UT_VALVE_MOD — Modulating valve or damper (analog positioner)

UT_VALVE_MOD — Modulating valve or damper (analog positioner)

Drives a valve or damper that has a positioner (4–20 mA / 0–10 V demand), with
optional position feedback. Typically sits after OpenPLC's PID. Mode, fail
action and protections work as UT_VALVE (UT_VALVE_CORE).

Pins

Pin Type Default What to wire
in AutoSp REAL 0.0 Position request in Auto, % (e.g. PID output). NaN / infinite is ignored (the last good value stands)
in PosFb REAL -1.0 Position feedback % (exactly −1 = not fitted)
in OpenLs / ClosedLs BOOL FALSE Optional end switches
in Interlock BOOL TRUE FALSE → failPosition
in DriveFault, SwHand, SwAuto, Reset As UT_VALVE
in Permissive BOOL TRUE FALSE: the valve moves only toward failPosition (an Auto request away from it waits where the valve is; a Hand one is dropped); it never forces it
in LocalOpen / LocalClose / LocalStop BOOL FALSE Local pushbuttons (Hand, rising edge): handSp 100 %, 0 %, or stop where it is (held: keeps stopping)
out Out REAL Demand to the positioner, % (100 − demand when reverseActing)
out OutRaw UINT Out scaled to rawMin..rawMax, clipped to 0–65535, for %QW
out IsOpen / IsClosed BOOL Feedback (or the demand) against the thresholds, or the end switch
out Fault BOOL A trip is holding it at the fail action
out State UT_STATE OFF closed, ON open, STARTING / STOPPING while ramping or the feedback catches up
inout Data UT_VALVE_DATA Shared valve record (UT_VALVE)
inout Modul UT_VALVE_MOD_DATA The modulating settings, protections and status (below)

Record UT_VALVE_MOD_DATA (pin Modul)

Field Type Default Meaning
outMin / outMax REAL 0.0 / 100.0 Clamp (min above max gives max, as IEC LIMIT)
rampRate REAL 0.0 Rate limit in Hand and Auto, in % per rateUnit (0 = off). The fail action is immediate
rateUnit UT_RATE_UNIT UT_PER_SEC Time unit of rampRate: UT_PER_SEC (0, % per second) or UT_PER_MIN (% per minute); UT_PER_HOUR and UT_PER_DAY work too
tightShutoff REAL 0.0 Demand below this → 0 % (seat it properly), even below outMin. 0 = off
fullOpenAbove REAL 100.0 Demand above this → 100 %, even above outMax. 100 = off
reverseActing BOOL FALSE Air-to-close: output inverted
failPosition REAL 0.0 Demand on interlock / fault / Off (below 0, or not a number = stay where it is)
holdOnFault BOOL FALSE A trip holds the last demand instead of failPosition
openThreshold / closedThreshold REAL 98.0 / 2.0 IsOpen at or above, IsClosed at or below, %
rawMin / rawMax REAL 0.0 / 65535.0 OutRaw at 0 % and 100 %
handSp REAL 0.0 Hand position (HMI); tracks the demand in Auto. Hand cmdOpen / cmdClose (in Data) set it to 100 / 0 %, cmdStop to the demand now (a ramp stops where it is)
deadband REAL 1.0 Feedback within this of the demand counts as there (State)
deviation UT_LEVEL WARN · 10 s · AUTO · sp 5 Feedback vs demand: sp is the limit in %, delay the time (faultCode bit 6)
posFeedback UT_PROTECTION TRIP · 500 ms · AUTO Feedback NaN, infinite or outside −5…105 % (faultCode bit 7)
demand REAL Status: the position asked for, %

In the valve record Data: position (the feedback, or the demand without one), the
modes, the other protections, the HMI commands and the status.

