07 - Block reference

07 - Block reference

Every block, every pin. For what they are for, see
04 - Being a device and
05 - Reading and writing.

Eleven function blocks: three you will always use, five you will use often, and three you place only when a default is not what you want.

Every block but MODBUS_NODE and MODBUS_BRIDGE takes the node on a NODE
in-out pin and returns ERROR and STATUS. The pin must be assigned at
every call — leaving it out is a compile error.

MODBUS_BRIDGE stands alone and takes no node, because a bridge is not a
client or a server: it is both ends of a wire.


MODBUS_NODE

The link. Call it first, in a fast task of its own. Eleven pins are the whole
of an ordinary link
— everything else lives on the three optional blocks
below, so it costs you nothing until you want it.

input type
TRANSPORT MODBUS_TRANSPORT where the bytes go
ROLE MODBUS_ROLE ask, answer, or both
TCP_HOST STRING(48) the device to connect to. Empty means be a server
TCP_PORT UINT 0 for 502
SERIAL_DEVICE STRING(48) serial device, e.g. /dev/ttyUSB0. Runtime only
SERIAL_BAUD DINT 0 for 19200
SERIAL_PARITY MODBUS_PARITY EVEN is the Modbus default
SERIAL_UNIT_ID BYTE the address this node answers to on a serial line, 1..247. Serial server only — a TCP server answers whatever unit id is asked for
RESET_STATS BOOL rising edge zeroes the counters MODBUS_STATUS reports
CONNECT BOOL TRUE by default. Drop it to release the port

The prefix says which transport a pin belongs to, and a pin for a transport
you are not using is ignored. SERIAL_UNIT_ID is the one people expect to need
on TCP and do not.

output type
READY BOOL the link is open
CONNECTED BOOL something is at the other end; for a server, that it is listening
CLIENTS INT clients connected. TCP server only
ERROR BOOL it did not open, or has since failed
STATUS MODBUS_RESULT why
LAST_ERROR STRING(64) the operating system's own words

The node waits one scan before opening, so a helper below may sit anywhere
in the same program — above or below. That is one millisecond of a fast task,
and it removes a placement rule nobody would remember.


MODBUS_CONFIG — optional

Tuning. Place it only where a default is not what you want.

input type
FRAMING MODBUS_FRAMING how frames are found. AUTO reads RTU on a serial line and MBAP on a socket. The pin for a converter
TIMEOUT DINT 0 measures it per device, which is almost always better than a figure you pick
RETRIES BYTE attempts after the first. 0 takes the library's
FAILSAFE DINT silence that counts as losing the client. 0 disables. Needed before MODBUS_MAP's ON_LOSS does anything
MAX_CLIENTS BYTE clients a TCP server holds at once. 0 for eight on the Runtime, two on a board. No ceiling of its own; too many for the board's memory stops the node with "out of memory for MAX_CLIENTS connections"
QUEUE UINT requests that may wait at once. 0 for 16 on a board, 64 on the Runtime
QUEUE_BYTES UINT bytes the waiting requests' values share. 0 for 1024 on a board, 16192 on the Runtime. Too much for the board stops the node with "out of memory for the request queue"
IDLE DINT close an unused connection. 0 for 60000, -1 never
RECONNECT DINT how often to retry a dropped link. Already on — 0 takes the library's two seconds; -1 turns recovery off
output type
APPLIED / ERROR / STATUS whether the settings reached the node

Automatic recovery is already on and needs no block. A link that drops is
retried every two seconds until it returns, and every watched value is made due
the moment it does. RECONNECT only paces that differently, or turns it off.

Assign TIMEOUT even when you want the default. It is the first pin, and
the editor reports a block whose first input is never assigned. TIMEOUT := 0
says "I have thought about the timeout and I want the measured one", which is
worth saying on a tuning block.


MODBUS_IDENTITY — optional

What this node answers function code 43 with.

input type
VENDOR / PRODUCT / REVISION STRING(32) its nameplate
output type
APPLIED / ERROR / STATUS whether it reached the node

Worth setting on anything somebody else will commission: six identical-looking
nodes on one segment are six nodes you can only tell apart by asking.


