UT_WATCHDOG — Comms / heartbeat monitor and generator

UT_WATCHDOG — Comms / heartbeat monitor and generator

Tells you a remote device, link or task is alive: it watches a value that should
keep changing (a heartbeat bit or counter from a remote PLC, a Modbus register, an
MQTT message counter) and raises CommsFail when it stops. It also produces a
heartbeat for the other side to watch.

Pins

Pin Type Default What to wire
in Beat BOOL FALSE Heartbeat bit from the remote (any change counts)
in Counter DINT 0 Or a counter/register from the remote (any change counts)
in Enable BOOL TRUE FALSE: not monitored (Ok and CommsFail off); on again starts over
in Reset BOOL FALSE Rising edge: reset a held failure (panel button)
out Ok BOOL Remote alive (off at start until the first change)
out CommsFail BOOL No change for timeout
out HeartbeatOut BOOL Toggles every beatPeriod; send this to the remote
out HeartbeatCount DINT Increments every beatPeriod
inout Data UT_WATCHDOG_DATA

Record UT_WATCHDOG_DATA

Field Type Default Meaning
timeout TIME T#10s No change for this long = link dead. Make it longer than the remote's beat and the PLC scan (T#0s: always failed)
recoverTime TIME T#0s Must be alive this long before Ok returns (and AUTO clears CommsFail)
beatPeriod TIME T#1s HeartbeatOut toggles every beatPeriod (0 = off)
failReset UT_RESET_MODE UT_RST_AUTO AUTO clears by itself; RETRY as AUTO three times an hour, then as MANUAL; MANUAL holds CommsFail until reset
cmdReset BOOL HMI: reset a held failure
cmdResetCount BOOL HMI: failures and downTime back to 0
ok BOOL Status: same as Ok
lastChange TIME Status: time since the remote last changed
failures UDINT Status: comms failures
downTime TIME Status: total time dead, from each timeout to the next change

How it works

  • The failure is a UT_PROTECT trip, so the reset modes work as on every
    device. A reset while the link is still dead is refused.
  • A link that drops out again while recovering fails again (and is counted again).
  • A link that is dead at start counts as a failure once timeout has passed.
  • The heartbeat keeps going when Enable is off. A beatPeriod shorter than the scan
    toggles every scan.
  • A held command acts once.
  • Power cut: nothing is kept. failures and downTime start at 0, a held (MANUAL)
    failure is forgotten, and a link that is still dead fails again after timeout.

Using it

LinkWd(Counter := RemoteHeartbeatReg, Data := LinkWdCfg);
RemoteHeartbeatOut := LinkWd.HeartbeatCount;     (* write to the remote *)
CommsAlarm(In := LinkWd.CommsFail, Data := Alarms[5]);