UT_PUMP_STATION — Multi-pump station (wet well, sump, tank, booster)

UT_PUMP_STATION — Multi-pump station (wet well, sump, tank, booster)

Runs a station of any number of pumps from one level or pressure signal. It
handles staged start/stop points, duty rotation (alternation), failover to the
next pump, staggered starts, backup floats, random start-level variation (stops
fat rings forming), sump cleaning, a pump-down on request (Demand), an inhibit that
keeps the overflow backup, and inflow, outflow and overflow statistics.

There's no per-pump wiring. Give the station the array of pump records, and each
UT_PUMP uses one element as its Data.

Pins

Pin Type Default What to wire
in Level REAL 0.0 Level (or pressure) signal, e.g. UT_ANALOG_IN.Value
in Enable BOOL TRUE FALSE = everything off: no pump is called, the high float included (pumps stop unless in Hand)
in LevelBad BOOL FALSE Transmitter failed (e.g. NOT LevelAI.Good). Switches to float/timer control. A level that is not a number does the same
in HighFloat BOOL FALSE Backup high-level float, TRUE = made. Also checks the transmitter (see transducer). A float that opens at high level: NOT at the pin
in LowFloat BOOL FALSE Low-level cut-out float, TRUE = level low (stops all pumps). A float that is made with water (fail-safe on a broken wire): NOT at the pin
in Rotate BOOL FALSE Rising edge: change the lead pump now
in Reset BOOL FALSE Rising edge: clear latched faults (a MANUAL transducer fault, cleanFailed), as cmdReset. The statistics are kept (cmdResetStats)
in Demand BOOL FALSE Pump down now (FILL: fill up): demandPumps pumps until demandStop. A remote run request (SCADA, a timer); see Demand
in Inhibit BOOL FALSE No level, demand or cleaning start (a running level cycle is released), while the high float still runs the pumps (the overflow backup). Enable FALSE is everything off
out RunningCount INT Pumps running
out HighLevel BOOL Level above highLevelAlarm, or the high float
out Shortfall BOOL Fewer pumps available than the level asks for
out Lead INT Array index of the lead pump
out Inflow REAL Estimated inflow per hour, in the vessel's volume unit: the rise of the Level vessel's volume (a UT_VESSEL on Level), plus the Flow meter's rate. 0 without a vessel
out TransducerFault BOOL The level can't be trusted: it disagreed with the high float (until it reads again, see transducer), or LevelBad / a level that is not a number. floatControl says whether the station runs on the floats and timers
out ConfigFault BOOL A setting makes level control meaningless. An unknown stationMode: no pump is called. Stage 1 the wrong way round or not a number: no level control; in EMPTY the high float still runs the pumps (float/timer control, the overflow backup never depends on settings), in FILL no pump is called. Until it is fixed
out Warning BOOL An invalid setting (a safe value is used), a cleaning timeout (cleanFailed), a transducer WARN, or ConfigFault
out Fault BOOL A configuration fault, the transducer check tripped, a bad level in FILL, or no pump available while one is wanted (faultCode says which)
inout Pumps ARRAY[*] OF UT_PUMP_DATA All the station's pump records (any size, any lower bound)
inout Data UT_STATION_DATA Station record

