UT_RUN_HOURS — Run-hour meter with service interval

UT_RUN_HOURS — Run-hour meter with service interval

Counts running time for anything (motor, heater, lamp, filter), keeps it across
power loss, and flags when a service is due. Split out of pumpSelectionControl.

Pins

Pin Type Default What to wire
in Running BOOL FALSE Equipment running (e.g. UT_MOTOR.Running)
in ResetService BOOL FALSE Rising edge: service done, restart the service count
out TotalHours REAL Lifetime hours
out ServiceDue BOOL Service hours ≥ interval
inout Data UT_RUN_HOURS_DATA

Record UT_RUN_HOURS_DATA

Field Type Default Meaning
serviceInterval REAL 0.0 Hours between services (0, negative or not a number = off)
saveEvery TIME T#12h How often the hours are saved for a power cut (T#0s = not kept). Presets, service resets and day rollovers are saved at once
cmdResetService BOOL HMI: service done
cmdPreset + presetHours BOOL + REAL HMI: set the total (e.g. after replacing the PLC). 0 to 1E9 h; anything else is ignored
cmdDayRollover BOOL Midnight pulse (from UT_SCHEDULE or the HMI): today → yesterday
totalHours, serviceHours, serviceDue REAL, REAL, BOOL Status
todayHours, yesterdayHours REAL Status: since / before the last day rollover
currentRun TIME Status: length of this run (0 when stopped)
lastRun TIME Status: length of the previous run
serviceLeft REAL Status: hours to the next service; negative = overdue by that many hours; 0 when serviceInterval is off

How it works

  • Time counts while Running is TRUE, from real elapsed time, so it is the same
    at any task rate. It is kept as whole milliseconds in a 64-bit integer plus the
    part of a millisecond left over, so it stays exact for centuries on every
    board (a REAL total would stop counting once it is large).
  • The hours are saved for a power cut every saveEvery, so a power cut costs at
    most that much running time (plus the controller's own save period, see
    conventions). After a restart the block
    carries on from the saved hours from the first scan, without counting
    anything twice.
  • Commands act once and are cleared; a command held on (a coil left on, a
    debugger force) acts once until it goes off again.