09 - Troubleshooting

09 - Troubleshooting

Arranged by what you are seeing, not by what is wrong.

The node will not start

READY is FALSE and ERROR is TRUE.

Read LAST_ERROR first. It says what failed, in the operating system's own
words, which say far more than a code can. While STATUS reads
BEEBUS_NOT_INITIALISED the node keeps trying — RETRY_IN counts down to the
next attempt — so fixing the cause is enough; there is nothing to restart.

LAST_ERROR
"could not bind group port: Address already in use" another program has the port. Often a second copy of this one still running
"could not open serial device: No such file or directory" the serial DEVICE path is wrong, or the adapter is not plugged in yet
"could not open serial device: Permission denied" the runtime user cannot open the serial port
"could not join multicast group: No such device" IFACE names an address this machine does not have, or the network is not up yet
"no serial device named" DEVICE was left empty with BEEBUS_NODE_RUNTIME_SERIAL (a setting: not retried)
"NODE_ID must be 1..254" a setting: not retried
"out of memory for the node", "... for the buffers and queues", "... for the link" the board has no room left for the node: the rest of the program has the memory. Retried with the back-off
"joining the network" WiFi is still associating. Not a fault — it clears on its own
"Ethernet cable unplugged" no link on the PHY
"no address from DHCP yet" cable is live, no lease yet. A fixed IP avoids the wait
"no Ethernet controller found on SPI" no W5100/W5500 answered. Check the wiring and CS pin
"set BEEBUS_ENABLE_ETHERNET to use Ethernet" Ethernet is opt-in. Add the flag in Build Settings, and install the Arduino Ethernet library
"this board has no WiFi" the board has no WiFi.h

STATUS = BEEBUS_INVALID_ARGUMENT with "that link needs a board, not the
Runtime"
— or "that link needs the Runtime, not a board" — means TRANSPORT
names a link the target cannot carry. Give it a BEEBUS_NODE_RUNTIME_* value on
the Runtime, a BEEBUS_NODE_ARDUINO_* value on a board.

The node started but never joins

READY is TRUE, CONNECTED stays FALSE, MEMBERS stays 1.

Work down this list.

1. Check STATUS for BEEBUS_DUPLICATE_NODE_ID. Two devices on one
NODE_ID. The second stands down entirely — no turn, no address, every read and
write refused. It looks exactly like a node that has not finished starting,
which is why the code exists. Find the other device and change one of them; the
node rejoins by itself.

This is the most common fault on a new network, and it is worth checking for a
device you had forgotten was still powered.

2. Are they on the same network at all? For UDP, both nodes need the same
GROUP and UDP_PORT. Leave both at their defaults on both nodes and they
will match. If you set them to separate two networks, check you set them the
same within each.

3. TTL. If the nodes are on different subnets, TTL := 1 keeps every
frame local and they will never hear each other. Raise it, or put them on one
subnet.

4. Multicast on the network. Some switches drop multicast between ports by
default. Two containers on one host always work; two PCs through a managed
switch may need IGMP snooping configured or turned off.

5. On serial: both ends at the same BAUD, A to A and B to B, and a 120 Ω
terminating resistor at each end of the run. Check NOISE_BYTES on
BEEBUS_NODE_STATUS — climbing means the line is being read but not understood, which
is usually a baud mismatch or missing termination.

Values are not arriving

QUALITY stays BEEBUS_TP_UNKNOWN and AGE is -1 — nothing has ever
arrived.

Check the peer is there first. BEEBUS_NODE_PEER_STATUS with that PEER. If
ALIVE is FALSE, this is a ring problem, not a topic problem — go back to the
section above.

Check NAME and TOPIC_ID match exactly. Both must be what the owning node
bound. A mismatched ID is the usual cause and nothing reports it as an error,
because from the protocol's side you have simply subscribed to a topic that node
does not have.

Check STATUS on the subscribe block. BEEBUS_INVALID_ARGUMENT means the
block could not bind its own side — a VALUE of a type the wire cannot carry,
or a NAME over 253 characters. BEEBUS_TP_SUBSCRIBE binds locally as well as asking
the peer, so this is about your declaration, not the peer's.

Both ends must declare the same type. If the owner bound a REAL and you
bound an INT, values are discarded on arrival — your QUALITY stays
BEEBUS_TP_UNKNOWN and nothing on the subscribe block says why. The refusal goes back
to the publisher instead. So when a subscription looks correct and still
receives nothing, compare the two declarations before anything else.

Values arrive, then stop

QUALITY goes BEEBUS_TP_UNCERTAIN then BEEBUS_TP_BAD, AGE climbs.

This is the mechanism working, not failing. Something upstream stopped.

VALUE deliberately holds its last reading rather than going to zero — zero
would be a lie. Use QUALITY to decide whether to trust it, and never raise a
process alarm from a value whose quality is not BEEBUS_TP_GOOD.

Check BEEBUS_NODE_PEER_STATUS.ALIVE for the publisher. If it is alive and values
still stopped, the topic binding on its side has gone — look at its BOUND pin.

