UT_HOA — Hand / Off / Auto for anything

UT_HOA — Hand / Off / Auto for anything

Mode selection for outputs that don't have their own block: lights, heaters,
solenoids, a whole system. (Motors and valves have this built in.) Same mode
sources and cmdMode codes as the devices (UT_MODE_SELECT),
without out of service.

Pins

Pin Type Default What to wire
in AutoCmd BOOL FALSE Output wanted in Auto
in HandCmd BOOL TRUE Output wanted in Hand (unwired = on)
in SwHand / SwAuto BOOL FALSE Selector switch (when modeSource uses it)
in Interlock BOOL TRUE FALSE forces the output off in every mode
out Out BOOL The output
out Mode UT_MODE The mode now
out IsOff, IsHand, IsAuto BOOL
inout Data UT_HOA_DATA

Record UT_HOA_DATA

Field Type Default Meaning
modeSource UT_MODE_SOURCE UT_SRC_HMI UT_SRC_HMI · UT_SRC_SWITCH · UT_SRC_REMOTE. The mode starts at Off and is retained (see powerUp, handPowerUp)
handTimeout TIME T#0s Hand goes back to Off after this (0 = never)
cmdMode INT −1 HMI: 0 Off · 1 Hand · 2 Auto. Acts once, when a new value arrives. Anything else is ignored. Set back to −1
mode UT_MODE status
out BOOL status
powerUp UT_POWERUP UT_PU_LAST After a power cut or a PLC stop / start: UT_PU_LAST the mode comes back as it was (but see handPowerUp); UT_PU_OFF every mode comes back Off
handPowerUp UT_HAND_POWERUP UT_HPU_OFF After a power cut, a Hand: UT_HPU_OFF comes back Off, the output never comes on by itself; UT_HPU_KEEP Hand and its output come back
handLeft TIME status: time until the hand timeout ends Hand (0 when no timeout is running)
statusCode UT_STATUS status: what it is doing, see Status codes
statusText STRING(30) status: statusCode in words, e.g. Running: Hand. The time to the hand timeout is in handLeft

How it works

Mode Out
Off FALSE
Hand HandCmd (TRUE when not wired, so Hand = on)
Auto AutoCmd

Interlock FALSE turns Out off in every mode; it comes back on when the interlock returns.

  • Hand. With HandCmd not wired, Hand means on, like a hard-wired HOA switch.
    Wire HandCmd to make Hand follow your own logic or a pushbutton latch.
  • Power cut (or a PLC stop / start). With the defaults, Auto comes back
    following AutoCmd and Off stays off, from the first scan. A Hand comes back
    Off (handPowerUp = UT_HPU_OFF): a Hand chosen on the HMI is set to Off, and
    a selector left in Hand holds the output off until it is turned out of Hand and
    back. A heater or motor left in Hand never starts by itself after a power cut
    (EN 60204-1). UT_HPU_KEEP brings Hand back on, for a light that should stay on.
    powerUp = UT_PU_OFF brings every mode back Off.
  • Hand timeout. Starts on entering Hand and restarts when the HMI asks for Hand
    again (cmdMode 1). When it runs out, a Hand chosen on the HMI goes back to Off.
    A selector left in Hand gives Mode Off and Out off until it is turned out of
    Hand and back. handLeft shows the time still to go.
  • HMI command. cmdMode acts once when a new value arrives; a value held or
    rewritten there acts once (so a held 1 does not keep restarting the hand
    timeout). With two masters, put UT_CMD in front.

Status codes

statusCode is a UT_STATUS (an HMI reads its number); statusText is the same in words.

statusCode statusText When
UT_ST_OFF Off Mode Off
UT_ST_IDLE_HAND Idle: Hand, command off Hand, HandCmd off
UT_ST_IDLE_NO_DEMAND Idle: no demand Auto, AutoCmd off
UT_ST_RUN_HAND Running: Hand Hand, output on (handLeft shows the time to the hand timeout)
UT_ST_RUN_AUTO Running: Auto Auto, output on
UT_ST_INTERLOCK Blocked: interlock The output is wanted but Interlock is FALSE
UT_ST_SELECTOR_HAND Waiting: selector out of Hand A selector in Hand after the hand timeout, or after a power cut

Using it

YardLights(AutoCmd := Dusk, SwHand := LightsHand, SwAuto := LightsAuto, Data := YardLightsHOA);
YardLightsContactor := YardLights.Out;