UT_TOTALISER — Totals from any source (flow, energy, production, runtime)

UT_TOTALISER — Totals from any source (flow, energy, production, runtime)

Accumulates a quantity from whatever the field gives you. Choose the method for
the meter you have; everything else (periods, interval records, batch target, rate
output, units, retention) works the same for every method.

Pins

Pin Type Default What to wire
in Value REAL 0.0 Flow rate (RATE), meter register (REGISTER/CHANGE), sampled value (SAMPLE/SNAPSHOT). The editor wants it wired: with PULSE or COUNT, wire 0.0
in Pulse BOOL FALSE Pulse input (PULSE method)
in Count UDINT 0 The counter's reading (COUNT method), e.g. a hardware library's pulse count
in Active BOOL TRUE Only totalise while TRUE (e.g. pump running). In RUNTIME mode, it's the running signal
in Clock DT DT#1970-01-01-00:00:00 Local real-time clock for the hour and day totals and the interval end times (leave unwired to switch the hour and day totals off)
in Rollover BOOL FALSE Rising edge: close the user period (shift change, batch end). SNAPSHOT: take a reading
in ResetBatch BOOL FALSE Rising edge: zero the batch total
out Total REAL Lifetime total
out Batch REAL Resettable batch/trip total
out Rate REAL Measured rate in outUnit per rateUnit (from pulses, counts or register changes too)
out BatchDone BOOL Batch ≥ batchTarget
out IntervalDone BOOL TRUE for one scan when an interval record has just been written
inout Data UT_TOTAL_DATA

Which meter, which method

Meter countMethod How to wire it
Pulse meter counted by the PLC scan (reed switch, pulse output) UT_TM_PULSE Pulse signal to Pulse. Set pulseValue (quantity per pulse) and inUnit. Up to one pulse per two scans.
Fast pulse meter counted outside the scan (the hardware library's pulse count) UT_TM_COUNT The hardware library's count (UDINT) to Count. Set pulseValue and inUnit; rolloverAt only if the counter wraps below 4 294 967 296 (a 16-bit counter: 65536); maxStep (counts).
4–20 mA or RS485 flow-rate transmitter UT_TM_RATE The scaled rate to Value. Set rateUnit (per second, minute, hour or day), inUnit and lowCutoff.
RS485 meter's own volume register UT_TM_REGISTER The register to Value. Set inUnit, rolloverAt (if the register wraps) and maxStep.

Methods — countMethod : UT_TOTAL_METHOD

Value Use for How it counts
UT_TM_RATE (0, default) 4–20 mA flow meter, power transducer Integrates Value over real time, in rateUnit. Values below lowCutoff (and negative ones) count as 0.
UT_TM_PULSE Pulse/reed-switch meters, kWh pulse outputs, product counters Each rising edge adds pulseValue (K-factor). Rate from the pulse period.
UT_TM_REGISTER A meter's own running total read over Modbus/MQTT (m³, kWh) Adds each increase of Value. Handles register rollover at rolloverAt (a wrap of less than half the range). A drop (meter reset, swap, comms glitch reading 0) counts nothing, and when the value comes back above where it was only the part above it counts. Steps bigger than maxStep are rejected. Each rejected step or drop counts in rejectedSteps.
UT_TM_CHANGE Any value whose change you want to total in both directions (tank volume in/out, stock level) Adds rises to totalIn and falls to totalOut, once the value has moved deadband from the last counted value. Total, batch, periods and Rate add the rises, or the falls with changeCountFalls
UT_TM_RUNTIME No meter: estimate from run time While Active, adds nominalRate × time (e.g. pump rated 12 m³/h).
UT_TM_SAMPLE Slow or noisy signals, or fixed-interval accounting Every sampleTime, adds Value × sampleTime (rate) or Value (if sampleAsQuantity)
UT_TM_SNAPSHOT Readings to log at fixed times (meter reads, levels) Every sampleTime (or Rollover edge), stores Value as snapshot/prevSnapshot and their difference as period. Nothing is totalised
UT_TM_COUNT (7) A pulse count kept outside the scan, on Count Each count adds pulseValue. The step is worked out in UDINT, so every count is exact at any reading, and the 32-bit wrap (4 294 967 295 → 0) is counted exactly. rolloverAt sets a lower wrap. A drop of less than half the range is a wrap; any other drop means the counter restarted (for example its hardware rebooted): it counted up again from 0, so Count itself is counted, not a huge step. Steps, and restarts, bigger than maxStep counts are rejected and counted in rejectedSteps. The first reading is the starting point. Value is not used

COUNT or REGISTER? A counter that starts again from 0 when its device restarts is
COUNT. A meter that keeps its own total through a power cut is REGISTER (a drop
there is a glitch or a meter swap, never a restart from 0).

