UT_TWO_POINT — On/off (hysteresis) controller
UT_TWO_POINT — On/off (hysteresis) controller
A thermostat-style controller. The setpoint order decides the direction, so there's no mode to set:
OnPoint < OffPoint→ fill / heat: on when low, off when high.OnPoint > OffPoint→ empty / cool: on when high, off when low.
Pins
| Pin | Type | Default | What to wire | |
|---|---|---|---|---|
| in | In |
REAL | 0.0 | Measured value |
| in | Enable |
BOOL | TRUE | FALSE = output off |
| in | OnPoint |
REAL | 20.0 | |
| in | OffPoint |
REAL | 80.0 | |
| in | OnDelay / OffDelay |
TIME | T#0s | Value must stay past the point this long |
| in | MinOn / MinOff |
TIME | T#0s | Anti-short-cycle |
| out | Q |
BOOL | The output | |
| out | BadInput |
BOOL | In or a point is NaN or infinite: Q is held |
|
| out | Remaining |
TIME | Time left before Q changes: the delay and MinOn / MinOff still to run while the value is past the point that changes it (T#0s otherwise) |
|
| out | Waiting |
BOOL | The value is past the point and its delay is over, but MinOn / MinOff still holds Q |
How it works
- A value exactly on a point is not past it, so nothing changes there.
- Equal points act as a simple comparator with no hysteresis, in the fill / heat
direction: on below the point, off above it (documented, not an error). OnDelay/OffDelay: the value must stay past the point the whole time; a blip
back starts the delay again.MinOn: once on,Qstays on at least this long.MinOff: once off,Qstays
off at least this long.MinOffis not applied at start-up.- The points are re-evaluated every scan, so changing or swapping them while
running takes effect cleanly (through the delays). EnableFALSE turnsQoff at once, even insideMinOn.MinOffcounts from
that moment.- A NaN or infinite
In,OnPointorOffPointholdsQas it is and sets
BadInput; the delays start again once the value is good.Enablestill
turnsQoff. UseBadInputto decide what the plant should do. Remainingis the longer of the delay and the minimum time still to run, so
an HMI can show "starts in 1 m 20 s" (UT_TIME_TEXT).
Waitingsays the minimum time is the only thing holdingQ("Waiting:
minimum off time").
Using it
SumpCtl(In := SumpLevel, OnPoint := 70.0, OffPoint := 25.0, OnDelay := T#5s, MinOff := T#2m);
SumpPumpAuto := SumpCtl.Q; (* empty: on above 70 %, off below 25 % *)