UT_ALARM_BEACON — Flash alarm numbers on a single lamp
UT_ALARM_BEACON — Flash alarm numbers on a single lamp
For sites with one fault lamp and no HMI. It steps through every active alarm in
turn and flashes its number, so a tech can read the fault code off the lamp.
Pins
| Pin | Type | Default | What to wire | |
|---|---|---|---|---|
| in | Enable |
BOOL | TRUE | FALSE: lamp off, Code 0; on again starts over |
| out | Lamp |
BOOL | ||
| out | Code |
INT | Alarm number being shown (0 = none) | |
| out | Active |
BOOL | Any alarm (also while Enable is off) |
|
| inout | Alarms |
ARRAY[*] OF BOOL | Alarm n = element n (write with coils) | |
| inout | Data |
UT_BEACON_DATA |
Record UT_BEACON_DATA
| Field | Type | Default | Meaning |
|---|---|---|---|
style |
UT_BEACON_STYLE | UT_BEACON_COUNT | UT_BEACON_COUNT: the number as that many short flashes. UT_BEACON_BINARY: long = 1, short = 0, most significant bit first |
bits |
INT | 6 | Binary: bits shown (1..15). A number too big for bits uses as many as it needs |
shortTime |
TIME | T#250ms | Short flash (count, and binary 0) |
longTime |
TIME | T#1s | Long flash (binary 1) |
gapTime |
TIME | T#500ms | Lamp off between flashes |
pauseTime |
TIME | T#3s | Lamp off between numbers |
steadyWhenNone |
BOOL | FALSE | Lamp on steady when no alarm is active (a "healthy" light); it goes off for gapTime before the first flash |
code |
INT | Status: same as Code |
|
activeCount |
INT | Status: alarms active |
How it works
- Alarm number = index − lower bound + 1, so
ARRAY[0..9]element 0 is alarm 1. - After an idle spell it starts from the lowest active alarm, then shows each active
alarm in turn and goes round again. - A number that has started is always finished, even if its alarm clears meanwhile;
then it moves on. Changingstylemid-number takes effect at the next number. - Each flash, gap and pause lasts at least one PLC scan, and is rounded up to whole scans.
| Number | Count | Binary, 6 bits |
|---|---|---|
| 1 | 1 short | SSSSSL |
| 9 | 9 short | SSLSSL |
| 31 | 31 short | SLLLLL |
Using it
VAR Faults : ARRAY[1..20] OF BOOL; END_VAR
Faults[1] := P1Overload;
Faults[2] := P2Overload;
Faults[3] := HighLevel;
Beacon(Enable := TRUE, Alarms := Faults, Data := BeaconCfg);
FaultLamp := Beacon.Lamp;
Last updated 2 hours ago