Units

inUnit is the unit of pulseValue, of the register or count quantity, of the
rate on Value and of nominalRate. outUnit is the unit of every total, of the
interval record and of Rate. When both are set, every addition and the rate are
converted; when either is UT_VOL_NONE (the default) nothing is converted.

UT_VOL_UNIT Unit
UT_VOL_NONE (0, default) No conversion
UT_VOL_L litre
UT_VOL_M3 cubic metre (1 000 L)
UT_VOL_ML megalitre (1 000 000 L), not millilitre

Example: a meter giving 1 pulse per 10 L, totals in m³: pulseValue := 10.0,
inUnit := UT_VOL_L, outUnit := UT_VOL_M3. Each pulse adds 0.01 m³.
A 4–20 mA transmitter scaled in L/s, totals in m³: rateUnit := UT_PER_SEC,
inUnit := UT_VOL_L, outUnit := UT_VOL_M3; Rate is then in m³/s.
scale still multiplies on top (meter calibration). lowCutoff, maxStep and
rolloverAt stay in the units of Value.

Interval records

Every interval (default 15 minutes) the block writes one record for the IoT
platform and sets IntervalDone for one scan:

Field Type Meaning
intervalVolume REAL The quantity counted in that interval, in outUnit
intervalEnd DT When the interval ended (from Clock)
intervalTotal REAL The lifetime total at that moment
intervalSeq UDINT +1 every interval: a gap in the numbers is a missed record

The fields hold until the next record; only IntervalDone is one scan.

  • With Clock: intervals end on whole multiples of interval since midnight
    (15 min: :00, :15, :30, :45), and intervalEnd is that boundary time. The first
    interval after power-up is a part interval (it starts at power-up). A clock jump
    forward closes one record covering the gap; a clock set back closes nothing.
  • Without Clock: intervals are counted from power-up, every interval of
    running time, and intervalEnd stays at DT#1970-01-01-00:00:00. Let the platform
    time-stamp the records.
  • interval := T#0s switches the records off. Changing interval starts again.
  • The records are not kept over a power cut: intervalSeq starts at 0 again.
    The platform stores the history and works out monthly figures.

Record UT_TOTAL_DATA

Settings

Field Type Default Meaning
saveEvery TIME T#12h How often the totals are saved for a power cut (T#0s = not kept). Resets, presets, user rollovers and the end of a run (Running falls, once per stop) are saved at once
countMethod UT_TOTAL_METHOD UT_TM_RATE How to count (method is a reserved word)
rateUnit UT_RATE_UNIT UT_PER_HOUR Time unit of Value (RATE/SAMPLE), of nominalRate and of Rate
inUnit UT_VOL_UNIT UT_VOL_NONE Unit of pulseValue, the register or count and the rate on Value (see Units)
outUnit UT_VOL_UNIT UT_VOL_NONE Unit of every total and of Rate
pulseValue REAL 1.0 PULSE / COUNT: quantity per pulse, in inUnit
nominalRate REAL 0.0 RUNTIME method
lowCutoff REAL 0.0 RATE: ignore values below this (meter noise at zero flow), in the units of Value; Rate below it shows 0
rolloverAt REAL 0.0 REGISTER: the register wraps at this value (0 = never). COUNT: the counter wraps at this value, 2 .. 4 294 967 296 (0 = the full 32 bits)
maxStep REAL 0.0 REGISTER / COUNT: reject single steps bigger than this, in the units of Value (COUNT: counts) (0 = off)
deadband REAL 0.0 CHANGE: ignore smaller changes
changeCountFalls BOOL FALSE CHANGE: the total, batch, periods (today, yesterday…), BatchDone and Rate count the falls instead of the rises. A sump's volume with Active := pump running then totals the pumped volume (net of any inflow during the run)
sampleTime TIME T#1m SAMPLE / SNAPSHOT
sampleAsQuantity BOOL FALSE SAMPLE: each sample is a quantity, not a rate
batchTarget REAL 0.0 BatchDone threshold (0 = off)
scale REAL 1.0 Multiplier on every addition (meter calibration)
interval TIME T#15m Interval records (T#0s = off)

