09 - Troubleshooting

09 - Troubleshooting

Arranged by what you are seeing, not by what is wrong.

The node will not start

READY is FALSE and ERROR is TRUE.

Read LAST_ERROR first. It carries the operating system's own words, which say
far more than a code can:

LAST_ERROR
"No such file or directory" the DEVICE path is wrong. Check what actually appeared: ls /dev/ttyUSB*
"Permission denied" the runtime user cannot open the port. On Linux, add it to the dialout group
"Address already in use" another program has the TCP port. Often a second copy of this one still running
"no serial device named" DEVICE was left empty on a serial transport
"a serial server needs UNIT_ID, 1 to 247" ROLE is server or both, and SERIAL_UNIT_ID is 0
"a TCP client needs HOST; leave it empty to be a server" ROLE is client on TCP with no HOST
"that transport needs a board, not the Runtime" TRANSPORT is a MODBUS_ARDUINO_* value on the Runtime. Use a MODBUS_RUNTIME_* one
"MBAP framing has no meaning on a serial line" FRAMING := MODBUS_FRAMING_TCP on a serial transport
"ASCII inside a TCP stream is not a Modbus transport" FRAMING := MODBUS_FRAMING_ASCII on a network transport
"TRANSPORT and FRAMING cannot change once started" something is writing those pins while the program runs
"out of memory for MAX_CLIENTS connections" the board cannot hold that many TCP clients. Lower MODBUS_CONFIG's (or MODBUS_BRIDGE's) MAX_CLIENTS
"out of memory for the request queue" the board cannot hold the queue MODBUS_CONFIG's QUEUE / QUEUE_BYTES ask for. Lower them

The node retries every two seconds, so a fault you fix is picked up without a
restart.

Nothing answers

STATUS is MODBUS_TIMEOUT on every request.

Work down this list. It is in the order that finds faults fastest.

1. Look at MODBUS_STATUS. If CHECKSUM_ERRORS, FRAMING_ERRORS and
NOISE_BYTES are all flat while SENT climbs, no bytes are arriving at
all. That is wiring, not protocol: wrong port, A and B swapped, transmit and
receive swapped, or the device is off. Stop reading this list and check the
wiring.

If any of them is climbing, bytes are arriving and you have a protocol or
signal-quality problem. Carry on.

2. Baud rate and parity. A mismatch produces a steady stream of
CHECKSUM_ERRORS — the bytes arrive, the maths does not agree. Note that
MODBUS_PARITY_NONE means 8N2, which is what the specification requires
when parity is off. A device set to 8N1 needs MODBUS_PARITY_NONE_8N1.

3. Unit id. The commonest single mistake. Check MODBUS_DEVICE.SILENT:
-1 means that unit id has never answered anything, which is a wrong address
rather than a dead device.

4. Termination and bias. NOISE_BYTES climbing steadily on an idle bus is
a floating line. 120 Ω at each far end, and bias resistors somewhere.

5. Is it RTU over TCP? If you are on TCP and getting silence, it is very
likely a terminal server. Set FRAMING := MODBUS_FRAMING_RTU. See
03 - The node block.

The device answers but says no

STATUS is MODBUS_REFUSED.

This is good news. Frames are going out, arriving, being understood and
being answered. Everything below the application layer works. You are arguing
about an address or a function code.

likely cause
the address is not in that device check the manual's map
off-by-one many manuals number registers from 1 and the wire numbers them from 0. "Register 40001" is usually address 0 in the holding registers
the wrong list address 40 in the holding registers is not address 40 in the input registers
the function code is not supported an older device may implement FC 06 and not FC 16. Name MODBUS_FC06_WRITE_SINGLE_REGISTER
too many at once some devices accept fewer than the specification's 125 registers. Read a smaller range

The values are nonsense

A float reads 4.6e-41, or 1.7e38, or a huge negative number.

The address is right and the word order is wrong. Try MODBUS_ORDER_CDAB if
you were on ABCD, or the other way round. See
05 - Reading and writing.

A number is right but a thousand times out. The device is publishing in
different units, or with an implied decimal point. That is in its manual, not
on the wire.

A signed value reads as a huge positive number. A WORD holds 0 to 65535.
Use WORD_TO_INT for a signed one.

Half the array is right and half is untouched. A length mistake. Check
COUNT against what you expected — that pin exists for exactly this.

Requests are refused before they go out

STATUS
MODBUS_INVALID_ARGUMENT a zero count, a LENGTH past the end of the variable, a quantity past what one request may carry (2000 bits or 125 registers for a read), or a BOOL aimed at a register list
MODBUS_DUPLICATE an identical request is already outstanding. Not an error — this is what stops a held REQ flooding the bus
MODBUS_SUPERSEDED a newer write to the same address replaced this one. Not an error
MODBUS_QUEUE_FULL you are asking faster than the bus can answer. Watch fewer things, or less often - or raise MODBUS_CONFIG's QUEUE / QUEUE_BYTES if the bursts are expected
MODBUS_LINK_DOWN on a block other than the node, the NODE pin has no started node behind it. Check node.READY and that the node is called first

Frames go missing on RS-485

FRAMING_ERRORS climbing, or reads that work intermittently.