How it works

  • Request → tight shutoff / full open → clamp → ramp → Out (inverted if
    reverse acting) → OutRaw.
  • The ramp is in % of the stroke per second, or per minute with
    rateUnit := UT_PER_MIN. For a slow damper that should take 5 minutes from
    closed to open: rampRate := 20.0, rateUnit := UT_PER_MIN (the same as
    rampRate := 0.3333 per second).
  • Bumpless: handSp follows the demand in Auto, so Auto → Hand doesn't move
    the valve. In Hand an interlock sets handSp to failPosition, so it does not
    move by itself when the interlock returns.
  • Deviation is checked only with good feedback, after its delay. Bad feedback
    trips posFeedback and applies the fail action; the demand is then used as
    the position.
  • travelElapsed is how long the ramp under way has run (a reversal starts a new
    one) and timeLeft the ramp's time left, with no ramp both 0.
  • OOS: Out = 0, faults hidden.
  • Power-up: with feedback, the demand and handSp start at the feedback, so in
    Hand the valve stays where it is. Without feedback the demand starts at 0 %
    (declare the record RETAIN to keep handSp).

Status

statusCode, faultId and statusText say the one main thing the valve is
doing, or what holds it back, so a technician can see on the HMI why it is not where
it was asked to be. The most important reason wins: configuration > fault > held /
waiting > warning > position > Off. The words hold no numbers: the target is in demand and the position in position. The time left
(travel, a pause, a fault's recover / retry wait) is in timeLeft. The text is
rebuilt only when the status or the fault changes. Where the valve is (the rows
marked (this block)) comes from the block's last scan, so it shows one scan after
it changes. The numbers are in conventions.

statusCode Words When
UT_ST_OFF Off Mode Off (it goes to its safe position)
UT_ST_OPEN Open (this block) At or above openThreshold
UT_ST_CLOSED Closed (this block) At or below closedThreshold
UT_ST_MOVING Moving (this block) Going to demand; timeLeft is the ramp's time left when a ramp is set
UT_ST_AT_POSITION At position (this block) Between the thresholds, at demand
UT_ST_INTERLOCK Blocked: interlock Interlock FALSE: at its safe position (every mode but OOS)
UT_ST_OOS Out of service
UT_ST_NOT_PERMITTED Not permitted (this block) Permissive FALSE holds back a move away from the safe position
UT_ST_WARNING Warning: <fault> A protection set to WARN is raised
UT_ST_WARN_SETTING Setting: <setting> An invalid setting, a safe value in use (settings below)
UT_ST_FAULT Fault: <fault> Tripped, AUTO: clears by itself once the cause has gone for recover (timeLeft while it counts)
UT_ST_FAULT_RETRY Retrying: <fault> Tripped, RETRY: the protection's retries of maxRetries (timeLeft while it counts)
UT_ST_FAULT_RESET Latched: <fault> Tripped, MANUAL: a reset (pin, cmdReset, Off) once the cause has gone
UT_ST_FAULT_LOCKED Locked: <fault> RETRY used up: now as MANUAL

<fault> is faultId, one of: UT_F_BOTH_LIMITS (both limits) · UT_F_ACTUATOR (actuator fault) · UT_F_POS_DEVIATION (pos. deviation) · UT_F_POS_FEEDBACK (position signal).
<setting> with UT_ST_WARN_SETTING is one of: UT_F_SAVE_EVERY (save every) · UT_F_RETRY_WINDOW (retry window) · UT_F_MODE_SOURCE (mode source) · UT_F_OUTPUT_MIN_MAX (output min / max) · UT_F_RAMP_RATE (ramp rate) · UT_F_RATE_UNIT (rate unit) · UT_F_SHUTOFF (shutoff / full open) · UT_F_FAIL_POSITION (fail position) · UT_F_OPEN_THRESHOLD (open/closed limit) · UT_F_RAW_MIN_MAX (raw min / max) · UT_F_DEADBAND (deadband).

Bad settings

A setting that is not a number, negative or unknown never drives the valve somewhere
it could do damage. configBad is set and faultCode bit 8, and faultId names the
setting (the lowest priority). A negative saveEvery keeps nothing; a negative retryWindow
uses the default 1 h; an unknown modeSource uses the HMI (warnings).

  • Warning only (a safe value is used): outMin / outMax not a number, outside
    0..100 or min above max (the 0..100 clamp holds); rampRate negative or not a number,
    or an unknown rateUnit (no ramp, as 0); tightShutoff / fullOpenAbove not a number (off); failPosition
    not a number (stay) or above 100 (100); openThreshold / closedThreshold not a
    number (98 / 2); rawMin / rawMax not a number or equal (OutRaw 0 or fixed);
    deadband negative or not a number.