MODBUS_ARDUINO — optional, boards only

The pins only a board has. On the Runtime it reports
MODBUS_INVALID_ARGUMENT rather than doing nothing quietly.

input type
PORT BYTE hardware serial port number
RX_PIN / TX_PIN INT -1 for the board's own. ESP32 only
DE_PIN INT RS-485 driver enable, -1 if the board wires it
DE_HOLD DINT hold after the last byte. 0 for two character times
SSID STRING(48) WiFi network
PASSWORD STRING(63) WiFi passphrase, up to 63 characters (the WPA2 maximum)
MAC STRING(32) Ethernet. Empty takes a built-in default — a collision the moment there are two
IP STRING(32) required on WiFi and Ethernet. 'dhcp' asks a server instead
GATEWAY STRING(32) empty derives it from IP, ending .1
SUBNET STRING(32) empty uses 255.255.255.0
output type
APPLIED / ERROR / STATUS whether the settings reached the node


MODBUS_MAP

Your variables at Modbus addresses. No request pin: once bound, the variable
is the register.

input type
TABLE MODBUS_TABLE which of the four lists
ADDRESS UINT the first address
ON_LOSS MODBUS_FAILSAFE what a writable address does when the client stops. Needs FAILSAFE on the node
SAFE_VALUE DINT what MODBUS_RESET_TO_VALUE goes to. Single values only
VALUE ANY the variable to bind. Single value or fixed-bounds array
output type
BOUND BOOL the addresses are live
COUNT UINT how many addresses were taken
WRITTEN BOOL one scan, when a client wrote any of them
SAFE_APPLIED BOOL one scan, when the safe state was applied
ERROR BOOL why not
STATUS MODBUS_RESULT why

MODBUS_READ

Reads a device, on a rising edge of REQ.

input type
REQ BOOL rising edge reads. Holding it high is safe
UNIT BYTE the device's address, 1..247
FC MODBUS_READ_FC which read, named as the manual names it
ADDRESS UINT the first address on that device
LENGTH UINT 0 means "as many as are in the variable", which is almost always right
ORDER MODBUS_ORDER how a 32- or 64-bit value is laid out. Ignored for BOOL and WORD
VALUE ANY the variable to read into
output type
BUSY BOOL a level: the request is outstanding
DONE BOOL one scan, when the answers arrived
COUNT UINT how many addresses were moved
ERROR BOOL one scan, when they did not
STATUS MODBUS_RESULT why

MODBUS_WRITE

Writes a device, on a rising edge of REQ.

input type
REQ BOOL rising edge writes
UNIT BYTE the device's address. 0 broadcasts, and nobody answers
FC MODBUS_WRITE_FC MODBUS_FC_AUTO picks it from what you passed
ADDRESS UINT the first address
LENGTH UINT 0 means "as many as are in the variable"
ORDER MODBUS_ORDER word order for values wider than a register
AND_MASK / OR_MASK WORD for MODBUS_FC22_MASK_WRITE_REGISTER only
VALUE ANY the variable to write from
output type
BUSY BOOL the request is outstanding
DONE BOOL one scan, when the device confirmed it
COUNT UINT how many addresses were written
ERROR BOOL one scan, when it did not
STATUS MODBUS_RESULT why

MODBUS_WATCH

A repeating read, with a quality. Never touches the wire itself.

input type
UNIT BYTE the device's address. May change while running
FC MODBUS_READ_FC which read. May change while running
ADDRESS UINT the first address. May change while running
EVERY TIME how often. T#1s if left at T#0s. QUALITY is judged against this
LENGTH UINT 0 means "as many as are in the variable". Fixed at the first call
ORDER MODBUS_ORDER word order. May change while running
DEADBAND UINT how far the value must move to count as a change
ENABLE BOOL TRUE by default. Stops and starts in place
VALUE ANY the variable to keep up to date. Fixed at the first call
output type
WATCHING BOOL the watch is running
COUNT UINT how many addresses it covers
QUALITY MODBUS_QUALITY how much to believe VALUE right now
SEEN BOOL a value has arrived at least once
AGE TIME since it last arrived, T#0s if it never has (SEEN tells which)
FAILURES UINT reads that failed in a row
ERROR BOOL could not be set up, or its last read failed
STATUS MODBUS_RESULT why

A new UNIT, FC, ADDRESS or ORDER re-aims the same watch: QUALITY goes
back to UNKNOWN and the next read goes to the new place.