Record UT_STATION_DATA

Settings

Field Type Default Meaning
stationMode UT_STATION_MODE UT_SM_EMPTY UT_SM_EMPTY (wet well, sump) or UT_SM_FILL (reservoir, booster on pressure)
stage ARRAY[1..4] OF UT_STAGE see below start/stop point per stage (stage n = n pumps running)
maxRunning INT 0 Limit on pumps running together (0 = no limit). No pump is called while this many run (Hand pumps count)
rotation UT_ROTATE_MODE UT_ROT_EACH_START Fixed / each cycle / equal hours / every interval
rotateInterval TIME T#24h For UT_ROT_INTERVAL (0 = never)
fixedLead INT 1 For UT_ROT_FIXED: the array index of the lead (out of range = the first)
stageDelay TIME T#5s Minimum gap between pump starts (inrush, water hammer), counted from the last pump's run command
destageDelay TIME T#2s Minimum gap between pump stops
failoverDelay TIME T#10s Called pump not running this long after its run command → skipped, the next is called. Set it longer than the motor's restartDelay
levelVariation REAL 0.0 Random ± offset on stage 1 start, new each cycle (fat-ring prevention). 0 = off
cleanEvery INT 0 Every N cycles, pump down to cleanLevel (sump clean). 0 = off
cleanLevel REAL 5.0
cleanTime TIME T#20s Extra run ("snore") once the clean level is reached
maxCleanTime TIME T#5m Cleaning not finished in this time (from its start): it ends with cleanFailed and the pumps running only for it stop at once (the well isn't coming down: blocked intake, air lock, cleanLevel below the pump), then normal control. Set it longer than a pump-down plus cleanTime. 0 = no limit
highFloatRunAll BOOL TRUE High float runs every available pump (FALSE: the lead only). Each high-float event also gives every pump skipped for a failed start one more try
highFloatHold TIME T#2m Keep running after the high float clears (level trusted)
floatRunTime TIME T#5m Float/timer control: keep running this long after the high float clears
floatLockout TIME T#1m Float/timer control: after the pumps stop, the high float can't start them again for this long (anti-cycling)
floatCheckDelay TIME T#10s High float made while the level reads below highLevelAlarm for this long → the transducer is suspect. A float tipping right at the alarm level for less than this is not a fault
transducer UT_PROTECTION TRIP · AUTO · recover 10 s What a suspect transducer does. response: OFF = no check · TRIP = float/timer control while it lasts · WARN = an alarm only, the level is still used (less safe: a stuck-low reading then never starts the pumps, only the high float does). reset: AUTO = it clears once the transducer reads properly again (a valid reading at or above highLevelAlarm) and recover has passed · MANUAL = it also needs Reset / cmdReset · RETRY = AUTO up to maxRetries in an hour, then MANUAL. delay is not used (floatCheckDelay is the check's delay). Status: active, tripped, retries, count
highLevelAlarm REAL 90.0 High-level alarm, and the transducer check. Set it at or below the level the high float makes at
wellArea REAL 0.0 Plan area of the well (m²) for the inflow estimate. 0 = off
pumpsUsed INT 0 Pumps fitted: the station uses the first pumpsUsed records of Pumps (0 = all). The others are left alone: never called, rotated in or counted, so a record can serve a pump that is not fitted yet, or one run on its own (e.g. a booster). Negative or more than the array: every pump, and the warning Setting: pumps used
floatsOnly BOOL FALSE EMPTY, no level transmitter: float-only control as the normal control (see How it works). Level is not used and is no fault. With FILL it is a configuration fault (UT_F_STATION_MODE)

UT_STAGE (start, stop : REAL) defaults: stage 1 = 60 / 20, stage 2 = 75 / 25,
stage 3 = 85 / 30, stage 4 = 90 / 35 (same units as Level). Stations with more than 4
pumps: stage 4 calls every remaining pump. In FILL mode, set start below stop. Stage 1
must be usable: the wrong way round for the mode (or not a number) is a configuration
fault and no pump runs. Stages 2–4 whose points are the wrong way round are not used, so
in FILL mode the EMPTY defaults of the stages you don't set never call a pump (not a
number there: not used, and a warning).

Demand settings (at the end of the record)

Field Type Default Meaning
demandPumps INT 1 Demand / cmdPumpDown: pumps to run (1 or more; staged a stageDelay apart, within maxRunning)
demandStop REAL 0.0 Demand / cmdPumpDown: run until the level reaches this (EMPTY: falls to it; FILL: rises to it). 0 = stage 1's stop point

HMI commands

cmdRotate (move the lead on now), cmdClean (clean now), cmdReset (clear latched
faults, as the Reset pin), cmdResetStats (cycles, highFloatEvents and
highFloatTime to 0; nothing else), cmdPumpDown (pump down now, as a new Demand).
Each acts once, on its rising edge, and is cleared.

Status fields

lead, runningCount, calledCount, availableCount, shortfall, highLevel,
floatControl (float/timer control active), transducerFault (as the pin),
configFault (as the pin), configBad (any invalid setting, configFault included),
cleaning, cleanFailed (cleaning timed out; until a reset or a clean that finishes),
warning (as the pin), cycles : UDINT,
highFloatEvents : UDINT, highFloatTime : TIME (overflow-risk duration),
inflow : REAL, startPointNow (stage 1 start including the variation),
statusCode : UT_STATUS, statusText : STRING(30) and statusUnit : DINT (what the
station is doing or what holds it back, and the pump it is about, see
Status), and at the end of the record:

