UT_MOTOR — Motor starter (DOL / contactor / soft starter)

UT_MOTOR — Motor starter (DOL / contactor / soft starter)

Controls and protects one motor started by a contactor, a soft starter or any
"run relay + run feedback" load (heater bank, fan, conveyor). Built in:
Hand/Off/Auto/Out-of-service, interlocks and permissives, overload, thermistor,
current monitoring, feedback supervision, welded-contactor detection and a
restart/backspin delay. Every protection can recover by itself, retry, or latch.

Pins

Pin Type Default What to wire
in AutoCmd BOOL FALSE Run request from your logic (used in Auto)
in Feedback BOOL FALSE Contactor auxiliary / soft-starter "running" relay
in Overload BOOL FALSE Overload relay tripped (TRUE = tripped; a NC aux through NOT at the pin)
in Thermistor BOOL FALSE PTC relay / motor thermal switch tripped (a NC contact through NOT at the pin)
in DriveFault BOOL FALSE Soft-starter fault relay
in Current REAL 0.0 Motor current in amps (used if fullLoadCurrent > 0). NaN / infinite while a current protection is on: a warning (wrnCurrentBad)
in Interlock BOOL TRUE FALSE stops the motor in every mode (e.g. UT_PUMP.Healthy)
in Permissive BOOL TRUE FALSE blocks starting only (e.g. UT_STARTS.StartPermit)
in SwHand / SwAuto BOOL FALSE Selector switch (if modeSource uses it)
in LocalStart BOOL FALSE Local start pushbutton (Hand)
in LocalStop BOOL FALSE Local stop pushbutton (TRUE = pressed; a NC button through NOT at the pin)
in Reset BOOL FALSE Reset for MANUAL protections (rising edge)
out Run BOOL Contactor coil
out Running BOOL Run confirmed by feedback
out Fault BOOL A trip is holding it off
out Warning BOOL A protection set to warn is active, a bad current signal, or an invalid setting
out Ready BOOL Would start now if asked: healthy, permitted, in Auto or Hand, not waiting out restartDelay (stays TRUE while running)
out Auto BOOL In Auto mode
out State UT_STATE For HMIs
inout Data UT_MOTOR_DATA The motor's record

Every input is TRUE = active (tripped, pressed). There is no NC setting: wire a
normally-closed contact through NOT at the pin or in the I/O mapping, e.g.
Overload := NOT M1_OL_NC.

Record UT_MOTOR_DATA (shared by every UT_MOTOR* block)

Settings

Field Type Default Meaning
modeSource UT_MODE_SOURCE UT_SRC_HMI Where the mode comes from. The mode starts at Off and is retained
useFeedback BOOL TRUE Supervise the run feedback
fullLoadCurrent REAL 0.0 Motor FLC in A (0 = current monitoring off)
currentStartMask TIME T#5s Ignore current after a start (inrush)
restartDelay TIME T#5s Minimum off time before a start, counted from power-up too (anti-short-cycle, pump backspin, staggered restart after a power cut). T#0s = none
restartAfterReset BOOL FALSE After a MANUAL reset, restart without the command cycling
resetByOff BOOL TRUE Switching to Off resets MANUAL faults
retryWindow TIME T#1h Window for RETRY counts. T#0s = no window: the count is cleared only by a reset or a power cycle
localStopInAuto BOOL TRUE Local stop also stops in Auto (restart on the next AutoCmd rising edge)
simulate BOOL FALSE The run feedback follows Run (so noFeedback, feedbackLost and stuck see the simulated feedback). Every other protection still acts: overload, thermistor, drive fault, driveNotReady and the current levels
powerUp UT_POWERUP UT_PU_LAST After a power cut: UT_PU_LAST the mode comes back (Auto carries on); UT_PU_OFF back to Off, the operator selects it again. A Hand start is never kept either way. See conventions
handMaxRun TIME T#0s Hand: stop after running this long (a remote user hand-starts and forgets). T#0s = no limit; negative = no limit and a warning

The reversing, star-delta, two-speed and VSD blocks keep their own settings, commands
and status in a second record of their own (Rev, Sd, Spd, Vsd), so a plain
motor carries none of them. See REV, SD,
2SPD and VSD.