Commands

  • HMI: cmdResetBatch, cmdRollover.
  • Admin or technician only, through the platform; never on an operator HMI:
    cmdResetTotal (resets total, totalIn, totalOut; needs cmdConfirm in the
    same write), cmdConfirm, cmdPreset + presetTotal (0 to 1E12; anything else
    is ignored). The block cannot check who wrote them: keep them out of operator
    screens.

Each command acts once and is cleared.

Status

Field Type Meaning
total, batch, rate REAL
totalIn / totalOut REAL CHANGE method
period / prevPeriod REAL User period (Rollover). SNAPSHOT: the last two differences
thisHour / lastHour REAL With Clock wired
today / yesterday REAL With Clock wired
snapshot / prevSnapshot REAL SNAPSHOT method
intervalVolume, intervalEnd, intervalTotal, intervalSeq REAL, DT, REAL, UDINT The last interval record
pulses, rejectedSteps UDINT Diagnostics (not kept over a power cut)
wrnRegisterJump BOOL A register or count step was rejected, or the register fell (until the next good step)
wrnPulseTooFast BOOL Pulses at the scan-rate limit (held 5 s)
wrnBadValue BOOL Value is not a number or infinite (not checked for PULSE, RUNTIME, COUNT), or would add over 1E9 in one scan: ignored
wrnConfig BOOL A setting is invalid: an unknown method or unit; pulseValue not above 0; nominalRate, lowCutoff, rolloverAt, maxStep, deadband, batchTarget or scale negative, not a number or infinite; COUNT rolloverAt outside 2 .. 4 294 967 296; a negative sampleTime, interval or saveEvery. Nothing else changes (the totals stay safe: a NaN addition is ignored)

Compliance metering

  • Counting in the PLC (PULSE or COUNT): the total lives in the PLC, so set a short
    saveEvery, for example T#1m. A power cut then loses at most that much counting.
  • REGISTER reads the meter's own total, so the meter keeps counting while the PLC is
    off and nothing is lost.
  • The platform logs the interval records.
  • NZ regulations require 15-minute records, sent daily, for takes of 5 L/s or more.

Notes

  • Power cut: kept as of the last save (saveEvery; resets, presets and user
    rollovers at once): every total and period total in the status table, with the
    hour and day they belong to, the snapshots and the register or count reading, so
    nothing is counted twice. After the restart REGISTER counts what the meter recorded
    while the PLC was off; COUNT counts a counter that restarted from 0 (or kept
    counting). Not kept: the interval records, pulses and rejectedSteps (start at
    0), the warnings.
  • Totals are kept in millionths of a unit in 64-bit integers, plus the part of a
    millionth left over, so they stay exact on every board (LREAL is only 32-bit on some small boards).
    A total of 10 000 000 still counts single units.
  • Pulses are seen once per scan: the maximum is one pulse per two scans (half the
    task rate, e.g. 50 Hz at 10 ms). wrnPulseTooFast is raised at that limit. Count
    faster meters outside the scan and use COUNT.
  • COUNT: the count is a UDINT on Count, exact at any reading (a REAL would lose
    single counts past 16 777 216). Leave rolloverAt at 0 for a 32-bit counter.
  • A counter that restarts close to rolloverAt looks like a wrap. maxStep limits
    what such a step can add.
  • Hour and day totals follow the clock's hour and day changes, also after a power
    cut that spanned midnight or a month end (the day before the cut becomes
    yesterday). A jump of more than one hour or day leaves the skipped period at 0;
    a clock set back closes nothing and never makes a negative period. Wire a
    local clock: the runtime's CURRENT_DT is UTC.
  • After a restart, REGISTER counts what the meter recorded while the PLC was off,
    also when the reading is 0 for a while (comms down) before or after the cut.