Field Type Meaning
demand BOOL Demand / cmdPumpDown is running pumps
inhibited BOOL Inhibit holds the level control off
timeLeft TIME The countdown that goes with the status: stage or destage delay, the high-float hold or floatRunTime, the float lockout, the clean (cleanTime once at the clean level, else maxCleanTime). 0 = none
phaseTime TIME Time in this cycle (pumps wanted), or idle since the last one
cleanElapsed TIME Time cleaning so far (0 when not cleaning)
rotateIn TIME INTERVAL: time to the next rotation (0 for the other rotations)
outflow REAL Estimated pumped flow per hour while pumps run: wellArea × the level fall per hour + inflow (FILL: the rise − use). Needs wellArea; 0 while idle
cycleVolume REAL Net volume drawn (EMPTY) or added (FILL) this cycle: wellArea × the level change since the cycle began; kept after it ends (not counted on while the level is not trusted)
fault, faultCode : DWORD As Fault: bit 0 config fault, 1 transducer fault (float check), 2 level signal bad (FILL), 3 no pump available
faultId UT_FAULT The lowest faultCode bit by name: the setting (UT_F_STATION_MODE, UT_F_STAGE1), UT_F_TRANSDUCER, UT_F_LEVEL_BAD, UT_F_NO_PUMP; UT_F_NONE when there is no fault
stopReason UT_STOP Why the last cycle ended (all pumps released), below
lastFaultCode, lastFault DWORD, UT_FAULT The last fault's bits and name, kept after it clears
trips UDINT Faults since power-up

Each pump's record shows its part: grpRank (1 = lead), grpRun (called),
grpSkipped (called but did not run; skipped until it has been unavailable or the next
cycle starts) and grpRunTime (its run time counted by the station since power-up,
for HOURS rotation).

Why the last cycle ended (stopReason):

stopReason Words (UT_STOP_TEXT) When
UT_STOP_DEMAND_ENDED Auto: demand ended The level reached the stop point
UT_STOP_SWITCHED_OFF Stopped: switched off Enable off
UT_STOP_INHIBITED Stopped: inhibited Inhibit
UT_STOP_LOW_LEVEL Stopped: low level The low float
UT_STOP_FULL Stopped: full FILL: the high float
UT_STOP_CLEAN_TIMEOUT Stopped: cleaning too long Cleaning timed out
UT_STOP_LEVEL_BAD Stopped: level signal bad FILL: the level is not trusted
UT_STOP_SETTING Stopped: setting invalid A configuration fault
UT_STOP_DONE Done Demand / cmdPumpDown reached the demand level

Status

statusCode, faultId and statusText say the one main thing the station is
doing, or what holds it back. The most important reason wins: configuration > fault >
held / waiting > warning > running > idle. A station asked to run (the level or the
high float wants a pump) with no pump running or starting always shows a held, fault
or configuration status. UT_ST_STARTING (a called pump's run command is out, its
feedback not yet in) shows over a warning. statusUnit is the pump (its array index)
the status is about, for UT_ST_STARTING and UT_ST_PUMP_DELAY; one below the
array's first index when none. Each pump's own status says more (e.g. Waiting: min off time). The words hold no numbers: the level is the Level output, the counts are
runningCount, calledCount and availableCount, and the time left is in
timeLeft. The text is rebuilt only when the status or the fault changes. The
numbers are in conventions.

