08 - Patterns

08 - Patterns

Worked examples, and the habits worth keeping.

The two-task split

Every project should look like this, and it is the one piece of structure that
matters:

task interval priority holds
APP_TASK T#20ms 0 the machine - no Modbus block at all
NET_TASK T#1ms on the Runtime, T#50ms on a board to start 20 MODBUS_NODE and every block given it

Values cross between them through globals, each written by one task.

PROGRAM net
VAR
    node : MODBUS_NODE;
END_VAR

node( TRANSPORT := MODBUS_RUNTIME_SERIAL,
      SERIAL_DEVICE    := '/dev/ttyUSB0', SERIAL_BAUD := 19200,
      ROLE      := MODBUS_ROLE_BOTH, SERIAL_UNIT_ID := 7 );

END_PROGRAM

The node is the only block that touches the wire, so its period is the floor on
how fast anything happens. Everything else just hands it work and reads pins.
10 - Scan rate has the numbers.

Call the node before the blocks that use it

Within a scan, a block placed above the node acts on the previous scan's state.
It corrects itself and costs one scan — it is not fatal — but there is no
reason to have it happen.

Keep the bus quiet for what matters

This is the habit that separates a Modbus system that works from one that
nearly works.

A Modbus segment carries one conversation at a time. Every read you issue is
time that a control word cannot have. So:

Read on demand what is only needed on demand. A nameplate, a serial number,
a configuration block, a recipe — read it once with MODBUS_READ on a rising
edge and keep it. It does not change.

Watch only what genuinely has to stay fresh, and at the rate the process
actually needs:

(* a tank level: seconds is plenty *)
level( NODE := node, UNIT := 1, FC := MODBUS_FC04_READ_INPUT_REGISTERS,
       ADDRESS := 30, EVERY := T#2s, VALUE := tankLevel );

(* a torque feedback in a closed loop: as fast as the bus will bear *)
torque( NODE := node, UNIT := 2, FC := MODBUS_FC04_READ_INPUT_REGISTERS,
        ADDRESS := 10, EVERY := T#100ms, VALUE := motorTorque );

Stop watching what you are not using. ENABLE stops and starts a watch in
place, with no second entry and no cost while it is off:

(* the dryer's sensors matter only while the dryer runs *)
dryerTemps( NODE := node, UNIT := 5, FC := MODBUS_FC04_READ_INPUT_REGISTERS,
            ADDRESS := 0, EVERY := T#500ms, ENABLE := dryerRunning,
            VALUE := temps );

Write only when the value changed. A write repeated every scan is a write
the bus has to carry every scan:

IF newSpeed <> lastSpeed THEN
    lastSpeed := newSpeed;
    sendSpeed := TRUE;
END_IF;

wr( NODE := node, REQ := sendSpeed, UNIT := 2, ADDRESS := 40, VALUE := newSpeed );

IF wr.DONE OR wr.ERROR THEN
    sendSpeed := FALSE;
END_IF;

Read a range, not an address at a time. One request for a hundred registers
is one frame. A hundred requests is a hundred frames and a hundred turnarounds:
at 19200 baud that is 126 ms against 1.3 seconds, for exactly the same data.

It is safe to call a read or a write in the loop. Nothing floods: a held
REQ reads once on the edge, a duplicate is refused, a superseded write is
replaced. The advice above is about the bus, not about safety.

A device that must be there

VAR
    drive     : MODBUS_DEVICE;
    speedFb   : MODBUS_WATCH;
    feedback  : ARRAY [0..1] OF WORD;
    driveLost : BOOL;
    driveMissing : BOOL;
END_VAR

speedFb( NODE := node, UNIT := 2, FC := MODBUS_FC04_READ_INPUT_REGISTERS,
         ADDRESS := 10, EVERY := T#200ms, VALUE := feedback );

drive  ( NODE := node, UNIT := 2 );

(* Two different faults, two different alarms, two different engineers *)
driveMissing := (drive.SILENT < 0);       (* never answered: commissioning *)
driveLost    := NOT drive.ANSWERING AND (drive.SILENT >= 0);

(* Act on the value only while it is worth acting on *)
IF speedFb.QUALITY = MODBUS_QUALITY_GOOD THEN
    actualSpeed := feedback[0];
ELSE
    driveTrip := TRUE;
END_IF;

Reading a float from a device

VAR
    flow     : MODBUS_WATCH;
    flowRate : REAL;
END_VAR

flow( NODE := node, UNIT := 3, FC := MODBUS_FC04_READ_INPUT_REGISTERS,
      ADDRESS := 30, EVERY := T#1s,
      ORDER := MODBUS_ORDER_CDAB, VALUE := flowRate );

If it reads 4.6e-41 instead of 1234.5, the address is right and ORDER is
wrong. Try MODBUS_ORDER_CDAB first if you were on ABCD, and the other way
round. See 05 - Reading and writing.