MISSED keeps climbing

Updates are being lost on the way. MISSED is a running total, so a steady
climb means it is happening now; a fixed number means it happened once.

  • CRC_ERRORS climbing too — a physical problem. Termination, bias, cable
    length, or a noisy environment.
  • NOISE_BYTES climbing — a floating bus or a baud mismatch.
  • Both quiet, MISSED still climbing — the network is saturated. Check
    PENDING_OPS and ROTATION; a rotation that has grown a lot means the
    ring is busy. Widen the deadbands, lengthen the intervals, or move fast values
    to BEEBUS_TP_PUBLISH_ALL so one frame serves every listener.

Everything works, but it is slow

Values do arrive and nothing reports an error — they just take longer than you
expected. Read ROTATION on BEEBUS_NODE_STATUS and divide by your node count.

  • About four times your task interval per node — normal, and it is the task
    interval you are paying for, not the network. A PLC only looks at the bus once
    per scan, so every hop of the token costs a scan.
    10 - Scan rate explains it and gives the fix: the node
    block and its blocks in their own fast task, the rest of the program left
    alone.
  • Much larger than that — the ring is busy rather than slow. Check
    PENDING_OPS, and see MISSED above.

Reads and writes fail

ERROR on BEEBUS_MB_READ or BEEBUS_MB_WRITE. Read STATUS:

BEEBUS_UNKNOWN_NODE that peer is not on the network — or the block ran above the node block
BEEBUS_DUPLICATE_NODE_ID this node stood down; another has its ID
BEEBUS_NOT_MAPPED the peer has nothing bound at that address
BEEBUS_TIMEOUT a confirmed write went unacknowledged after every retry
BEEBUS_NODE_LOST the peer left before it was delivered
BEEBUS_QUEUE_FULL too much outstanding — almost always REQ held high
BEEBUS_INVALID_ARGUMENT wrong table for the type, or a count Modbus disallows

BEEBUS_QUEUE_FULL is nearly always REQ. It is edge-triggered. Holding it
TRUE fires once, but a program that sets it every scan from a level rather
than an edge fills the queue. Use a step counter — see
08 - Patterns.

BEEBUS_NOT_MAPPED on a range — the peer has some of the addresses but
not all. BEEBUS_MB_MAP on that node takes COUNT addresses from ADDRESS; check the
whole span you are asking for is inside it.

BUSY never clears

BUSY stuck TRUE with no DONE and no ERROR means the block is waiting for
something that is not coming.

Check the peer is ALIVE. A confirmed write to a node that vanished mid-flight
reports BEEBUS_NODE_LOST once the ring notices, which can take a few turns —
give it ROTATION × a few before concluding it is stuck.

If it never clears at all, note the PEER and ADDRESS and raise it: a block
that waits forever is a defect, not a configuration.

The safe state never applies

SAFE_APPLIED never pulses.

  • FAILSAFE := TRUE on the node block? Without it, ON_LOSS does nothing.
    This is the usual answer.
  • ON_LOSS := BEEBUS_MB_RESET_TO_VALUE? BEEBUS_MB_HOLD_LAST_VALUE is the default and
    is a no-op by design.
  • Is it a single value on a writable table? A range has no one safe value
    and a string has no numeric one, so those ignore ON_LOSS.
  • Has a peer actually written it? The safe state applies when the peer that
    was driving an address goes quiet. An address nobody ever wrote has no driver
    to lose.

Everything worked, then one node was replaced

A new node with the same ID as the old one. Check for
BEEBUS_DUPLICATE_NODE_ID first — if the old device is still powered somewhere
on the segment, the new one stands down.

Subscriptions re-establish themselves. When a peer rejoins, subscriptions to
it are re-issued automatically. You do not need to restart the subscribers.

Buffered topics deliver their history. If the replaced node owned a buffered
topic, its subscribers receive what accumulated, oldest first, each carrying the
age it was taken at. MISSED may jump if the buffer overflowed while it was
away — that is the loss being reported honestly rather than hidden.

Nothing above fits

Turn on DEBUG_ENABLE on BEEBUS_NODE_STATUS and read the runtime console. It prints
the protocol's own running commentary — joins, token passes, refusals and why.
It is read once at start-up, so set it and download rather than toggling it
live. On a ModBee Node it prints only in a firmware built with
BEEBUS_ENABLE_DEBUG defined.

Then check these three numbers together on every node, at the same moment:

what a disagreement means
MEMBERS nodes disagreeing about the count means a one-way link — one can hear the other but not the reverse
ROTATION wildly different figures mean the nodes are not in the same ring
CRC_ERRORS rising on one node only points at that node's wiring

STATUS says BEEBUS_WRONG_TASK

The block is in a different task from its node. It does nothing until it is
moved: OpenPLC runs each task on a thread of its own, and a block in another
task would be inside the node while the node's own scan is. Move it into the
node's program, and hand your application the value through a global — see
10 - Scan rate.