UT_ROTATION — Shaft / belt speed monitor (proximity sensor)

UT_ROTATION — Shaft / belt speed monitor (proximity sensor)

Watches a proximity sensor on a shaft, pulley or target wheel. It detects a stall
(sensor stuck on or off), underspeed (belt slip, overload) and overspeed, and
measures the speed: shaft speed in rpm or rev/s, or belt / chain line speed in
m/min or m/s. Wire Healthy to the motor's Interlock to stop on a stall.
Replaces rotationMonitor (Better Eggs).

Pins

Pin Type Default What to wire
in Running BOOL FALSE Machine running (UT_MOTOR.Running)
in Sensor BOOL FALSE Proximity sensor
in Reset BOOL FALSE Rising edge: reset a latched fault
out Healthy BOOL No fault → motor Interlock
out Rotating BOOL Pulses being seen (one within stallTime)
out Speed REAL In speedUnit (rpm by default)
out Fault BOOL
inout Data UT_ROTATION_DATA

Record UT_ROTATION_DATA

Field Type Default Meaning
pulsesPerRev INT 1 Targets on the wheel, for rpm and rev/s (0 or negative counts as 1)
speedUnit UT_SPEED_UNIT UT_SPD_RPM Unit of Speed, speed, minSpeed and maxSpeed: UT_SPD_RPM (0, rpm), UT_SPD_RPS (revolutions per second = Hz of the shaft), UT_SPD_M_MIN (line speed, m/min), UT_SPD_M_S (line speed, m/s)
distPerPulse REAL 0.0 Line speed only: belt or chain travel per pulse, in m (e.g. a 0.3 m drum circumference with 2 targets = 0.15). Must be above 0 for m/min and m/s
startDelay TIME T#5s After a start, stall and underspeed are ignored this long
stallTime TIME T#3s No pulse this long while running = stalled
minSpeed / maxSpeed REAL 0.0 / 0.0 Under / over speed limits, in speedUnit (0 = off)
speedDelay TIME T#5s Under / over speed must last this long
filterTime TIME T#1s Speed is measured over at least this long
coastDown TIME T#10s After a stop, pulses are expected this long
retryWindow TIME T#1h RETRY counts trips within this window
stall UT_PROTECTION TRIP · MANUAL b0: a stalled conveyor usually needs a look
underspeed UT_PROTECTION WARN · AUTO b1: belt slip
overspeed UT_PROTECTION OFF b2
sensor UT_PROTECTION WARN · AUTO b3: pulses while stopped, after coastDown
(invalid setting) warning b4: wrnConfig, see below
cmdReset BOOL HMI reset (acts once, on its rising edge; cleared by the block)
speed, rotating, period REAL, BOOL, TIME Status (speed in speedUnit; period: time between the last two pulses)
wrnTooFast BOOL Pulses at the scan-rate limit (held 5 s)
wrnConfig BOOL speedUnit unknown, or a line speed with distPerPulse not above 0 (or not a number)
fault, warning, faultCode BOOL, BOOL, DWORD See conventions
timeLeft TIME The countdown the status shows: the start delay, or a recover / retry wait
statusCode UT_STATUS What it is doing, or what is wrong (codes below)
faultId UT_FAULT The fault, warning or setting the status is about (UT_F_NONE when none)
statusText STRING(30) statusCode and faultId in words, e.g. Latched: stalled

Status codes

statusCode is a UT_STATUS and faultId a UT_FAULT (an HMI reads their numbers); statusText is the two in words.

statusCode faultId statusText When
UT_ST_STOPPED Stopped Not running, no pulses
UT_ST_RUNNING Running Running, past the start delay, no fault
UT_ST_STILL_TURNING Stopped: still turning Not running, pulses still seen (coasting down)
UT_ST_CHECKS_DELAY Starting: checks delayed Running, inside startDelay (timeLeft counts it down)
UT_ST_WARNING UT_F_PULSES_FAST Warning: pulses too fast wrnTooFast
UT_ST_WARNING the protection Warning: stalled A protection set to WARN: UT_F_STALLED (stalled), UT_F_UNDERSPEED, UT_F_OVERSPEED, UT_F_PULSES_STOPPED (turning when off)
UT_ST_WARN_SETTING UT_F_SPEED_UNIT / UT_F_DIST_PER_PULSE Setting: speed unit wrnConfig
UT_ST_FAULT the protection Fault: stalled A trip, AUTO reset (timeLeft: the recover still to go)
UT_ST_FAULT_RETRY the protection Retrying: stalled A trip, RETRY with retries left (timeLeft: the wait)
UT_ST_FAULT_LOCKED the protection Locked: stalled A trip, RETRY, retries used up: reset needed
UT_ST_FAULT_RESET the protection Latched: stalled A trip, MANUAL: reset needed

A trip comes first, then a warning, a bad setting, pulses too fast, starting,
running, coasting, stopped.

How it works

  • The pulse rate f (pulses per second) is measured from pulse to pulse over at
    least filterTime, so a slow shaft is accurate. While no pulse comes it falls
    (1 / time since the last pulse), so a stopping shaft is seen slowing; after
    stallTime it is 0. The speed, and the limits, are in speedUnit:

    speedUnit Speed
    UT_SPD_RPM (default) rpm = 60 × f / pulsesPerRev
    UT_SPD_RPS rev/s (Hz) = f / pulsesPerRev
    UT_SPD_M_MIN m/min = 60 × f × distPerPulse
    UT_SPD_M_S m/s = f × distPerPulse

    This divides by pulsesPerRev; the original multiplied.

  • Example, a conveyor that should run at 45 m/min, with one target on a tail
    drum of 0.4 m circumference: speedUnit := UT_SPD_M_MIN, distPerPulse := 0.4, minSpeed := 35.0 (belt slip below 35 m/min). The same drum in rpm:
    minSpeed := 87.5 (35 / 0.4).

  • The maximum measurable rate is set by the scan rate: 1 / (2 × scan time)
    pulses per second (60 / (2 × scan time × pulsesPerRev) rpm). The block warns
    (wrnTooFast) at it.

  • Invalid settings. An unknown speedUnit, or a line speed with
    distPerPulse 0, negative or not a number, sets wrnConfig, warning and
    fault bit 4 (status Setting: speed unit or
    Setting: distance per pulse): the speed reads 0 and the under / over
    speed checks are off until it is fixed. The stall and sensor checks still act.

  • A stall is seen with the sensor stuck ON or stuck OFF (no rising edge either way).

  • Each protection is a UT_PROTECTION: change its response and reset as you like.
    Reset by the Reset pin or cmdReset, each on its rising edge: one held on (a
    Modbus coil left on) resets once; a reset while the shaft is still stalled is
    refused.