Protections (each a UT_PROTECTION or UT_LEVEL; set each one's response and reset independently)

Field Bit Default response · delay · reset Raised when
overload 0 TRIP · 100 ms · AUTO Overload relay tripped. Resetting the relay in the panel puts the motor back in service
thermistor 1 TRIP · 0 · AUTO (recover 5 min) Motor too hot. Restarts after cooling
noFeedback 2 TRIP · 3 s · RETRY (3, recover 30 s) Run without feedback (failed to start). The delay is the start time
feedbackLost 3 TRIP · 500 ms · RETRY (3, recover 30 s) Feedback dropped while running
stuck 4 TRIP · 2 s · MANUAL Feedback with no Run: welded contactor
currentHigh 5 OFF · 5 s · RETRY (3, recover 5 min) · sp 115 % FLC Overcurrent / jam (UT_LEVEL)
currentLow 6 OFF · 5 s · RETRY (3, recover 5 min) · sp 40 % FLC Underload: dry pump, broken belt or coupling (UT_LEVEL)
drive 7 TRIP · 0 · AUTO DriveFault input
(speed deviation) 8 VSD only Vsd.speedDev (UT_MOTOR_VSD)
(changeover) 9 REV / SD / 2SPD only The variant's changeover (REV, SD, 2SPD)
(drive not ready) 10 VSD only Vsd.driveNotReady (UT_MOTOR_VSD)
(current signal bad) 11 Warning Current is NaN or infinite while fullLoadCurrent > 0 and currentHigh or currentLow is not OFF (wrnCurrentBad). The motor keeps running; the current levels hold as they were
(invalid setting) 12 Warning, or a fault A setting is invalid (wrnConfig), see Invalid settings

faultCode has a bit for every protection that is raised, warnings included
(a WARN protection sets its bit as a TRIP one does), and faultId names the
lowest bit set. Bits 8 to 10 are the variants' protections, which live in the
variant's own record.

HMI commands

Field Type Meaning
cmdMode INT 0 Off · 1 Hand · 2 Auto · 3 OOS (acts when a new value arrives; the block sets it back to −1)
cmdStart / cmdStop BOOL Hand start / stop
cmdReset BOOL Reset MANUAL protections

The reversing and two-speed blocks have their direction and speed commands
(cmdFwd / cmdRev, cmdLow / cmdHigh) in their own record.

Every BOOL command acts once, on its rising edge, and is cleared by the block. One
held TRUE (a Modbus coil left on, a debugger force) acts once: a held cmdStart does
not restart a Hand motor after a stop, and a held cmdReset never turns a MANUAL trip
into an automatic one. Stop always wins: no start in a scan in which cmdStop or
LocalStop reads TRUE, so one held TRUE keeps the motor stopped. A master that
rewrites a command every poll goes through UT_CMD.

Status fields

mode, state, run, running, ready, fault, warning, interlocked,
notPermitted, restartBlocked, restartIn : TIME, current, currentPct,
runTime : TIME (this run), faultCode : DWORD and faultId : UT_FAULT (both cover
warnings too), statusCode : UT_STATUS and statusText : STRING(30) (what it is
doing or what holds it back, see Status), wrnCurrentBad (bit 11),
wrnConfig (bit 12).

Group fields. The motor block writes only isVsd; a group block
(UT_DUTY, UT_PUMP_CASCADE) writes the grp…
fields; you set capacity and jockey:

Field Type Meaning
grpActive BOOL A group owns this motor (set every scan by the group, cleared by the motor)
grpRun BOOL The group asks it to run
grpRank INT Its place in the group's order
grpSpeed REAL VSD: the speed the group asks for, % (used in Auto while owned)
isVsd BOOL TRUE on a UT_MOTOR_VSD record, FALSE on the others, set every scan, so a group knows which pumps have a speed
capacity REAL Setting, default 0.0. A pump in a UT_PUMP_CASCADE: its flow at full speed at the setpoint pressure (0 = not known). Ignored by the motor
jockey BOOL Setting, default FALSE. A pump in a UT_PUMP_CASCADE: the small pump that carries the low demand. Ignored by the motor
grpRunTime TIME The run time the group has counted since power-up, for its HOURS rotation (the group sets it back to 0 on its first scan after a power cut, also in a RETAIN record)

Added for time visibility and "why it stopped" (at the end of the record):

