UT_LIMIT — Four independent alarm levels (HH / H / L / LL)

UT_LIMIT — Four independent alarm levels (HH / H / L / LL)

Checks a value against up to four levels. Each level is fully independent: its
own setpoint, deadband, delay, response (off / warning / trip) and reset mode
(auto-recover, retry or latch). Each has its own output, so you can use HH alone,
treat L as a warning only, or latch LL but let HH recover by itself. Each level
works as a UT_LEVEL_CHECK.

Pins

Pin Type Default What to wire
in In REAL 0.0 The value (e.g. UT_ANALOG_IN.Value)
in Inhibit BOOL FALSE Suppress all levels (start-up, maintenance)
in Reset BOOL FALSE Rising edge: clear MANUAL levels whose condition has gone
out HiHi BOOL High-high in effect
out Hi BOOL High in effect
out Lo BOOL Low in effect
out LoLo BOOL Low-low in effect
out Trip BOOL Any level whose response is TRIP is in effect
out Warning BOOL Any level whose response is WARN is in effect, or wrnConfig
inout Data UT_LIMIT_DATA

Record UT_LIMIT_DATA

Four UT_LEVELs: hiHi, hi, lo, loLo.

Default hiHi hi lo loLo
sp 90 80 20 10
response TRIP WARN WARN TRIP
reset AUTO AUTO AUTO AUTO
delay 2 s 2 s 2 s 2 s
deadband 1.0 1.0 1.0 1.0
recover / maxRetries 10 s / 3 10 s / 3 10 s / 3 10 s / 3

Each level's status: active, tripped, retries, count, timeLeft.

Field Type Default Meaning
retryWindow TIME T#1h RETRY counts trips within this window
cmdReset BOOL HMI: as the Reset pin (acts once, on its rising edge; cleared by the block)
value REAL Status: the value checked
inhibited BOOL Status: Inhibit is on
wrnBadInput BOOL Status: the value is NaN or infinite; every level holds its state
orderCheck BOOL TRUE Check the setpoint order HH > H > L > LL among the levels in use
wrnConfig BOOL Status: setpoints out of order, or a level's setting invalid
activeLevel INT Status: the most severe level in effect: 0 none, 1 HH, 2 H, 3 L, 4 LL
timeLeft TIME Status: the countdown the status shows (a level's delay, or a recover / retry wait)
statusCode UT_STATUS Status: what it is doing (codes below)
faultId UT_FAULT Status: the level the status is about (UT_F_HIGH_HIGH, UT_F_HIGH, UT_F_LOW, UT_F_LOW_LOW), the bad value or the setting; UT_F_NONE when none
statusText STRING(30) Status: statusCode and faultId in words, e.g. Latched: high-high

Status codes

statusCode is a UT_STATUS and faultId a UT_FAULT (an HMI reads their numbers); statusText is the two in words.

statusCode faultId statusText When
UT_ST_OK UT_F_NONE OK No level in effect, nothing counting
UT_ST_OK the level OK A level's delay is counting (the most severe one: HH, LL, H, L); timeLeft shows it
UT_ST_INHIBITED Blocked: inhibit Inhibit is on
UT_ST_WARNING UT_F_VALUE_BAD Warning: value not a number wrnBadInput: every level holds its state
UT_ST_WARNING the level Warning: high A level set to WARN is in effect
UT_ST_WARN_SETTING UT_F_SP_ORDER Setting: setpoint order orderCheck found the setpoints out of order
UT_ST_WARN_SETTING UT_F_LEVEL_SETTING Setting: a level A level's setpoint, deadband or times are invalid, or a negative retryWindow
UT_ST_FAULT the level Fault: high-high A TRIP level in effect, AUTO reset (timeLeft: the recover still to go)
UT_ST_FAULT_RETRY the level Retrying: high-high RETRY, retries left (the level's retries; timeLeft: the wait)
UT_ST_FAULT_LOCKED the level Locked: high-high RETRY, retries used up: reset needed
UT_ST_FAULT_RESET the level Latched: high-high MANUAL: reset needed

A trip comes first, then inhibited, a warning, a bad value, the settings, a delay
counting, OK.

How it works

  • High levels are beyond above sp and clear below sp - deadband; low levels are
    beyond below sp and clear above sp + deadband. Exactly at sp is not beyond.
  • Response and reset work as UT_PROTECT: a WARN follows the
    condition (MANUAL: until reset), a TRIP clears recover after the condition has
    gone (AUTO / RETRY) or on a reset once it has gone (MANUAL). A reset while the
    condition is still present is refused.
  • Inhibit treats every condition as absent: AUTO levels clear after recover, a
    latched MANUAL level stays latched but can now be reset.
  • Setpoint order (orderCheck, on by default): of the levels in use (response
    not OFF), HH must be above H, H above L and L above LL, and any high level above
    any low level. Out of order sets wrnConfig and Warning (UT_ST_WARN_SETTING); the levels
    still act as set, each only looking at its own setpoint. orderCheck FALSE turns
    the check off for a deliberate odd order.
  • activeLevel is the most severe level in effect (HH, then LL, H, L), for an HMI
    colour or a SCADA alarm class.
  • count lives in your record: declare the record RETAIN to keep it.

Using it

HH as a latched trip, L as a warning, nothing else:

PressLimCfg.hi.response := UT_RESP_OFF;   PressLimCfg.loLo.response := UT_RESP_OFF;
PressLimCfg.hiHi.reset  := UT_RST_MANUAL;              (* set once, or from the HMI *)
PressLim(In := Press.Value, Data := PressLimCfg);