while Masked.
  • Each level's status fields stay up to date in the record, including timeLeft
    (Meas.lo.timeLeft: its delay, or its recover / retry wait, still to go).

For block builders: UT_MEAS_RUN

The same logic as a function, UT_MEAS_RUN, which the pump and controller blocks
use inside (see UT_PROT_RUN). The
owning block keeps the measurement's working state in a UT_MEAS_ST (one
UT_PROT_ST per level) and passes it with the record.

Pin Type What to wire
in TNow TIME TIME() of this scan
in In, HighSwitch, LowSwitch, Running, Masked, ResetReq, RetryWindow As the block's pins above (no defaults: wire every one)
inout Meas UT_MEAS Settings and status
inout St UT_MEAS_ST The working state. Its trip, warn, hiHi, hi, lo, loLo, reset, badInput and badSetting are the block's outputs. Not for HMIs
returns BOOL Trip