UT_RUN_HOURS — Run-hour meter with service interval
UT_RUN_HOURS — Run-hour meter with service interval
Counts running time for anything (motor, heater, lamp, filter), keeps it across
power loss, and flags when a service is due. Split out of pumpSelectionControl.
Pins
| Pin | Type | Default | What to wire | |
|---|---|---|---|---|
| in | Running |
BOOL | FALSE | Equipment running (e.g. UT_MOTOR.Running) |
| in | ResetService |
BOOL | FALSE | Rising edge: service done, restart the service count |
| out | TotalHours |
REAL | Lifetime hours | |
| out | ServiceDue |
BOOL | Service hours ≥ interval | |
| inout | Data |
UT_RUN_HOURS_DATA |
Record UT_RUN_HOURS_DATA
| Field | Type | Default | Meaning |
|---|---|---|---|
serviceInterval |
REAL | 0.0 | Hours between services (0, negative or not a number = off) |
saveEvery |
TIME | T#12h | How often the hours are saved for a power cut (T#0s = not kept). Presets, service resets and day rollovers are saved at once |
cmdResetService |
BOOL | HMI: service done | |
cmdPreset + presetHours |
BOOL + REAL | HMI: set the total (e.g. after replacing the PLC). 0 to 1E9 h; anything else is ignored | |
cmdDayRollover |
BOOL | Midnight pulse (from UT_SCHEDULE or the HMI): today → yesterday |
|
totalHours, serviceHours, serviceDue |
REAL, REAL, BOOL | Status | |
todayHours, yesterdayHours |
REAL | Status: since / before the last day rollover | |
currentRun |
TIME | Status: length of this run (0 when stopped) | |
lastRun |
TIME | Status: length of the previous run | |
serviceLeft |
REAL | Status: hours to the next service; negative = overdue by that many hours; 0 when serviceInterval is off |
How it works
- Time counts while
Runningis TRUE, from real elapsed time, so it is the same
at any task rate. It is kept as whole milliseconds in a 64-bit integer plus the
part of a millisecond left over, so it stays exact for centuries on every
board (a REAL total would stop counting once it is large). - The hours are saved for a power cut every
saveEvery, so a power cut costs at
most that much running time (plus the controller's own save period, see
conventions). After a restart the block
carries on from the saved hours from the first scan, without counting
anything twice. - Commands act once and are cleared; a command held on (a coil left on, a
debugger force) acts once until it goes off again.