Field Type Meaning
timeLeft TIME The countdown the status shows: the restart delay, a dead time or star time, a fault's recover / retry wait, the Hand run limit
offTime TIME Time stopped, since the last stop or power-up (0 while running)
maskLeft TIME The current start mask still to run (0 when not masking)
faultClearIn TIME An AUTO / RETRY trip clears (or retries) in this (0 = nothing counting)
stopReason UT_STOP Why the last run ended (below; UT_STOP_NONE = none since power-up), kept until the next run ends
lastFaultCode DWORD The faultCode bits of the last trip, kept after it clears, until the next trip
lastFault UT_FAULT Its name (the lowest bit), e.g. UT_F_OVERLOAD, kept the same way
trips UDINT Trips since power-up (not kept over a power cut)

Why the last run ended (stopReason, the common
stop reasons):

stopReason Words (UT_STOP_TEXT) When
UT_STOP_DEMAND_ENDED Auto: demand ended AutoCmd dropped
UT_STOP_OPERATOR Stopped: operator A Hand stop (cmdStop, LocalStop), or a local stop in Auto
UT_STOP_SWITCHED_OFF Stopped: switched off The mode changed to Off or OOS
UT_STOP_INTERLOCK Stopped: interlock Interlock dropped
UT_STOP_FAULT Stopped: fault A protection tripped (or a setting keeps it off); lastFault says which
UT_STOP_MAX_RUN Stopped: max run time handMaxRun ran out
UT_STOP_GROUP Stopped: group A group (UT_DUTY, UT_PUMP_CASCADE) stopped it

How it works

  • Mode (UT_MODE_SELECT): Off → stopped. Hand → cmdStart/LocalStart (rising edge) latch it on,
    cmdStop/LocalStop stop it. A start given while the Permissive is FALSE is
    dropped: the motor does not start later when the permissive returns; the
    operator presses start again (a start waiting out restartDelay is dropped too
    if the permissive goes). Auto → follows AutoCmd, or grpRun while a group (UT_DUTY, UT_PUMP_CASCADE) owns it (grpActive).
    OOS → stopped, protections suppressed, no fault or warning reported.
  • Run = requested AND Interlock AND (already running OR Permissive) AND no trip AND
    not restart-blocked. A running motor keeps running if the permissive goes.
  • A trip drops Run at once. In Auto, AUTO/RETRY recovery puts it back in service
    by itself if AutoCmd is still on. In Hand a trip drops the hand start, like the
    interlock: once the fault has cleared the operator presses start again. After a
    MANUAL reset of a stopped motor the command must cycle (unless restartAfterReset):
    in Auto, AutoCmd goes off and on; in Hand, the operator presses start again.
  • A local stop in Auto stops it; it restarts on the next rising edge of AutoCmd.
  • Hand run limit (handMaxRun): a Hand run stops after that long (counted from
    the start, or from the change to Hand of a running motor; status Running: Hand
    with timeLeft counting down, then Hand: max run, press start and stopReason
    UT_STOP_MAX_RUN). The operator presses start again for another run.
  • In Hand, losing the interlock drops the hand start, so the motor does not restart
    by itself when the interlock returns. In Auto it restarts (its request is still on).
  • restartDelay holds back a start until the motor has been off that long; a
    running motor is never stopped by it, nor by the permissive. It counts from
    power-up too, so motors with different delays come back one after the other.
  • After a power cut the mode is kept (Off, Hand, Auto, OOS), unless powerUp is
    UT_PU_OFF: then it comes back Off and stays stopped until the operator selects a
    mode again (a conveyor someone must restart on purpose). Auto restarts by
    itself once restartDelay has run. Hand needs a fresh start: a start button held
    through the power cut, or a start command already waiting, is not one. Trips,
    latches and retries are not kept; a fault still there trips again.
  • Mode changes are bumpless: Auto → Hand keeps a running motor running.
  • State: OOS · FAULT · INTERLOCKED · STARTING (run, no feedback yet) · WARNING ·
    ON · STOPPING (feedback still on after the stop) · OFF.

Status

statusCode, faultId and statusText say the one main thing the motor is
doing, or what holds it back, so a technician can see on the HMI why it is not
running without opening the program. A motor asked to run that is not running
always shows a held, fault or configuration status. The most important reason wins:
configuration > fault > held / waiting > warning > running > idle. A warning shows
over "Running" so it is seen. The time that goes with a status is in timeLeft.
The text is rebuilt only when the status or the fault changes. The numbers are in
conventions.

