UT_CMD — Commands from two masters, with local / remote

UT_CMD — Commands from two masters, with local / remote

A site often has two masters that both command the same device: the local
panel HMI and a remote SCADA. UT_CMD sits between them and the device:

  • Each master writes its own variables, and nobody clears them. The block
    reacts to each change, so a SCADA that rewrites the same value every poll,
    or a value left set, acts only once.
  • Local / remote: with RemoteEnabled FALSE (a technician on site) remote
    requests are refused, counted and reported, except a stop.
  • Stop wins: a stop and a start in the same scan give the stop.
  • The outputs are one-scan requests you wire into the device record's cmdXxx
    and cmdMode.

Pins

Pin Type Default What to wire
in LocalCmd DWORD 0 The local master's command bits (bit 0 stop, bit 1 start … you choose the map). Each bit acts on its rising edge. Wire it (0 if the local master has no command bits)
in RemoteCmd DWORD 0 The remote master's command bits, same map
in LocalMode INT −1 The local master's mode request: acts when it changes to 0 or more. −1 = no request
in RemoteMode INT −1 The remote master's mode request
in RemoteEnabled BOOL TRUE FALSE: local control. The remote master is refused (see remoteStop). Wire a Local / Remote switch here
out Cmd DWORD Accepted command bits, for one scan
out Mode INT Accepted mode request for one scan, else −1. Wire into the record's cmdMode
out Refused BOOL One scan: a remote request was refused
out Cmd0 … Cmd7 BOOL Bits 0 to 7 of Cmd, for Ladder and FBD. Wire into the record's cmdStop, cmdStart, cmdReset …
inout Data UT_CMD_DATA Settings and status

Record UT_CMD_DATA

Field Type Default Meaning
stopMask DWORD 16#00000001 The stop / off bits. When one is accepted, every other bit and mode request of that scan is dropped
localOnlyMask DWORD 0 Bits only the local master may give, e.g. a reset that needs someone on site. Refused from remote at all times
remoteModes WORD 16#FFFF The mode codes the remote master may ask for: bit n = code n. 16#0005 = Off (0) and Auto (2) only. Codes above 15 are refused from remote
remoteStop BOOL TRUE Under local control, the remote stop bits and mode 0 (Off) still act. FALSE refuses them too
lastSource UT_CMD_FROM status: who gave the last accepted request: UT_FROM_NONE · UT_FROM_LOCAL · UT_FROM_REMOTE
lastCmd DWORD status: its command bits
lastMode INT −1 status: its mode request (−1 = none)
refused UDINT status: remote requests refused (not kept over a power cut)
statusCode UT_STATUS status: see Status codes
statusText STRING(30) status: statusCode in words

How it works

What the masters write.

  • Command bits: set the bit, and clear it again before the next command (an
    HMI momentary button does this: 1 while pressed, 0 when released). A master that
    rewrites the same value every poll is fine: only a change from 0 to 1 acts.
  • Mode: write the code (0 Off, 1 Hand, 2 Auto, 3 OOS, or the device's own
    codes). It acts when the value changes. To ask for the same mode again after
    someone else changed it, write −1 (or any negative number) first. The block
    passes codes 0 and up through; the device checks them.

In each scan:

  1. Each master's new bits (0 → 1) and new mode request are found.
  2. Remote requests are filtered: with RemoteEnabled FALSE only the stopMask
    bits and mode 0 pass (and only while remoteStop); localOnlyMask bits and
    modes not in remoteModes never pass. A refused request sets Refused for one
    scan, adds 1 to refused and is shown in the status.
  3. Stop wins: if a stop bit or mode 0 is accepted, every other bit and any
    other mode request in that scan is dropped. Otherwise, when both masters ask for
    a mode in the same scan, the local one is used.
  4. Cmd, Cmd0…Cmd7 and Mode carry the result for one scan.

Nothing acts on the first scan after a power cut or PLC start: the block only
reads the masters' values. A command bit or mode left set over a power cut does not
act, so UT_PU_OFF (a mode that comes back Off) can't be undone by a value SCADA
left behind.

Status codes

statusCode is a UT_STATUS (an HMI reads its number); statusText is the same in words.

statusCode statusText When
UT_ST_LOCAL_REMOTE Local and remote RemoteEnabled TRUE
UT_ST_LOCAL Local control RemoteEnabled FALSE
UT_ST_REFUSED_LOCAL Refused: local control A remote request was refused under local control
UT_ST_REFUSED_LOCAL_ONLY Refused: local only A localOnlyMask bit, or a mode not in remoteModes

A refusal stays shown until the next accepted request, or until
RemoteEnabled changes.

Using it

Bit map for this pump: bit 0 stop, bit 1 start, bit 2 reset (on site only).

Pump1Cmd(LocalCmd := HMI_P1_Cmd, RemoteCmd := SCADA_P1_Cmd,
         LocalMode := HMI_P1_Mode, RemoteMode := SCADA_P1_Mode,
         RemoteEnabled := NOT LocalSwitch, Data := Pump1CmdData);  (* localOnlyMask := 16#4 *)
Pump1.cmdStop := Pump1Cmd.Cmd0;
Pump1.cmdStart := Pump1Cmd.Cmd1;
Pump1.cmdReset := Pump1Cmd.Cmd2;
Pump1.cmdMode := Pump1Cmd.Mode;

The masters write only HMI_P1_* and SCADA_P1_*, never Pump1.cmd….