UT_REPORT_ARRAY — Report by exception for a whole list of values
UT_REPORT_ARRAY — Report by exception for a whole list of values
One block for all the values a site sends to SCADA or the IoT platform (60 to 80
metrics need one block, not 80). Each value has its own
UT_REPORT record, with its own deadband, mode, span, resolution,
minimum interval and heartbeat, and behaves exactly as a UT_REPORT.
Pins
| Pin | Type | Default | What to wire | |
|---|---|---|---|---|
| in | Enable |
BOOL | TRUE | FALSE: no reports; on again every item reports as at start (wire the link-up signal, or leave TRUE) |
| in | Force |
BOOL | FALSE | Rising edge: report every item now (each when its minInterval allows) |
| out | AnyReport |
BOOL | One scan: at least one item reports | |
| out | ReportCount |
INT | Items reporting this scan | |
| out | SizeMismatch |
BOOL | In and Items differ in length: only the common part is handled |
|
| inout | In |
ARRAY[*] OF REAL | The values to watch (a BOOL or INT converted to REAL first) | |
| inout | Items |
ARRAY[*] OF UT_REPORT_DATA | One record per value, in the same order |
Values and records are matched by position: the first In goes with the first item,
whatever the arrays' lower bounds.
Each item (UT_REPORT_DATA)
Every field as in UT_REPORT: the settings
(deadband, deadbandMode, span, resolution, minInterval, heartbeat,
reportOnStart) and the status. Three fields are for the array form:
| Field | Type | Meaning |
|---|---|---|
inQuality |
UT_QUALITY | The quality of this item's value (default UT_Q_GOOD); a change is reported |
report |
BOOL | Status: TRUE for the scan this item reports. Send lastValue with quality |
reason |
UT_REPORT_REASON | Status: why it last reported (FIRST, CHANGE, HEARTBEAT, FORCED) |
cmdForce reports one item (on its rising edge).
How it works
- Each scan every item is checked as a UT_REPORT would: a change past its deadband, a
quality change, its heartbeat, a force. A change held back byminIntervalis sent
when the interval ends, with the final value. - If
InandItemsdiffer in length, only the common part is handled and
SizeMismatchis set; the extra items never report. - Nothing is kept over a power cut: after one every item reports FIRST again, even
with the item list declaredRETAIN(to keep its settings).
Using it
VAR
Vals : ARRAY[1..3] OF REAL;
Rpt : ARRAY[1..3] OF UT_REPORT_DATA;
END_VAR
Vals[1] := WetWell.Value;
Vals[2] := FlowAI.Value;
Vals[3] := BOOL_TO_REAL(P1.Running);
RptAll(Enable := NOT ScadaWd.CommsFail, In := Vals, Items := Rpt);
IF RptAll.AnyReport THEN
(* publish every item with Rpt[i].report: Rpt[i].lastValue, Rpt[i].quality *)
END_IF;