UT_MODE_SELECT — Off / Hand / Auto / Out of service

UT_MODE_SELECT — Off / Hand / Auto / Out of service

The mode logic every device block uses, and usable on its own for anything that
needs a mode. The HMI mode starts at Off and is retained. After a power cut
it comes back as PowerUp says: as it was (the default), or Off.

Pins

Pin Type Default What to wire
in Source UT_MODE_SOURCE UT_SRC_HMI UT_SRC_HMI · UT_SRC_SWITCH · UT_SRC_REMOTE
in SwHand / SwAuto BOOL FALSE Selector switch contacts
in AllowOOS BOOL TRUE FALSE: code 3 (out of service) is not offered
in PowerUp UT_POWERUP UT_PU_LAST What the mode does after a power cut or a PLC stop / start (below). A device block passes its record's powerUp here
in ForceOff BOOL FALSE TRUE holds the mode at Off, in every source. The choice underneath is kept and comes back when it drops
out Mode UT_MODE The mode now
out EnteredOff BOOL One scan: just changed to Off (reset-by-Off uses this)
out Changed BOOL One scan: the mode just changed
out HmiChoice UT_MODE The HMI's choice (what CmdMode last selected), whatever the source and ForceOff
out HeldOff BOOL Mode is Off because of ForceOff, or because a selector is waiting to be moved after power-up
inout CmdMode INT HMI request: 0 Off · 1 Hand · 2 Auto · 3 OOS. Set back to −1

How it works

Source Mode
UT_SRC_HMI The HMI's choice (retained)
UT_SRC_SWITCH The selector: Hand, Auto, neither = Off, both made = Off
UT_SRC_REMOTE Selector Off and Hand act locally; selector Auto hands control to the HMI's choice

CmdMode acts once, when a new value arrives: when it differs from the value
read the scan before. The block then sets it back to −1 ("no request"). A value
held there (a debugger force, a master that rewrites it) acts once. Any other code
that is not a mode (4 and up, a negative number, or 3 while AllowOOS is FALSE)
is ignored and set back to −1. If two masters (a panel HMI and SCADA) both change
the mode, put UT_CMD in front.

Power-up (a power cut, or a PLC stop / start):

PowerUp HMI mode Selector found in Hand or Auto
UT_PU_LAST (default) Comes back as it was left, from the first scan Acts at once
UT_PU_OFF Back to Off: the operator selects it again Held at Off (HeldOff) until it is moved. With UT_SRC_REMOTE only a selector in Hand is held; its Auto position hands over to the HMI, which is Off

UT_PU_LAST suits an unattended pump that must carry on after a power cut;
UT_PU_OFF suits plant that someone must restart on purpose (a quarry conveyor).
A motor in Hand needs a fresh start press after a power cut in either case (the
motor blocks never keep a Hand start).

ForceOff holds the mode at Off while it is TRUE: a plant-wide off, a
maintenance isolator's auxiliary contact. EnteredOff and reset-by-Off work as for
any change to Off. The HMI's choice is still accepted and kept (HmiChoice) and
takes effect when ForceOff drops.

There is no local / remote lock on CmdMode here: this block can't tell which
master wrote it. Local / remote belongs in UT_CMD (which knows the
source) or in the selector with UT_SRC_REMOTE.