UT_CMD — Commands from two masters, with local / remote
UT_CMD — Commands from two masters, with local / remote
A site often has two masters that both command the same device: the local
panel HMI and a remote SCADA. UT_CMD sits between them and the device:
- Each master writes its own variables, and nobody clears them. The block
reacts to each change, so a SCADA that rewrites the same value every poll,
or a value left set, acts only once. - Local / remote: with
RemoteEnabledFALSE (a technician on site) remote
requests are refused, counted and reported, except a stop. - Stop wins: a stop and a start in the same scan give the stop.
- The outputs are one-scan requests you wire into the device record's
cmdXxx
andcmdMode.
Pins
| Pin | Type | Default | What to wire | |
|---|---|---|---|---|
| in | LocalCmd |
DWORD | 0 | The local master's command bits (bit 0 stop, bit 1 start … you choose the map). Each bit acts on its rising edge. Wire it (0 if the local master has no command bits) |
| in | RemoteCmd |
DWORD | 0 | The remote master's command bits, same map |
| in | LocalMode |
INT | −1 | The local master's mode request: acts when it changes to 0 or more. −1 = no request |
| in | RemoteMode |
INT | −1 | The remote master's mode request |
| in | RemoteEnabled |
BOOL | TRUE | FALSE: local control. The remote master is refused (see remoteStop). Wire a Local / Remote switch here |
| out | Cmd |
DWORD | Accepted command bits, for one scan | |
| out | Mode |
INT | Accepted mode request for one scan, else −1. Wire into the record's cmdMode |
|
| out | Refused |
BOOL | One scan: a remote request was refused | |
| out | Cmd0 … Cmd7 |
BOOL | Bits 0 to 7 of Cmd, for Ladder and FBD. Wire into the record's cmdStop, cmdStart, cmdReset … |
|
| inout | Data |
UT_CMD_DATA | Settings and status |
Record UT_CMD_DATA
| Field | Type | Default | Meaning |
|---|---|---|---|
stopMask |
DWORD | 16#00000001 | The stop / off bits. When one is accepted, every other bit and mode request of that scan is dropped |
localOnlyMask |
DWORD | 0 | Bits only the local master may give, e.g. a reset that needs someone on site. Refused from remote at all times |
remoteModes |
WORD | 16#FFFF | The mode codes the remote master may ask for: bit n = code n. 16#0005 = Off (0) and Auto (2) only. Codes above 15 are refused from remote |
remoteStop |
BOOL | TRUE | Under local control, the remote stop bits and mode 0 (Off) still act. FALSE refuses them too |
lastSource |
UT_CMD_FROM | status: who gave the last accepted request: UT_FROM_NONE · UT_FROM_LOCAL · UT_FROM_REMOTE |
|
lastCmd |
DWORD | status: its command bits | |
lastMode |
INT | −1 | status: its mode request (−1 = none) |
refused |
UDINT | status: remote requests refused (not kept over a power cut) | |
statusCode |
UT_STATUS | status: see Status codes | |
statusText |
STRING(30) | status: statusCode in words |
How it works
What the masters write.
- Command bits: set the bit, and clear it again before the next command (an
HMI momentary button does this: 1 while pressed, 0 when released). A master that
rewrites the same value every poll is fine: only a change from 0 to 1 acts. - Mode: write the code (0 Off, 1 Hand, 2 Auto, 3 OOS, or the device's own
codes). It acts when the value changes. To ask for the same mode again after
someone else changed it, write −1 (or any negative number) first. The block
passes codes 0 and up through; the device checks them.
In each scan:
- Each master's new bits (0 → 1) and new mode request are found.
- Remote requests are filtered: with
RemoteEnabledFALSE only thestopMask
bits and mode 0 pass (and only whileremoteStop);localOnlyMaskbits and
modes not inremoteModesnever pass. A refused request setsRefusedfor one
scan, adds 1 torefusedand is shown in the status. - Stop wins: if a stop bit or mode 0 is accepted, every other bit and any
other mode request in that scan is dropped. Otherwise, when both masters ask for
a mode in the same scan, the local one is used. Cmd,Cmd0…Cmd7andModecarry the result for one scan.
Nothing acts on the first scan after a power cut or PLC start: the block only
reads the masters' values. A command bit or mode left set over a power cut does not
act, so UT_PU_OFF (a mode that comes back Off) can't be undone by a value SCADA
left behind.
Status codes
statusCode is a UT_STATUS (an HMI reads its number); statusText is the same in words.
statusCode |
statusText |
When |
|---|---|---|
UT_ST_LOCAL_REMOTE |
Local and remote |
RemoteEnabled TRUE |
UT_ST_LOCAL |
Local control |
RemoteEnabled FALSE |
UT_ST_REFUSED_LOCAL |
Refused: local control |
A remote request was refused under local control |
UT_ST_REFUSED_LOCAL_ONLY |
Refused: local only |
A localOnlyMask bit, or a mode not in remoteModes |
A refusal stays shown until the next accepted request, or until
RemoteEnabled changes.
Using it
Bit map for this pump: bit 0 stop, bit 1 start, bit 2 reset (on site only).
Pump1Cmd(LocalCmd := HMI_P1_Cmd, RemoteCmd := SCADA_P1_Cmd,
LocalMode := HMI_P1_Mode, RemoteMode := SCADA_P1_Mode,
RemoteEnabled := NOT LocalSwitch, Data := Pump1CmdData); (* localOnlyMask := 16#4 *)
Pump1.cmdStop := Pump1Cmd.Cmd0;
Pump1.cmdStart := Pump1Cmd.Cmd1;
Pump1.cmdReset := Pump1Cmd.Cmd2;
Pump1.cmdMode := Pump1Cmd.Mode;
The masters write only HMI_P1_* and SCADA_P1_*, never Pump1.cmd….