UT_ANALOG_IN — Analog input (scale, NAMUR NE43, filter, quality, simulate)

UT_ANALOG_IN — Analog input (scale, NAMUR NE43, filter, quality, simulate)

Turns a raw analog reading into engineering units. It detects a failed transmitter
or a wire break (NAMUR NE43 bands for 4–20 mA), filters noise, reports quality,
and decides what value to give when the signal is bad.

Pins

Pin Type Default What to wire
in In REAL 0.0 Raw value (INT_TO_REAL(%IW0)), counts or mA
out Value REAL Engineering value
out Percent REAL 0–100 % of the range
out Good BOOL Quality is GOOD (or SIM)
out Fault BOOL Signal failed (BAD)
out Quality UT_QUALITY GOOD / UNCERTAIN / BAD / SIM
inout Data UT_ANALOG_DATA

Record UT_ANALOG_DATA

Field Type Default Meaning
signal UT_AI_SIGNAL UT_AI_4_20MA UT_AI_4_20MA (NE43 checks), UT_AI_0_20MA, UT_AI_0_10V, UT_AI_CUSTOM
rawMin / rawMax REAL 0.0 / 65535.0 Raw value at the bottom and top of the signal (4 mA and 20 mA for 4–20). For a reading already in mA use 4.0 / 20.0
engMin / engMax REAL 0.0 / 100.0 Engineering range (engMin > engMax works)
filterTime TIME T#0s First-order low-pass time constant (0 = off)
clamp BOOL TRUE Clamp Value to the engineering range
lowCutoff REAL 0.0 Values below this read as engMin (flow meters near zero). 0 = off
faultDelay TIME T#2s A failure must last this long to become a Fault
faultAction UT_AI_FAULT UT_AI_HOLD Value while failed: UT_AI_HOLD last good, UT_AI_MIN engMin, UT_AI_MAX engMax, UT_AI_SUBST substValue, UT_AI_PASS keep the reading
substValue REAL 0.0
customLowFail / customHighFail REAL -5.0 / 105.0 UT_AI_CUSTOM: fail at or beyond these % of the span
simulate, simValue BOOL, REAL FALSE, 0.0 simValue is in engineering units
faultReset UT_RESET_MODE UT_RST_AUTO AUTO: Fault clears when the signal has been good for recover; MANUAL: holds until reset
recover TIME T#2s
cmdReset BOOL HMI: reset a MANUAL fault (acts once, cleared by the block)
raw, value, percent, quality, fault Status, as the pins (raw = In)
underRange, overRange BOOL Status: UNCERTAIN, outside the range
failLow, failHigh BOOL Status: in a fail band now
wrnConfig BOOL Status: zero or invalid span (BAD at once), or a trimOffset / altFactor / altOffset that is not a number
faults UDINT Count of failure events
trimOffset REAL 0.0 Field zero trim, engineering units, added to the reading (before the filter and the clamp)
altFactor REAL 1.0 Second unit: valueAlt = value × altFactor + altOffset (bar → psi: 14.5038; °C → °F: 1.8)
altOffset REAL 0.0 (°C → °F: 32)
valueAlt REAL Status: the value in the second unit

NE43 bands (UT_AI_4_20MA):

Signal Meaning Quality
≤ 3.6 mA fail low (sensor fault / wire break) BAD
3.6 – 3.8 mA under range UNCERTAIN
3.8 – 20.5 mA measurement (3.8 and 20.5 included) GOOD
20.5 – 21 mA over range UNCERTAIN
≥ 21 mA fail high BAD

The mA thresholds are computed from rawMin/rawMax, so any card scaling works
(0–27648 for 4–20 mA: fail low at −691.2 counts, fail high at 29376).
UT_AI_0_20MA and UT_AI_0_10V have no fail bands (a wire break reads as 0): below
0 % or above 100 % is UNCERTAIN. UT_AI_CUSTOM is the same plus fail bands at
customLowFail / customHighFail.

How it works

  • A failure (a fail band, or a NaN / infinite reading) must last faultDelay.
    Meanwhile the value is held at the last good one and the quality is UNCERTAIN,
    so a short spike does nothing. After the delay it is a Fault (a
    UT_PROTECT trip with faultReset / recover), quality BAD, and
    faultAction gives the value. Each fault is counted in faults.
  • The filter is exact at any scan rate and stops while the signal has failed, so
    HOLD gives the last good filtered value.
  • A zero or invalid span is BAD at once with wrnConfig; it is not counted as a
    signal failure. Value and Percent are never NaN or infinity.
  • Simulate: Value = simValue, quality SIM, failures are not checked.
  • Zero trim: trimOffset corrects a transmitter that reads a little off in the
    field (e.g. −0.02 m on a level that shows 0.02 m with the well empty). It is added
    to the scaled reading, so the clamp still holds Value inside the range.
  • Second unit: valueAlt follows Value (also while held or simulated). Unset
    (altFactor 1, altOffset 0) it equals Value. A trim, factor or offset that is
    not a number or infinite sets wrnConfig and is not used (trim 0, valueAlt 0);
    the quality is not affected.
  • Power cut: nothing is kept. faults starts at 0, a MANUAL fault is forgotten,
    and a signal that is still failed faults again after faultDelay.

Using it

LevelCfg.rawMax := 27648.0;  LevelCfg.engMax := 5.0;   (* 0..5 m: the HMI shows the unit *)
Level(In := INT_TO_REAL(%IW0), Data := LevelCfg);