MODBUS_POINT

One value on a device, defined entirely by settings: read and re-read from its
pins every scan. See 11 - Points from settings.

input type
UNIT BYTE the device's address
FC MODBUS_PT_FC FC01..FC04 to read, FC05 / FC06 / FC16 to write
ADDRESS UINT the register or coil
DTYPE MODBUS_PT_TYPE BIT, INT16, UINT16, INT32, UINT32, FLOAT32, REG_BIT
ORDER MODBUS_ORDER word order of a 32-bit value
BIT USINT REG_BIT only: which bit, 0..15
SCALE REAL value = raw × SCALE + OFFSET. 1.0 by default
OFFSET REAL
EVERY TIME how often to read, or to send a write again. T#1s if T#0s
STALE TIME no good answer this long = lost (BAD). T#0s: 3 × EVERY
TIMEOUT TIME this device's answer time limit (radio: a few seconds). T#0s: measured
WRITE_VALUE REAL write points: the value, in engineering units
ENABLE BOOL TRUE by default. FALSE = not fitted: never asked, never ok
output type
VALUE REAL engineering units. The last good value is held while not ok
Q BOOL VALUE <> 0, for a bit
OK BOOL good or a little late. FALSE before the first answer and once lost
QUALITY MODBUS_QUALITY UNKNOWN never answered, GOOD, UNCERTAIN late, BAD lost
AGE TIME since the last good answer
FAILURES UINT failed attempts in a row
ERROR BOOL the last attempt failed, or the settings cannot work
STATUS MODBUS_RESULT why. MODBUS_INVALID_ARGUMENT for settings that cannot work

MODBUS_POINTS

The same, as a table: one block for every point on the bus.

in-out type
NODE MODBUS_NODE which node
SETTINGS ARRAY OF MODBUS_PT_CFG one row a point. Retain it
POINTS ARRAY OF MODBUS_PT_STS what each row is doing. Do not retain it
input type
RUN BOOL TRUE by default. FALSE stops asking
output type
GOOD_COUNT INT enabled rows that are ok
LOST_COUNT INT enabled rows that are not
FIRST_LOST INT the first such row, 0 when none
ERROR BOOL LOST_COUNT > 0
STATUS MODBUS_RESULT the first lost row's result
STATUS_TEXT STRING(30) pt 3 unit 5 lost, pt 2 unit 9 no answer, pt 4 bad settings

MODBUS_PT_CFG (settings): unit, fc, address, dtype, order, bit,
scale (1.0), offset, every (T#1s), stale, timeout, enable (TRUE).

MODBUS_PT_STS: w (your logic: the value to write), and the status v, q,
ok, quality, age, failures, result.


MODBUS_STATUS

How the link is doing. No inputs: it reports and changes nothing.

output type
CONNECTED BOOL there is something at the other end
CLIENTS INT clients connected, for a server
PENDING INT requests queued and not yet concluded
SENT / RECEIVED DINT frames, both directions
CHECKSUM_ERRORS DINT the bytes arrived and the maths did not agree
FRAMING_ERRORS DINT structurally impossible frames
NOISE_BYTES DINT discarded while hunting for a frame start
FRAMING_REASON STRING(160) how this link finds frames, and why, in a sentence
ERROR BOOL no such node
STATUS MODBUS_RESULT why

MODBUS_DEVICE

How one device is doing. Free while POLL is 0 — it reads the traffic your
program already makes and sends nothing. Which means a device nobody asks
anything reads as not answering
: give POLL to a device this block is the
only thing pointed at.

input type
UNIT BYTE the device's address
IDENTIFY BOOL rising edge asks for its nameplate. Once is enough
POLL DINT ask this device whether it is alive, this often. 0 watches only the traffic you already make — which answers nothing about a device nobody talks to
GONE DINT silence before ANSWERING drops. 0 uses 5000
output type
ANSWERING BOOL it has answered within GONE
SILENT DINT since it last answered, or -1 if it never has
ROUND_TRIP DINT how long it takes to reply, measured
VENDOR / PRODUCT / REVISION STRING(32) its nameplate
IDENTIFIED BOOL one scan, when the nameplate arrived
ERROR BOOL no such node, or the nameplate could not be read
STATUS MODBUS_RESULT why

MODBUS_BRIDGE

TCP clients in front, a serial segment behind. Takes no NODE; put it in the
fast task a node would go in.

