UT_LIMIT — Four independent alarm levels (HH / H / L / LL)
UT_LIMIT — Four independent alarm levels (HH / H / L / LL)
Checks a value against up to four levels. Each level is fully independent: its
own setpoint, deadband, delay, response (off / warning / trip) and reset mode
(auto-recover, retry or latch). Each has its own output, so you can use HH alone,
treat L as a warning only, or latch LL but let HH recover by itself. Each level
works as a UT_LEVEL_CHECK.
Pins
| Pin | Type | Default | What to wire | |
|---|---|---|---|---|
| in | In |
REAL | 0.0 | The value (e.g. UT_ANALOG_IN.Value) |
| in | Inhibit |
BOOL | FALSE | Suppress all levels (start-up, maintenance) |
| in | Reset |
BOOL | FALSE | Rising edge: clear MANUAL levels whose condition has gone |
| out | HiHi |
BOOL | High-high in effect | |
| out | Hi |
BOOL | High in effect | |
| out | Lo |
BOOL | Low in effect | |
| out | LoLo |
BOOL | Low-low in effect | |
| out | Trip |
BOOL | Any level whose response is TRIP is in effect | |
| out | Warning |
BOOL | Any level whose response is WARN is in effect, or wrnConfig |
|
| inout | Data |
UT_LIMIT_DATA |
Record UT_LIMIT_DATA
Four UT_LEVELs: hiHi, hi, lo, loLo.
| Default | hiHi |
hi |
lo |
loLo |
|---|---|---|---|---|
sp |
90 | 80 | 20 | 10 |
response |
TRIP | WARN | WARN | TRIP |
reset |
AUTO | AUTO | AUTO | AUTO |
delay |
2 s | 2 s | 2 s | 2 s |
deadband |
1.0 | 1.0 | 1.0 | 1.0 |
recover / maxRetries |
10 s / 3 | 10 s / 3 | 10 s / 3 | 10 s / 3 |
Each level's status: active, tripped, retries, count, timeLeft.
| Field | Type | Default | Meaning |
|---|---|---|---|
retryWindow |
TIME | T#1h | RETRY counts trips within this window |
cmdReset |
BOOL | HMI: as the Reset pin (acts once, on its rising edge; cleared by the block) |
|
value |
REAL | Status: the value checked | |
inhibited |
BOOL | Status: Inhibit is on |
|
wrnBadInput |
BOOL | Status: the value is NaN or infinite; every level holds its state | |
orderCheck |
BOOL | TRUE | Check the setpoint order HH > H > L > LL among the levels in use |
wrnConfig |
BOOL | Status: setpoints out of order, or a level's setting invalid | |
activeLevel |
INT | Status: the most severe level in effect: 0 none, 1 HH, 2 H, 3 L, 4 LL | |
timeLeft |
TIME | Status: the countdown the status shows (a level's delay, or a recover / retry wait) | |
statusCode |
UT_STATUS | Status: what it is doing (codes below) | |
faultId |
UT_FAULT | Status: the level the status is about (UT_F_HIGH_HIGH, UT_F_HIGH, UT_F_LOW, UT_F_LOW_LOW), the bad value or the setting; UT_F_NONE when none |
|
statusText |
STRING(30) | Status: statusCode and faultId in words, e.g. Latched: high-high |
Status codes
statusCode is a UT_STATUS and faultId a UT_FAULT (an HMI reads their numbers); statusText is the two in words.
statusCode |
faultId |
statusText |
When |
|---|---|---|---|
UT_ST_OK |
UT_F_NONE |
OK |
No level in effect, nothing counting |
UT_ST_OK |
the level | OK |
A level's delay is counting (the most severe one: HH, LL, H, L); timeLeft shows it |
UT_ST_INHIBITED |
Blocked: inhibit |
Inhibit is on |
|
UT_ST_WARNING |
UT_F_VALUE_BAD |
Warning: value not a number |
wrnBadInput: every level holds its state |
UT_ST_WARNING |
the level | Warning: high |
A level set to WARN is in effect |
UT_ST_WARN_SETTING |
UT_F_SP_ORDER |
Setting: setpoint order |
orderCheck found the setpoints out of order |
UT_ST_WARN_SETTING |
UT_F_LEVEL_SETTING |
Setting: a level |
A level's setpoint, deadband or times are invalid, or a negative retryWindow |
UT_ST_FAULT |
the level | Fault: high-high |
A TRIP level in effect, AUTO reset (timeLeft: the recover still to go) |
UT_ST_FAULT_RETRY |
the level | Retrying: high-high |
RETRY, retries left (the level's retries; timeLeft: the wait) |
UT_ST_FAULT_LOCKED |
the level | Locked: high-high |
RETRY, retries used up: reset needed |
UT_ST_FAULT_RESET |
the level | Latched: high-high |
MANUAL: reset needed |
A trip comes first, then inhibited, a warning, a bad value, the settings, a delay
counting, OK.
How it works
- High levels are beyond above
spand clear belowsp - deadband; low levels are
beyond belowspand clear abovesp + deadband. Exactly atspis not beyond. - Response and reset work as UT_PROTECT: a WARN follows the
condition (MANUAL: until reset), a TRIP clearsrecoverafter the condition has
gone (AUTO / RETRY) or on a reset once it has gone (MANUAL). A reset while the
condition is still present is refused. Inhibittreats every condition as absent: AUTO levels clear afterrecover, a
latched MANUAL level stays latched but can now be reset.- Setpoint order (
orderCheck, on by default): of the levels in use (response
not OFF), HH must be above H, H above L and L above LL, and any high level above
any low level. Out of order setswrnConfigandWarning(UT_ST_WARN_SETTING); the levels
still act as set, each only looking at its own setpoint.orderCheckFALSE turns
the check off for a deliberate odd order. activeLevelis the most severe level in effect (HH, then LL, H, L), for an HMI
colour or a SCADA alarm class.countlives in your record: declare the recordRETAINto keep it.
Using it
HH as a latched trip, L as a warning, nothing else:
PressLimCfg.hi.response := UT_RESP_OFF; PressLimCfg.loLo.response := UT_RESP_OFF;
PressLimCfg.hiHi.reset := UT_RST_MANUAL; (* set once, or from the HMI *)
PressLim(In := Press.Value, Data := PressLimCfg);
Last updated 2 hours ago