statusCode Words When
UT_ST_OFF Off Mode Off
UT_ST_IDLE Idle Auto with nothing asking it to run
UT_ST_RUN_AUTO Running: Auto
UT_ST_RUN_HAND Running: Hand With handMaxRun: timeLeft is the time left
UT_ST_STARTING Starting Run given, run feedback not yet in
UT_ST_STOPPING Stopping Stopped, run feedback still on
UT_ST_RUN_GROUP Running: group A group (UT_DUTY, UT_PUMP_CASCADE) runs it; grpRank is its place
UT_ST_RESTART_DELAY Waiting: restart delay Asked to run, restartDelay not over yet (timeLeft counts down)
UT_ST_INTERLOCK Blocked: interlock Interlock FALSE (every mode but OOS)
UT_ST_NOT_PERMITTED Not permitted Permissive FALSE while stopped, in Hand or Auto
UT_ST_HAND_PRESS_START Hand: press start Hand and stopped: no start given, or it was dropped (a stop, a trip, the interlock, not permitted)
UT_ST_WAIT_GROUP Waiting: turn in group A group owns it and does not run it now
UT_ST_HAND_MAX_RUN Hand: max run, press start handMaxRun ended the Hand run
UT_ST_MUST_CYCLE Waiting: command must cycle After a MANUAL reset, or a local stop in Auto: AutoCmd must go off and on
UT_ST_OOS Out of service
UT_ST_WARNING Warning: <fault> A protection set to WARN is raised, or Current is NaN or infinite while a current level is in use (UT_F_CURRENT_BAD, current signal)
UT_ST_WARN_SETTING Setting: <setting> An invalid setting, a safe value in use (settings below)
UT_ST_FAULT Fault: <fault> Tripped, AUTO: clears by itself once the cause has gone for recover (timeLeft while it counts)
UT_ST_FAULT_RETRY Retrying: <fault> Tripped, RETRY: the protection's retries of maxRetries (timeLeft while it counts)
UT_ST_FAULT_RESET Latched: <fault> Tripped, MANUAL: a reset (pin, cmdReset, Off) once the cause has gone
UT_ST_FAULT_LOCKED Locked: <fault> RETRY used up: now as MANUAL
UT_ST_CONFIG Config: <setting> An invalid setting keeps the motor off

<fault> is faultId, one of: UT_F_OVERLOAD (overload) · UT_F_MOTOR_HOT (motor
too hot) · UT_F_NO_FEEDBACK (no run feedback) · UT_F_FEEDBACK_LOST (feedback
lost) · UT_F_WELDED (contactor welded) · UT_F_CURRENT_HIGH (current high) ·
UT_F_CURRENT_LOW (current low) · UT_F_DRIVE (drive fault) · UT_F_SPEED_DEV
(speed deviation) · UT_F_CHANGEOVER (changeover) · UT_F_DRIVE_NOT_READY (drive
not ready).
<setting> is one of: UT_F_FLC (full load current) · UT_F_CURRENT_NEEDS_FLC
(current needs FLC) · UT_F_START_MASK (start mask) · UT_F_RESTART_DELAY (restart
delay) · UT_F_HAND_MAX_RUN (hand max run) · a protection's name (its delay,
recover or maxRetries).
The variants add their own statuses and settings, listed in their docs.

Invalid settings

An invalid or out-of-range setting never runs the motor unsafely. Either it falls
back to a safe value and warns (Warning, wrnConfig, faultCode bit 12 "Invalid
setting"), or the motor is kept off with a fault (Fault, wrnConfig, bit 12),
until the setting is fixed. Common to every motor block (warning, fallback):

Setting Invalid Fallback
fullLoadCurrent negative, NaN, infinite Current monitoring off
currentHigh / currentLow not OFF while fullLoadCurrent is 0 or invalid They cannot act (no FLC)
currentStartMask, restartDelay, retryWindow negative 0 (retryWindow 0 = no window)
handMaxRun negative No limit
Any protection in use negative delay / recover; negative maxRetries with RETRY 0: acts at once; latches on the first trip
A level in use (currentHigh, currentLow, a VSD's speedDev) sp NaN or infinite; deadband negative, NaN or infinite The value cannot raise it; deadband 0

The variants add their own: REV and 2SPD
negative dead times (warning), SD starTime 0 or negative (kept
off), VSD speed limits and raw scaling (kept off)
and its other settings (warning).

Using it

M1(AutoCmd := Pump1.RunCmd, Feedback := P1_Aux, Overload := P1_OL,
   Interlock := Pump1.Healthy, Permissive := P1Starts.StartPermit, Data := Motor1);
P1_Contactor := M1.Run;