UT_DOSE — Dosing and batching (batch, flow-paced, timed)

UT_DOSE — Dosing and batching (batch, flow-paced, timed)

Doses chemical, fertiliser or product three ways:

  • Batch: deliver a target quantity, with fast/slow (dribble) stages and in-flight
    compensation (stops early by the amount still flowing after the stop), which can be
    learned automatically. Used for tank filling, recipe ingredients and irrigation shots.
  • Flow-paced (proportional): dose in proportion to the water flow. Used for
    fertigation, chlorination, pH correction feed-forward and stock-water additives.
    It drives a dosing pump by speed (%) or by stroke pulses.
  • Timed: X seconds on every Y minutes while enabled.

Pins

Pin Type Default What to wire
in Start BOOL FALSE BATCH: rising edge starts a dose (or resumes a held one). FLOW/TIMED: dose while TRUE
in Target REAL 0.0 BATCH quantity (0 = use Data.target)
in Actual REAL 0.0 BATCH: delivered so far (meter total, UT_TOTALISER.Batch, scale weight)
in Flow REAL 0.0 FLOW: carrier water flow, per flowPer (e.g. m³/h, or L/s with flowPer := UT_PER_SEC)
in Hold BOOL FALSE Pause while TRUE
in Abort BOOL FALSE End the dose (no start while TRUE)
in Interlock BOOL TRUE FALSE pauses dosing (e.g. carrier pump not running, so no dosing into a dead line)
in Reset BOOL FALSE Rising edge: reset MANUAL protections
out Fast BOOL BATCH fast feed / main valve. FLOW/TIMED: dosing pump run
out Slow BOOL BATCH slow (dribble) feed. Never on with Fast: for a coarse + fine valve pair, open the fine valve on Fast OR Slow
out Rate REAL FLOW: dosing pump speed %. TIMED: maxRate while on
out RateRaw UINT Rate as 0..65535 for %QW
out PulseOut BOOL FLOW: stroke pulses for pulse-input dosing pumps
out Done BOOL BATCH complete (until the next start)
out Busy BOOL A dose is in progress (held or not)
out Fault / Warning BOOL
out Remaining REAL BATCH: target − delivered
inout Data UT_DOSE_DATA

Record UT_DOSE_DATA

Field Type Default Meaning
saveEvery TIME T#12h How often doses and dosedTotal are saved for a power cut (T#0s = not kept)
doseMode UT_DOSE_MODE UT_DOSE_BATCH UT_DOSE_BATCH (0) · UT_DOSE_FLOW · UT_DOSE_TIMED. A change takes effect when idle
Batch
target REAL 0.0 Used when the Target pin is 0. No target: the start is refused with a configBad warning
slowAt REAL 0.0 Change to slow when this much remains (0 = no slow stage)
preact REAL 0.0 In-flight compensation: stop this much early (not a number = 0). The preact in use (preactActive) is never more than half the batch's target
learnPreact BOOL FALSE Correct the preact in use (preactActive) by half of each dose's error. Doses more than 25 % off are not learned from; it stays between 0 and half the target. Changing preact restarts the learning from it
tolerance REAL 0.0 ± allowed; outside it → outOfTolerance (0 = not checked)
settleTime TIME T#2s Wait after stopping before the result is taken
actualIsTotal BOOL FALSE Actual is a running total: the dose is Actual minus its value at the start
Flow-paced
flowPer UT_RATE_UNIT UT_PER_HOUR The time unit of Flow, pumpCapacity and required: UT_PER_SEC, UT_PER_MIN, UT_PER_HOUR, UT_PER_DAY
ratio REAL 0.0 Dose units per flow unit (e.g. L of product per m³ of water). Required rate = Flow × ratio per flowPer
pumpCapacity REAL 0.0 Dosing pump output at 100 %, units per flowPer (e.g. L/h). Rate = required / capacity. 0 with pulseVolume set: a pulse pump, dosed as required
pulseVolume REAL 0.0 Dose per stroke pulse (PulseOut; 0 = not used)
pulseWidth TIME T#200ms Pulse on time, and the least off time (each at least one scan)
minFlow REAL 0.0 No dosing below this carrier flow
maxRate REAL 100.0 % cap (below 0 or not a number = 0)
Timed
onTime / offTime TIME T#10s / T#5m Starts with the on part. A pause stops the clock. offTime 0 = always on
Protections
noFlow (bit 1) UT_PROTECTION TRIP · 30 s · RETRY BATCH: Actual not rising while feeding. TRIP holds the dose (quantity kept); RETRY feeds again after recover
maxTime (bit 2) UT_PROTECTION OFF BATCH: whole dose (holds included) too long (delay = limit). TRIP ends the dose
overCapacity (bit 3) UT_PROTECTION WARN · AUTO FLOW: the required rate is above the pump's capacity at maxRate. TRIP stops dosing until it clears
outOfTolerance (bit 4) UT_PROTECTION WARN · AUTO BATCH result outside tolerance; shown until the next start or a reset. TRIP blocks the next start until it clears
retryWindow TIME T#1h RETRY counts
HMI
cmdStart BOOL BATCH: start or resume. FLOW/TIMED: run until Abort / cmdAbort. Acts once, on its rising edge: one held TRUE doses one batch, never a second
cmdAbort BOOL End the dose (wins over cmdStart in the same scan)
cmdHold BOOL Hold until the next start
cmdReset BOOL Reset MANUAL protections. After a MANUAL reset a held batch needs a start to carry on