Read MODBUS_STATUS.FRAMING_REASON. It says which rule the link is using and
why, in a sentence.

RTU ends a frame with three and a half character times of silence, and several
ordinary things destroy that silence:

  • a USB-to-RS-485 adapter, which delivers bytes in clumps on its own
    schedule;
  • a virtual serial port, which has no timing at all;
  • a busy PLC scan, if the node's task is not fast enough.

If the node is not in a fast task of its own, put it there first — see
10 - Scan rate. If the link genuinely cannot hold the timing,
MODBUS_FRAMING_ASCII removes the requirement entirely at the cost of twice
the bytes.

A watched value stopped updating

QUALITY is MODBUS_QUALITY_BAD.

It was arriving and has stopped. Check FAILURES — one is a hiccup, ten is a
device that has gone — and MODBUS_DEVICE.SILENT for how long.

Note the backoff: a device that stops answering is retried progressively less
often, down to one attempt in sixteen, so that one dead unit does not consume
the segment. It will pick itself up when the device returns; it just will not
do it instantly.

QUALITY is MODBUS_QUALITY_UNKNOWN and stays there.

It has never arrived. That is not a running fault — it is a wrong address,
a wrong unit id, a wrong list, or a device that was never fitted. Check
STATUS on the watch block for which.

QUALITY flickers to MODBUS_QUALITY_UNCERTAIN.

The value is arriving late. Either EVERY is shorter than the bus can
manage, or the node's task is too slow, or there are too many watches. All
three are in 10 - Scan rate.

A client cannot read my PLC

ROLE must be MODBUS_ROLE_SERVER or MODBUS_ROLE_BOTH.

SERIAL_UNIT_ID must match what the client is asking for — on serial. On TCP the
unit id does not matter.

MODBUS_MAP.BOUND must be TRUE. If it is FALSE with
MODBUS_INVALID_ARGUMENT, the variable and the list disagree: a BOOL in a
register list, a number in a coil list, an unwired VALUE pin, or an
ARRAY [*], which is a view rather than a variable.

The addresses are where you said, from the array's lower bound. Check
COUNT.

The failsafe never fires

ON_LOSS needs FAILSAFE on a MODBUS_CONFIG block. Without a silence to measure
there is no loss to act on, and the map block cannot tell you that because
nothing is wrong with it.

MODBUS_RESET_TO_VALUE applies to a single value only — a range has no one
safe value. Bind the few addresses that need a safe state individually.

Test it by pulling the cable and watching SAFE_APPLIED.

It works on the Runtime and not on the board

An ANY pin fed from a Global Variable List does not compile for a board.
Move the variable into the POU that calls the block. See
08 - Patterns.

MODBUS_ARDUINO reports MODBUS_INVALID_ARGUMENT on the Runtime. Every
pin on it describes hardware a board has and a Linux runtime does not. It says
so rather than doing nothing quietly.

MODBUS_ARDUINO_ETHERNET says "define MODBUS_ENABLE_ETHERNET to build
Ethernet in"
.
Installing the Arduino Ethernet library is not enough on its
own: the Arduino builder adds a user library to the include path only when it
sees a plain #include for it, and a header behind a conditional is
invisible to that scanner. Add MODBUS_ENABLE_ETHERNET to the project's build
flags and it compiles in.

The node will not start and says "set IP, or 'dhcp' to ask for one". A
fixed address is required on WiFi and on Ethernet — see
03 - The node block. Write IP := 'dhcp' if you
genuinely want a server-assigned one.

Ethernet says "no Ethernet controller found on SPI". The shield or module
is not answering — usually the chip select pin, or it is not seated.

Ethernet says "Ethernet cable unplugged". The controller is there and the
link is not. Ethernet is behind a build flag, because
compiling it in unconditionally breaks the link step on boards that have no
Ethernet at all.

Serial goes nowhere on an ESP32-S3. With USB CDC on boot, Serial is the
USB device and not a UART. The node falls back to Serial0, which is UART0.
Use PORT := 1 or PORT := 2 with RX_PIN and TX_PIN on a MODBUS_ARDUINO
block for a real port.

Next: 10 - Scan rate

STATUS says MODBUS_WRONG_TASK

The block is in a different task from its node. It does nothing until it is
moved: OpenPLC runs each task on a thread of its own, and a block in another
task would be inside the node while the node's own scan is. Move it into the
node's program, and hand your application the value through a global — see
10 - Scan rate.