statusCode Words When
UT_ST_IDLE_NO_DEMAND Idle: no demand No pump wanted
UT_ST_STARTING Starting Pump statusUnit is called, its run command is out, not running yet
UT_ST_STOPPING Stopping More pumps called than wanted: the next release after destageDelay (timeLeft)
UT_ST_RUNNING Running Pumps running (any mode); runningCount says how many
UT_ST_RUN_DEMAND Running: demand Demand / cmdPumpDown is running pumps
UT_ST_IDLE_LEVEL_REACHED Idle: demand level reached Demand still held, the level at demandStop: it waits for the start point or a new Demand (never "no demand" while Demand is TRUE)
UT_ST_CLEANING Cleaning Pumping down to cleanLevel (timeLeft is the time left of maxCleanTime), then cleanTime
UT_ST_HIGH_FLOAT Running: high float EMPTY, level trusted: the high float runs the pumps (made, then highFloatHold, counting in timeLeft)
UT_ST_FLOAT_RUN Running: on floats floatsOnly: the high float started the lead; it runs to the low float (or floatRunTime, counting in timeLeft, after the high float clears)
UT_ST_NOT_PERMITTED Not permitted Enable FALSE
UT_ST_INHIBITED Blocked: inhibit Inhibit, no pump running (the high float still acts)
UT_ST_LOW_FLOAT Blocked: low float (dry) LowFloat made: every pump stopped (not with floatsOnly: there it is the stop float, made whenever the well is down)
UT_ST_FULL Blocked: high float (full) FILL: HighFloat made
UT_ST_STAGE_DELAY Waiting: stage delay More pumps wanted, the next start after stageDelay (timeLeft)
UT_ST_PUMP_DELAY Waiting: pump own delay Pump statusUnit is called but waits out its own startDelay / minOffTime or its StartHold (the pump's status says which)
UT_ST_MAX_RUNNING Waiting: max running reached More pumps wanted, maxRunning already running (e.g. one running down)
UT_ST_SHORTFALL Shortfall: too few available More pumps wanted than are available (tripped, not in Auto, skipped); availableCount says how many are
UT_ST_WARNING Warning: level vs high float UT_F_FLOAT_DISAGREE: the transducer check set to WARN
UT_ST_WARNING Warning: cleaning too long UT_F_CLEAN_TIME: cleanFailed
UT_ST_WARN_SETTING Setting: a setting UT_F_SETTING: configBad without a configuration fault
UT_ST_WARN_SETTING Setting: pumps used UT_F_PUMPS_USED: pumpsUsed negative or more than the array (every pump is used)
UT_ST_FLOAT_CONTROL Float control EMPTY: float/timer control, with faultId UT_F_TRANSDUCER (the transducer check tripped) or UT_F_LEVEL_BAD (LevelBad or a NaN / infinite level); runningCount pumps running
UT_ST_FLOAT_LOCKOUT Float lockout Float/timer control: the high float can't start the pumps again for floatLockout (timeLeft)
UT_ST_FAULT Fault: level signal bad FILL: a bad level stops every pump
UT_ST_FAULT Fault: no pump ready Pumps wanted, none available (all tripped, not in Auto or skipped) and none running
UT_ST_CONFIG Config: <setting> No level control until fixed: UT_F_STATION_MODE (station mode: unknown), UT_F_STAGE1 (stage 1 start / stop: the wrong way round, equal, or not a number), UT_F_NO_UNITS (no units in array: an empty pump array)

How it works

  1. Ranking. Pumps are ranked by the rotation rule (grpRank). A pump is a
    candidate when it is available (healthy, motor ready, motor in Auto) and not
    skipped. Pumps running in Hand (or exercising) count toward the demand; a pump
    running down after a stop or a trip does not.
  2. Staging. As the level rises past stage n's start, n pumps are wanted. Pumps are
    called one at a time, best rank first, at least stageDelay apart and only once
    the last one called is running. Each stage drops out at its own stop point, and
    pumps are released one at a time (worst rank first), at least destageDelay apart.
  3. Failover. A called pump that isn't running within failoverDelay of its run
    command is skipped and the next is called (it rejoins next cycle: no retry storm). A
    pump still waiting out its own startDelay / minOffTime (after a power cut, or
    just stopped) hasn't failed: after failoverDelay it hands over if another pump can
    be called, and is called again once no other is left. A pump that trips, loses its
    motor or leaves Auto is released at once and replaced. It rejoins once it's
    available again (no needless swap of a pump already running). A pump whose
    StartHold is on (startHold, e.g. a stirrer pre-run) has not failed either: it
    stays called, with no failover, and starts when the hold ends.
  4. Rotation. FIXED: fixedLead. EACH_START: the lead moves on when a cycle ends
    (all pumps released). HOURS: at each cycle start the pump with the least run time
    leads (each pump's grpRunTime, counted by the station; every pump counts). INTERVAL: every
    rotateInterval. Rotate/cmdRotate move the lead on now. A rotation while
    running starts the new lead before stopping the old one, never dropping below the
    demand; at maxRunning the old one stops first, so the limit is never passed.
  5. Backup floats (EMPTY). HighFloat runs every available pump (or the lead)
    whatever the transmitter says, and keeps them running highFloatHold after it
    clears. LowFloat and Enable off release every pump at once.
    Transducer check. If the high float is made while the transmitter reads below
    highLevelAlarm for longer than floatCheckDelay, the transmitter is suspect
    (stuck, drifted, fouled): TransducerFault, and with the default TRIP, float/timer
    control. It does not latch for ever: build-up round a sensor clears. A healthy
    transmitter shows the high level as the well refills, before or as the float
    makes; once it reads a valid value at or above highLevelAlarm, the fault clears
    after transducer.recover (AUTO). A transmitter still stuck never shows it, so the
    float catches it again. With MANUAL it also needs Reset / cmdReset. A reset
    clears it at any time (refused while the float is made and the reading is still
    low); so does a power cut.
    Float/timer control (a transducer fault, LevelBad, or a level that is not a
    number): the level is ignored. When the high float makes, the pumps run while it
    stays made (never stopped during a real flood) and floatRunTime after it clears.
    After they stop, the high float can't start them again for floatLockout. The
    low float stops them at once and ends the run (the lockout follows).
    FILL mode: HighFloat (tank full) and a bad level release every pump;
    LowFloat still cuts out.
    Float-only control (floatsOnly, EMPTY, no transmitter): the normal control,
    not a fault. HighFloat (the start float) calls the lead pump; it runs until
    LowFloat (the stop float) makes, or floatRunTime after the high float clears
    (0 = the low float only). No lockout, no transducer check, HighLevel is not
    set by the start float (wire a high-level float to its own alarm), and level
    stages, Demand, cleaning and the inflow estimate are not used. Failover and
    rotation work as usual; a second pump is called only by failover. Inhibit stops
    it (it is the level control).
  6. Cleaning and variation. These reduce grease build-up in sewage wells. A clean
    cycle runs a pump down to cleanLevel, then cleanTime more. A pump that trips
    during the clean (its own dry-run protection) ends it. A clean not finished within
    maxCleanTime ends with cleanFailed (a warning) and the pumps running only for
    it stop at once; if the level still wants a pump, it runs on as normal.
    levelVariation must be less than the gap between stage 1's start and stop.
  7. Inflow. While no pump runs, the level rise × wellArea, averaged since the
    pumps stopped (published after 2 s, a fresh window every minute). Held while
    pumps run.
  8. Invalid settings. A configuration fault (ConfigFault, until fixed): an
    unknown stationMode (no pump at all); stage 1 the wrong way round for the mode or
    not a number (no level control: an EMPTY station drops to float/timer control so
    the high float still protects the well; a FILL station calls no pump, and must set
    stage 1). A
    warning (configBad, Warning) with a safe value: maxRunning negative (as
    0, no limit); failoverDelay 0 or negative (10 s: 0 would skip every pump before
    it could start); levelVariation negative, not a number or not below the stage 1
    gap (no variation); cleanEvery negative, cleanLevel not a number, a negative
    cleanTime or maxCleanTime (no cleaning); an unknown rotation; fixedLead out
    of range with FIXED (the first pump); pumpsUsed negative or more than the array
    (every pump); stages 2–4 not a number (not used); a negative
    time (as 0); highLevelAlarm not a number; wellArea negative or not a number
    (inflow off); transducer with an unknown response (as TRIP) or reset (as AUTO),
    or a bad time.
  9. Resets. Reset (rising edge) and cmdReset clear latched faults (a MANUAL or
    used-up RETRY transducer fault, cleanFailed); cmdResetStats clears the
    statistics. Neither does the other's job.