Every cmdXxx acts once, on its rising edge, and is cleared by the block. A SCADA
master that rewrites cmdStart every poll would start a new batch after each one
finishes (an overdose): put UT_CMD in front of it.
| Status | | | |
| phase | UT_DOSE_PHASE | | UT_DP_IDLE, UT_DP_FAST, UT_DP_SLOW, UT_DP_SETTLE, UT_DP_HELD, UT_DP_DONE, UT_DP_ABORTED, UT_DP_DOSING, UT_DP_WAITING (FLOW below minFlow or paused, TIMED off part) |
| modeActive, targetActive | | | The dose in progress |
| delivered, lastDelivered, lastError | REAL | | This dose; the last one; last batch delivered − target |
| preactActive | REAL | | Preact in use (learned) |
| required, rate | REAL | | FLOW: product rate needed (units per flowPer); Rate % |
| pulses | UDINT | | Stroke pulses given |
| doses | UDINT | | Batch doses completed (aborted ones are not counted) |
| dosedTotal | REAL | | Everything dosed (batch, flow and timed), kept as of the last save |
| held | BOOL | | Paused (Hold, cmdHold, Interlock, a trip) |
| configBad, fault, warning, faultCode : DWORD | | | Bit 0 = configBad |
| statusCode | UT_STATUS | | What it is doing, or what holds it back (see Status codes) |
| faultId | UT_FAULT | | The fault, warning or setting the status is about (UT_F_NONE when none) |
| statusText | STRING(30) | | statusCode and faultId in words, e.g. Dosing fast. The quantities are in delivered / targetActive, the speed in rate |
| doseTime | TIME | | How long the dose in progress has run, holds included (the last dose's once it ends) |
| timeLeft | TIME | | The countdown the status shows: TIMED on / off time left, the settle time left, the maxTime left while a batch doses (maxTime in use), a fault's recover / retry wait |
| stopReason | UT_STOP | | Why the last dose ended (see below; UT_STOP_NONE = none since power-up), kept until the next one ends |
| lastFaultCode | DWORD | | The faultCode bits of the last trip, kept after it clears, until the next trip |
| lastFault | UT_FAULT | | The last trip, e.g. UT_F_DOSE_NO_FLOW, kept the same way |
| trips | UDINT | | Trips since power-up (not kept over a power cut) |

Why the dose ended (stopReason, a UT_STOP; an HMI reads its number):

stopReason When
UT_STOP_DEMAND_ENDED FLOW / TIMED: Start dropped
UT_STOP_MAX_RUN BATCH: maxTime (TRIP) ended it
UT_STOP_DONE BATCH: the target was delivered and the result taken
UT_STOP_ABORTED The Abort pin
UT_STOP_ABORT_CMD cmdAbort

An interlock, Hold or a trip (no flow) pauses a dose; they do not end it.

