UT_DUTY — Duty / assist / standby for any group of motors

UT_DUTY — Duty / assist / standby for any group of motors

Shares a demand ("I need N units running") across a group of motor-driven units:
fans, compressors, blowers, heater banks, cooling towers, or pumps when you
don't need UT_PUMP_STATION's level logic. It handles rotation,
failover, staggered starts and exercise of idle units.

The group is an array of the units' motor records. Each UT_MOTOR* block uses
one element as its Data, and its Auto command comes from the group automatically
(grpActive / grpRun). A unit is available when it is in Auto and ready (healthy,
interlock and permissive made).

Pins

Pin Type Default What to wire
in Required INT 1 How many units should run (0 or negative = none)
in Rotate BOOL FALSE Rising edge: change the lead now
out RunningCount INT Units running (any mode)
out Shortfall BOOL Fewer available than Required
out Lead INT Array index of the lead unit
inout Units ARRAY[*] OF UT_MOTOR_DATA The motor records of the group (any size, any lower bound)
inout Data UT_DUTY_DATA Group record

Record UT_DUTY_DATA

Field Type Default Meaning
rotation UT_ROTATE_MODE UT_ROT_EACH_START FIXED · EACH_START (the lead moves on when the group goes to none) · HOURS (fewest run hours leads, decided when the group starts from none) · INTERVAL
rotateInterval TIME T#24h INTERVAL (0 = never)
fixedLead INT 1 FIXED: array index of the lead (out of range = the first)
stageDelay / destageDelay TIME T#5s / T#2s Minimum gap between starts / stops
failoverDelay TIME T#10s A called unit not running in this time is skipped, the next is called. A unit still in its own restartDelay hands over to another, and is called again when no other is left
swapWhileRunning BOOL FALSE Rotate without stopping: start the new lead, then stop the old one. FALSE: the old one stops first
countHandUnits BOOL TRUE A unit running in Hand counts toward Required
exerciseInterval / exerciseTime TIME T#0s / T#30s Run idle units briefly (0 = off)
cmdRotate BOOL HMI command: move the lead on now (acts once, cleared)
lead, runningCount, calledCount, availableCount, shortfall, exercising Status
statusCode UT_STATUS What the group is doing, or what holds it back (see Status)
faultId UT_FAULT The setting a configuration status is about (UT_F_NO_UNITS); else UT_F_NONE
statusText STRING(30) The status in words, for a person looking at the PLC
statusUnit DINT The unit (array index) the status is about; one below the array's first index when none
rotateIn TIME status: INTERVAL: time to the next rotation (0 for the other rotations, or rotateInterval 0)
nextExerciseIn TIME status: time until the next idle unit is exercised: the one idle longest (0 with exercise off, or while one is exercised)
timeLeft TIME status: the countdown that goes with the status: stage, failover, destage or restart delay, or the exercise run still to go (0 = none)

Each unit's rank is in Units[i].grpRank (1 = lead). Run time per unit for
UT_ROT_HOURS is counted by the group in Units[i].grpRunTime, for every unit.

Status

statusCode and statusText say the one main thing the group is doing, or what
holds it back. The group has no faults of its own: each unit's motor status says why
it tripped. The most important reason wins: held / waiting > running > idle. With
Required above 0 and no unit running or starting (its run command out), the status
is always a held one. The unit a status is about is statusUnit (an array index),
the time left is in timeLeft, and the counts are runningCount, calledCount and
availableCount. The text is rebuilt only when the status changes. The numbers are
in conventions.

statusCode Words When
UT_ST_IDLE_NO_DEMAND Idle: no demand Required 0 (or less), nothing running
UT_ST_RUN_HAND Running: Hand Nothing wanted; units run in Hand
UT_ST_STARTING Starting Unit statusUnit called, not running yet; skipped if not running within timeLeft (the failover delay)
UT_ST_STOPPING Stopping More called than wanted: the next release after destageDelay (timeLeft); or a released unit running down
UT_ST_RUNNING Running Units running (any mode); runningCount of Required
UT_ST_EXERCISING Exercising Unit statusUnit is on an exercise run (timeLeft)
UT_ST_RESTART_DELAY Waiting: restart delay Unit statusUnit waits out its motor's restartDelay (timeLeft), or the group is short only because a unit is in its restart delay
UT_ST_FAILOVER Waiting: start failed, next A unit did not run (failover, or its motor tripped while starting); unit statusUnit is called instead
UT_ST_STAGE_DELAY Waiting: stage delay More units wanted, the next start after stageDelay (timeLeft)
UT_ST_SHORTFALL Shortfall: too few available Fewer units available (in Auto and ready, not skipped) or running in Hand than Required; availableCount says how many are
UT_ST_CONFIG Config: no units in array faultId UT_F_NO_UNITS: an empty array

How it works

  • Units are called one at a time, best rank first, at least stageDelay apart and
    only once the last one called is running. Extra units are released one at a time,
    worst rank first, at least destageDelay apart.
  • A unit that trips or leaves Auto (Hand, Off, OOS) is released at once and replaced.
    A called unit that does not run within failoverDelay is skipped until it has been
    unavailable or the group next starts from none (skip memory: first 32 units). A
    unit coming back is not swapped in while another is doing the job. A unit that is
    only waiting out its own restartDelay (just stopped, or after a power cut) has not
    failed: it hands over to another unit if there is one, and is called again once no
    other is left, so a lone compressor restarts when its delay ends.
  • Exercise: one idle, available unit at a time (any unit in the array) whose motor has
    been stopped for exerciseInterval (its offTime) runs exerciseTime. It does not count toward Required, only
    touches units in Auto, and counts as a start for stageDelay. nextExerciseIn
    shows when the next one is due.
  • rotateIn counts down to the next INTERVAL rotation and starts again at each
    rotation (also one by Rotate / cmdRotate).
  • Power cut: only the lead is kept (saved at once when it changes, which is
    rare), so the rotation carries on instead of the first unit always leading after
    frequent power cuts. Run times for HOURS (grpRunTime) start again at 0, also when the
    motor records are RETAIN (equal times go in turn from the kept lead), and so does
    the exercise timing (the motors' offTime counts from power-up). Every grpRun starts cleared
    and units start one at a time again. The motors keep their own modes. A motor ignores grpRun on its first scan,
    so a retained record never starts it, and it clears grpActive each scan: if UT_DUTY stops being called,
    its motors go back to their own AutoCmd on the next scan. Call order does not
    matter (after the motors, they follow one scan later).

Using it

VAR Fans : ARRAY[1..3] OF UT_MOTOR_DATA; END_VAR
Duty(Required := FansNeeded, Units := Fans, Data := DutyCfg);
F1(AutoCmd := FALSE, Feedback := F1_Aux, Overload := F1_OL, Data := Fans[1]);
(* … F2, F3 … *)

AutoCmd must be wired (the editor checks it) but is not used while the group owns
the motor.