UT_STATUS_TEXT — A status in words (function), and UT_STATUS_KIND

UT_STATUS_TEXT — A status in words (function), and UT_STATUS_KIND

Two functions for the status every device block keeps in its record
(see conventions):

  • UT_STATUS_TEXT turns a statusCode and a faultId into a short line of words,
    such as Running: Auto, Waiting: restart delay or Latched: overload.
  • UT_STATUS_KIND tells you the kind of a statusCode: normal, held, warning,
    fault or configuration. Use it for a colour on the HMI or to filter messages.

The device blocks already call UT_STATUS_TEXT for their own statusText. Use these
functions in your own blocks, or to show a status from somewhere else.

Pins

UT_STATUS_TEXT

Pin Type Default What to wire
in Status UT_STATUS UT_ST_IDLE A block's statusCode
in Fault UT_FAULT UT_F_NONE The same block's faultId. Only the warning, fault and configuration statuses use it
returns STRING(30) The status in words, at most 30 characters

UT_STATUS_KIND

Pin Type Default What to wire
in Status UT_STATUS UT_ST_IDLE A block's statusCode
returns UT_KIND UT_KIND_NORMAL (0) · UT_KIND_HELD · UT_KIND_WARNING · UT_KIND_FAULT · UT_KIND_CONFIG
MyData.statusText := UT_STATUS_TEXT(MyData.statusCode, MyData.faultId);
(* UT_ST_RESTART_DELAY            -> 'Waiting: restart delay'  *)
(* UT_ST_FAULT_RESET, UT_F_OVERLOAD -> 'Latched: overload'      *)
(* UT_ST_CONFIG, UT_F_VALVE_TYPE  -> 'Config: valve type'       *)

PumpIsFaulted := UT_STATUS_KIND(Pump1Data.statusCode) = UT_KIND_FAULT;

How it works

The words. Each normal or held status has its own words (Idle, Running: Auto, Blocked: interlock). The warning, fault and configuration statuses are a
prefix that says how the fault behaves, followed by the words of the fault or
setting in Fault:

Status Prefix Meaning
UT_ST_FAULT Fault: A trip that resets by itself once the cause has gone (AUTO)
UT_ST_FAULT_RETRY Retrying: A trip that retries (RETRY), retries still left
UT_ST_FAULT_RESET Latched: A trip that needs a reset (MANUAL)
UT_ST_FAULT_LOCKED Locked: A RETRY trip whose retries are used up: it needs a reset
UT_ST_WARNING Warning: It runs, but something needs looking at
UT_ST_WARN_SETTING Setting: A setting is not valid; a safe value is used instead
UT_ST_CONFIG Config: A setting is not valid and keeps the device off until it is fixed

So UT_ST_FAULT_RETRY with UT_F_NO_FEEDBACK reads Retrying: no run feedback,
and UT_ST_WARN_SETTING with UT_F_FLC reads Setting: full load current. A
setting with no words of its own reads a setting.

The text never holds a number. The time left, the pump number or the count that
goes with a status is in the block's record (timeLeft, statusUnit,
runningCount and so on), so an HMI can show it beside the words.

The full lists of statuses, faults and their words are in
conventions.md, Status.

The kinds. UT_STATUS_KIND returns the kind of any status. Use it rather than the
status's number: the statuses after UT_ST_CONFIG are not in the kind groups.

Kind What it means Example
UT_KIND_NORMAL Idle, off, running, moving Running: Auto
UT_KIND_HELD Asked to run, but something holds it back (not a fault) Waiting: restart delay
UT_KIND_WARNING It runs, but something needs looking at Warning: current signal
UT_KIND_FAULT A protection holds it off, or it runs in a fallback Latched: overload
UT_KIND_CONFIG A setting keeps it off Config: valve type

Cost. Both are plain functions with no memory of their own. The device blocks
call UT_STATUS_TEXT only when the status or the fault changes, not every scan.