Demand and inhibit

  • Demand (or cmdPumpDown, once) pumps down now, e.g. a SCADA "empty the
    sump before the rain" or a timed draw-off: demandPumps pumps run until the level
    reaches demandStop (0 = stage 1's stop point), status UT_ST_RUN_DEMAND. Every station protection
    still acts: the low float, the transducer check (no demand while the level is not
    trusted), maxRunning, failover and staging. At demandStop the pumps stop
    (stopReason UT_STOP_DONE); a Demand still held waits (UT_ST_IDLE_LEVEL_REACHED) and runs again once the
    level is back at the stage 1 start point, or on a new rising edge. Refused on the low
    float, a level that is not trusted, Enable off or Inhibit. In FILL mode it fills
    up to demandStop instead.
  • Inhibit holds the level control off (no level, demand or cleaning start; a
    pump running for the level is released, stopReason UT_STOP_INHIBITED) while the high float still
    runs the pumps
    : the overflow backup stays. Enable FALSE is everything off, the
    high float included (stopReason UT_STOP_SWITCHED_OFF).

Power cut: only the lead is kept (saved at once when it changes, so after
frequent power cuts the first pump does not always lead). With HOURS a tie in run
time goes to the kept lead,
cycles, highFloatEvents, highFloatTime and the pumps' grpRunTime at 0 (also when the pump records are RETAIN), and a transducer
fault and cleanFailed are cleared. Every
grpRun starts cleared and the pumps are called one at a time again, even if your
pump records are RETAIN.

Using it

VAR Pumps : ARRAY[1..3] OF UT_PUMP_DATA; END_VAR
Station(Level := WetWell.Value, LevelBad := NOT WetWell.Good,
        HighFloat := HiFloat, LowFloat := LoFloat, Pumps := Pumps, Data := StationCfg);
P1(Demand := HiFloat, Running := M1.Running, MotorReady := M1.Ready, MotorAuto := M1.Auto,
   DryRun := LoFloat, Data := Pumps[1]);
(* … P2, P3 … *)

Each pump's Demand is only its fallback: while the station runs, the station decides.
If the station block stops being called, each pump is back on its own control (here:
run on the high float) from the next scan.