input type
SERIAL_DEVICE STRING(48) the serial device behind. Runtime only
SERIAL_BAUD DINT 0 for 19200
SERIAL_PARITY MODBUS_PARITY EVEN is the Modbus default
PORT / RX_PIN / TX_PIN BYTE / INT board only
DE_PIN / DE_HOLD INT / DINT RS-485 driver enable
TCP_PORT UINT the port clients connect to. 0 for 502
FIRST_UNIT / LAST_UNIT BYTE the unit ids out on the segment
MAX_CLIENTS BYTE clients at once. 0 for eight on the Runtime, two on a board. No ceiling of its own
MAX_PENDING BYTE transactions outstanding on the serial bus. 0 for 8
PASS_OTHERS BOOL forward anything not routed, instead of refusing it
CONNECT BOOL TRUE by default
output type
READY BOOL both ends are open
CLIENTS INT clients connected
FORWARDED DINT requests sent to the serial segment
NO_PATH DINT refused: we have no route. Our problem
NO_DEVICE DINT refused: the device did not answer. Its problem
FRAMING_REASON STRING(160) how the serial segment finds frames
ERROR BOOL it did not open
STATUS MODBUS_RESULT why
LAST_ERROR STRING(64) in words

The enumerations

type values
MODBUS_TRANSPORT MODBUS_RUNTIME_SERIAL, MODBUS_RUNTIME_TCP, MODBUS_ARDUINO_SERIAL, MODBUS_ARDUINO_WIFI, MODBUS_ARDUINO_ETHERNET
MODBUS_FRAMING MODBUS_FRAMING_AUTO, MODBUS_FRAMING_RTU, MODBUS_FRAMING_ASCII, MODBUS_FRAMING_TCP
MODBUS_ROLE MODBUS_ROLE_CLIENT, MODBUS_ROLE_SERVER, MODBUS_ROLE_BOTH
MODBUS_PARITY MODBUS_PARITY_EVEN, MODBUS_PARITY_ODD, MODBUS_PARITY_NONE (8N2), MODBUS_PARITY_NONE_8N1
MODBUS_TABLE MODBUS_COILS, MODBUS_DISCRETE_INPUTS, MODBUS_HOLDING_REGISTERS, MODBUS_INPUT_REGISTERS
MODBUS_READ_FC MODBUS_FC01_READ_COILS, MODBUS_FC02_READ_DISCRETE_INPUTS, MODBUS_FC03_READ_HOLDING_REGISTERS, MODBUS_FC04_READ_INPUT_REGISTERS
MODBUS_WRITE_FC MODBUS_FC_AUTO, MODBUS_FC05_WRITE_SINGLE_COIL, MODBUS_FC06_WRITE_SINGLE_REGISTER, MODBUS_FC15_WRITE_MULTIPLE_COILS, MODBUS_FC16_WRITE_MULTIPLE_REGISTERS, MODBUS_FC22_MASK_WRITE_REGISTER
MODBUS_ORDER MODBUS_ORDER_ABCD, MODBUS_ORDER_CDAB, MODBUS_ORDER_BADC, MODBUS_ORDER_DCBA
MODBUS_QUALITY MODBUS_QUALITY_UNKNOWN, MODBUS_QUALITY_GOOD, MODBUS_QUALITY_UNCERTAIN, MODBUS_QUALITY_BAD
MODBUS_FAILSAFE MODBUS_HOLD_LAST_VALUE, MODBUS_RESET_TO_VALUE
MODBUS_PT_FC MODBUS_PT_FC01_READ_COILS, MODBUS_PT_FC02_READ_DISCRETE_INPUTS, MODBUS_PT_FC03_READ_HOLDING_REGISTERS, MODBUS_PT_FC04_READ_INPUT_REGISTERS, MODBUS_PT_FC05_WRITE_COIL, MODBUS_PT_FC06_WRITE_REGISTER, MODBUS_PT_FC16_WRITE_REGISTERS
MODBUS_PT_TYPE MODBUS_PT_BIT, MODBUS_PT_INT16, MODBUS_PT_UINT16, MODBUS_PT_INT32, MODBUS_PT_UINT32, MODBUS_PT_FLOAT32, MODBUS_PT_REG_BIT
MODBUS_RESULT see 06 - Diagnostics

Not in this version

FC 23, read/write multiple registers. It needs a second buffer and a second
address, which would leave four pins dead on every ordinary write. Use a write
followed by a read.

FC 43 as a general call. It appears as the identity outputs on
MODBUS_DEVICE instead, which is what anybody actually wants from it.

Next: 08 - Patterns