A PLC that is also a device

PROGRAM net
VAR
    node : MODBUS_NODE;
    cfg  : MODBUS_CONFIG;
    name : MODBUS_IDENTITY;
END_VAR
node( TRANSPORT := MODBUS_RUNTIME_SERIAL,
      SERIAL_DEVICE    := '/dev/ttyUSB0', SERIAL_BAUD := 19200,
      ROLE      := MODBUS_ROLE_BOTH, SERIAL_UNIT_ID := 7 );

(* Optional, and here only because this node wants a failsafe *)
cfg ( NODE := node, TIMEOUT := T#0s, FAILSAFE := T#5s );
name( NODE := node, VENDOR := 'Example Co', PRODUCT := 'Pump House' );
END_PROGRAM
PROGRAM app
VAR
    node     : MODBUS_NODE;
    measured : MODBUS_MAP;
    commands : MODBUS_MAP;
    readings : ARRAY [0..15] OF WORD;
    setpoints: ARRAY [0..3] OF WORD;
END_VAR

(* Read-only to anyone outside: the list has no write function code *)
measured( NODE := node, TABLE := MODBUS_INPUT_REGISTERS,
          ADDRESS := 0, VALUE := readings );

(* Writable, and therefore validated *)
commands( NODE := node, TABLE := MODBUS_HOLDING_REGISTERS,
          ADDRESS := 100, VALUE := setpoints );

IF commands.WRITTEN THEN
    IF setpoints[0] > 1500 THEN setpoints[0] := 1500; END_IF;
    acceptSetpoint := TRUE;
END_IF;
END_PROGRAM

A terminal server

A serial-to-Ethernet converter with three RS-485 ports is three nodes, one per
TCP port:

segmentA( TRANSPORT := MODBUS_RUNTIME_TCP, FRAMING := MODBUS_FRAMING_RTU,
          TCP_HOST := '192.168.1.50', TCP_PORT := 4001 );
segmentB( TRANSPORT := MODBUS_RUNTIME_TCP, FRAMING := MODBUS_FRAMING_RTU,
          TCP_HOST := '192.168.1.50', TCP_PORT := 4002 );

Both in the fast task. Two nodes are two independent buses, which is exactly
what they are physically.

A gateway

Several SCADA clients sharing one RS-485 segment:

PROGRAM gateway
VAR
    bridge : MODBUS_BRIDGE;
END_VAR

bridge( SERIAL_DEVICE := '/dev/ttyUSB0', SERIAL_BAUD := 19200,
        TCP_PORT := 502, FIRST_UNIT := 1, LAST_UNIT := 32 );

(* Two alarms, because they send you to different places *)
gatewayFault := bridge.NO_PATH > 0;      (* our routing is wrong *)
fieldFault   := bridge.NO_DEVICE > 0;    (* a device is not answering *)
END_PROGRAM

Habits worth keeping

Interlock on QUALITY, never on a value alone. A stale register looks
exactly like a steady process.

Give UNKNOWN and BAD separate alarms. One is a commissioning fault, the
other is a running fault.

Read LAST_ERROR before anything else when a node will not start. It
carries the operating system's own words.

Put anything a client must not change in a read-only list. It is not a
permission somebody can alter later.

Validate what a client writes. The register is your variable, so the check
belongs in your program.

Test the failsafe by pulling the cable, on commissioning, and watch
SAFE_APPLIED. A failsafe nobody has seen fire is a failsafe nobody knows
works.

Use WORD for registers, not INT. WORD is what you can mask, shift and
take a bit of.

One limitation on Arduino targets

An ANY pin fed from a Global Variable List does not compile on a board.
The generated code needs a newer C++ standard than the ESP32 core builds with.
check passes either way, so it only appears at board build time.

Until that is fixed upstream, VALUE pins take POU locals on Arduino
targets
— which is why every example above keeps the variable and the block
in the same program. On the Runtime there is no such limit.

Next: 09 - Troubleshooting