UT_LINK_SUPERVISOR — Escalating recovery of a remote site's comms link

UT_LINK_SUPERVISOR — Escalating recovery of a remote site's comms link

Gets a remote site back online by itself when its link to SCADA or the IoT platform
dies: first a modem restart, then a modem power cycle, then one controlled reboot of
the controller, then modem retries further and further apart. The reboots are counted
and limited per day, and the count is kept over the reboot itself, so a dead link can
never make the controller reboot in a loop.

Pins

Pin Type Default What to wire
in LinkOk BOOL FALSE The link works: NOT UT_WATCHDOG.CommsFail on the SCADA heartbeat, the modem's connected flag. Unwired: the link is down from power-up
in RebootAllowed BOOL TRUE FALSE: no reboot now (e.g. while equipment runs); the reboot waits and happens once allowed, in the same outage
in Clock DT DT#1970-01-01-00:00:00 Local time, for the reboots-per-day count. Unwired or not set: a rolling window instead (see below)
out RestartModem BOOL TRUE for pulseTime: restart the modem (its restart input or command)
out PowerCycle BOOL TRUE for powerOffTime: switch the modem's power off (a relay or HAT power, TRUE = off)
out RebootReq BOOL Reboot the controller; held until it does
out LinkDown BOOL The link is down
inout Data UT_LINK_SUPERVISOR_DATA
Field Type Default Meaning
restartAfter TIME T#30s Link down this long: restart the modem (0 = step off)
powerCycleAfter TIME T#5m Link down this long: power cycle the modem (0 = step off)
rebootAfter TIME T#10m Link down this long: reboot the controller once (0 = step off)
pulseTime TIME T#1s RestartModem pulse length
powerOffTime TIME T#10s How long the modem stays off
maxBackoff TIME T#10m The longest wait between retries
maxRebootsPerDay INT 3 Reboots allowed in one day (0 = never reboot)
rebootSaveWait TIME T#3s The count is saved this long before RebootReq
countWindow TIME T#24h No clock: the count starts again this long (running time) after the first counted reboot
cmdResetReboots BOOL HMI: set the reboot count to 0 (acts once, on its rising edge, and is cleared)
linkOk BOOL Status: the link is up
downFor TIME Status: time the link has been down (0 while up)
timeLeft TIME Status: time to the next step (0 = none)
nextStep INT Status: the next step: 1 modem restart, 2 power cycle, 3 reboot, 0 none
rebootPending BOOL Status: the reboot is due but RebootAllowed is FALSE
rebootsToday INT Status: reboots counted in this day or window (kept over a reboot or power cut)
restarts, powerCycles, outages UDINT Status: since power-up
lastDownFor TIME Status: how long the last outage lasted
statusCode UT_STATUS Status: what it is doing (codes below)
statusText STRING(30) Status: statusCode in words. The times are in downFor and timeLeft
countResetIn TIME Status: no clock, reboots counted: time until the count starts again (0 = none)

Status codes

statusCode is a UT_STATUS (an HMI reads its number); statusText is the same in
words. downFor says how long the link has been down, timeLeft the time to the step.

statusCode statusText When
UT_ST_LINK_OK Link OK The link is up
UT_ST_LINK_RESTART Link down: modem restart Waiting for the modem restart step
UT_ST_LINK_POWER_CYCLE Link down: power cycle Waiting for the power cycle step
UT_ST_LINK_REBOOT Link down: reboot Waiting for the reboot step
UT_ST_LINK_REBOOT_WAITS Link down: reboot not allowed The reboot is due, RebootAllowed FALSE
UT_ST_LINK_NO_STEPS Link down: no more steps Every step done or off, no retries
UT_ST_LINK_RETRY Link down: retry Modem retries with the back-off
UT_ST_LINK_REBOOTING Link down: rebooting RebootReq is on (or the count was saved and it follows)

How it works

  • The steps are timed from when the link went down (or from power-up, if it is down
    then). Each is optional (its time 0 = off). The outputs are pulses of their full
    length, even if the link comes back meanwhile.
  • Retries: once the restart and power cycle steps are past, the modem is tried
    again (a power cycle, or a restart if the power cycle step is off). The first retry
    comes restartAfter after the last step (powerCycleAfter if the restart step is
    off), each wait twice the one before, up to maxBackoff. The back-off starts again
    once the link has stayed up for maxBackoff; a short flap keeps it.
  • Reboots: at most maxRebootsPerDay. The reboot is counted and saved first;
    RebootReq follows rebootSaveWait later, so the count survives the reboot. At the
    limit no reboot is asked for, however long the link stays down: the retries go on.
  • The day: with a set Clock (2000 or later), the count starts again at each date
    change. Without one (unwired, or the clock not set yet), it starts again
    countWindow of running time after the first counted reboot: a rolling window. Its
    progress is saved in 24 steps (one an hour by default), so a reboot or a power cut
    loses at most one step and the window only gets longer; time switched off does not
    count. countResetIn shows when it ends.
  • Kept over a power cut: only the reboot count, its day and the window's progress.

Using it

LinkSup(LinkOk := NOT ScadaWd.CommsFail, RebootAllowed := NOT P1.Running, Clock := Now,
        Data := LinkSupCfg);
ModemRestart := LinkSup.RestartModem;
ModemPowerOff := LinkSup.PowerCycle;      (* relay contact in the modem's supply *)
IF LinkSup.RebootReq THEN
  (* ask the controller to reboot *)
END_IF;