Status codes

statusCode is a UT_STATUS and faultId a UT_FAULT (an HMI reads their numbers);
statusText is the two in words, changed only when one of them changes. The one main
thing, in the order config, fault, held, warning, normal, idle. The quantities are in
delivered and targetActive, the pump speed in rate, the countdown in timeLeft.

statusCode faultId statusText When
UT_ST_IDLE Idle No dose
UT_ST_DONE Idle: done After the last batch completed
UT_ST_ABORTED Idle: aborted After the last batch was aborted
UT_ST_DOSE_FAST Dosing fast BATCH fast stage
UT_ST_DOSE_SLOW Dosing slow BATCH slow (dribble) stage
UT_ST_SETTLING Settling BATCH stopped, waiting settleTime for the result
UT_ST_DOSE_FLOW Dosing: flow-paced FLOW dosing (rate; 0 with a pulse pump)
UT_ST_DOSE_TIMED Dosing: timed TIMED on part
UT_ST_DOSE_NEXT Timed: waiting next dose TIMED off part
UT_ST_INTERLOCK Blocked: interlock Interlock FALSE during a dose
UT_ST_PAUSED_HOLD Paused: Hold input Hold during a dose
UT_ST_PAUSED_START Paused: press Start cmdHold, or a MANUAL reset, during a dose
UT_ST_LOW_CARRIER Waiting: carrier flow low FLOW: Flow 0 or below minFlow
UT_ST_WARNING UT_F_ACTUAL_NAN Warning: Actual not a number BATCH: the last value is held
UT_ST_WARNING UT_F_FLOW_NAN Warning: Flow not a number FLOW: not dosing
UT_ST_WARN_SETTING UT_F_SETTING Setting: a setting See Bad settings: a safe value is used
UT_ST_WARNING the protection Warning: no dose flow A protection set to WARN
UT_ST_FAULT the protection Fault: no dose flow A protection set to TRIP with AUTO reset (timeLeft: the recover once the cause has gone)
UT_ST_FAULT_RESET the protection Latched: no dose flow TRIP with MANUAL reset
UT_ST_FAULT_RETRY the protection Retrying: no dose flow TRIP with RETRY (the protection's retries; timeLeft)
UT_ST_FAULT_LOCKED the protection Locked: no dose flow RETRY, maxRetries used up: reset needed
UT_ST_CONFIG UT_F_NO_TARGET Config: no target set BATCH start refused: no target
UT_ST_CONFIG UT_F_NO_CAPACITY Config: no capacity / ratio FLOW started without a capacity or pulse volume, or a bad ratio
UT_ST_CONFIG UT_F_TIMED_ON_OFF Config: timed on / off time TIMED started with a negative time
UT_ST_CONFIG UT_F_DOSE_MODE Config: dose mode doseMode not one of the three

The protection is UT_F_DOSE_NO_FLOW (no dose flow), UT_F_DOSE_TOO_LONG (dose too long),
UT_F_PUMP_TOO_SMALL (pump too small) or UT_F_TOLERANCE (out of tolerance), the first
tripped in that order.

Power cut

Kept: doses and dosedTotal, as of the last save (saveEvery). Not kept: a dose
in progress and the learned preact. After a power-up a batch doser is idle and nothing
starts by itself
, even with Start still on: a new Start edge (or cmdStart)
starts a new dose of the full target; a batch is never resumed. The preact in use
starts again from the preact setting. FLOW and TIMED are different: Start is a
level (dose while TRUE), so if Start is still on at power-up the flow-paced or timed
dosing carries on at once (from the start of a fresh on-time). A cmdStart latch is not
kept: after a power cut it needs Start or a new cmdStart.

Bad settings

  • Nothing doses: an unknown doseMode (taken only when idle); TIMED with a negative
    onTime or offTime (a negative off time would never stop). configBad, status UT_ST_CONFIG.
  • Warning, safe values (configBad, bit 0, status Setting: a setting): preact negative or not a
    number (0: stops at the target); slowAt, tolerance, ratio, pumpCapacity,
    pulseVolume, minFlow negative or not a number; maxRate outside 0..100 or not a
    number (clamped, NaN = 0); a negative settleTime, pulseWidth (0) or saveEvery
    (nothing kept); a negative retryWindow (the default 1 h); an unknown flowPer (per
    hour).
  • A pulseVolume so small that more than a million stroke pulses would be owed: the
    extra pulses are dropped (the pulse count never overflows).
Last updated 2 hours ago